Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10
~30
)
Thermistor (TH3)
<Outdoor pipe>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Outdoor>
Thermistor (TH8)
<Heatsink>
Thermistor (TH32)
<Outdoor pipe>
Thermistor (TH33)
<Outdoor pipe>
Normal
160k
~410k
4.3k
~9.6k
39k
~105k
TH4
TH3
TH6
TH7
TH32
TH33
TH8
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
)
Solenoid valve coil
<Four-way valve>
(21S4)
Motor for compressor
(MC)
Linear expansion valve
(LEV-A/LEV-B/LEV-C)
Normal
Abnormal
Open or short
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20
)
Normal
Gray - Black
Gray - Red
Gray - Yellow
Gray - Orange
Abnormal
46
$
3
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
)
Solenoid valve coil
<Bypass valve>
(SV)
Refer to next page.
Fan motor
(MF1,MF2)
HRP100, 125Y
HRP71, 100V
0.188
0.302
Measure the resistance between the terminals with a tester.
(Winding temperature 20
)
Normal
Abnormal
Open or short
Normal
Abnormal
Open or short
W
V
U
1435
$
150
1197
$
10
11-6. HOW TO CHECK THE PARTS
PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2
PUHZ-HRP71VHA2R1 PUHZ-HRP100VHA2R1 PUHZ-HRP100YHA2R1 PUHZ-HRP125YHA2R1
PUHZ-HRP100VHA2R2