86
Function
Settings
No.
Mode
No.
Setting
: Initial setting (Factory setting)
- : Not available
4-Way
cassette
Ceiling
concealed
Wall mounted
PLA-BA(2)(3)
PEAD-EA(2)
PEAD-GA
PKA-GAL
PKA-FAL(2)
Filter sign
100h
1
2500h
07
2
No filter sign indicator
3
Air flow
Quiet
1
-
-
(Fan speed)
Standard
08
2
-
-
High ceiling
3
-
-
No.of air outlets
4 directions
1
-
-
3 directions
09
2
-
-
2 directions
3
-
-
Optional high efficiency
Not supported
10
1
-
-
filter
Supported
2
-
-
Vane setting
No vanes (Vane No.3 setting : PLA only)
1
-
-
Vane No.1 setting
11
2
-
-
Vane No.2 setting
3
-
-
Energy saving air
Disabled
12
1
-
-
flow (Heating mode)
Enabled
2
-
-
-
-
Optional humidifier
Not supported
13
1
-
-
(PLA only)
Supported
2
-
-
Vane differential setting
No.1 setting (TH5: 24-28
)
1
-
in heating mode
No.2 setting (Standard, TH5:28-32
)
14
2
-
(cold wind prevention)
No.3 setting (TH5: 32-38
)
3
-
Swing
Not available Swing
23
1
-
Available
Wave air flow
2
-
Set temperature in heating Available
Temperature correction: Valid
24
1
mode (4 deg up)
+
1
Not available
Temperature correction: Invalid
2
Fan speed when the
Extra low
1
heating thermostat is OFF Stop
25
2
Set fan speed
3
Fan speed when the
Set fan speed
27
1
cooling thermostat is OFF Stop
2
Detection of abnormality of Available
28
1
the pipe temperature (P8) Not available
2
}
PLA
}
PLA
+
1 PKA-HAL/KAL : 2 deg up
PKA-HAL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PKA-KAL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
(2) Functions are available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to
4
Set the
indoor unit number of Operating Procedure.
• When setting functions for a simultaneous twin indoor unit system, set the unit number to 01 to 02 for each indoor unit in
case of selecting different functions for each unit referring to
4
setting the indoor unit number of Operating Procedure.
• When setting the same functions for an entire simultaneous twin indoor unit system, set refrigerant address to AL (07 in
case of wireless remote controller) referring to
4
setting the indoor unit number of Operating Procedure.
Mode No.11
Setting No.
Settings
PLA-BA(2)(3)
1
No Vanes
Vane No.3 setting
( Downward position than the standard )
Less smudging
2
Vane No.1 setting
Standard
3
Vane No.2 setting
( Upward position than the standard )
Less draft *
* Be careful of the smudge on ceiling.
Function
Settings
No.
Mode
No.
Setting
: Initial setting
(Factory setting)
Filter sign
100h
1
2500h
07
2
No filter sign indicator
3
External static pressure 35/50/70/100/150Pa
08
10
1
2
Extra low
3
Fan speed during the
heating thermo OFF
Stop
25
1
Set fan speed
2
27
1
2
Detection of abnormality
of the pipe temperature (P8)
1
28
2
Set temperature in heating
24
mode (4 deg up)
Refer to the right table
External static pressure 35/50/70/100/150Pa
Refer to the right table
Available
Not available
Fan speed during the
cooling thermo OFF
Set fan speed
Stop
Available
Not available
External static
pressure
Setting No.
Initial setting
(Factory setting)
35Pa
50Pa
70Pa
100Pa
150Pa
2
3
1
2
3
Mode No. 08 Mode No. 10
1
1
2
2
2
PEAD-RP
•
JA(L)
OCH425D