14
TROUBLESHOOTING
8
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the control board of outdoor unit. Actions to be taken for service,
which depends on whether or not the trouble is reoccurring at service, are summarized in the table below. Check the contents
below before investigating details.
8-1. TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The trouble is reoccurring.
Displayed
Judge what is wrong and take a corrective action according to
“8-3. Self-diagnosis action table”.
Not displayed
Conduct troubleshooting and ascertain the cause of the
trouble.
The trouble is not reoccurring.
Logged
1
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc. Re-
check the symptom, and check the installation environment,
refrigerant amount, weather when the trouble occurred,
matters related to wiring and etc.
2
Reset error code logs and restart the unit after
fi
nishing
service.
3
There is no abnormality in electrical component, controller
board, and etc.
Not logged
1
Re-check the abnormal symptom.
2
Conduct troubleshooting and ascertain the cause of the
trouble.
3
Continue to operate unit for the time being if the cause is
not ascertained.
4
There is no abnormality concerning of parts such as
electrical component, controller board, and etc.