63
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Minute
Thermo-ON time to error stop
0~999
0~999
(When the time is 100 or more, the hundreds
digit and tens, unit digits are displayed by turns.)
(Example) When 415 minutes
One second interval
4 15
1
ON
2 3 4 5 6
°C
Indoor unit piping temperature / cond. /
Eva. (TH5) indoor 1
–39~88
–39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
°C
Indoor unit piping temperature / cond. /
Eva. (TH5) indoor 2
–39~88
–39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When no indoor unit, “00” is displayed.
1
ON
2 3 4 5 6
°C
Indoor unit piping temperature / cond. /
Eva. (TH5) indoor 3
–39~88
–39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When no indoor unit, “00” is displayed.
1
ON
2 3 4 5 6
°C
Indoor unit piping temperature / cond. /
Eva. (TH5) indoor 4
–39~88
–39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When no indoor unit, “00” is displayed.
●
For A-control Service Tool [ PAC-SK52ST ]
[Operation for
A-control Service Tool
]
1. By operating the dip switch SW2 on A-control Service Tool, the digital display of light-emitting diode (LED1) indicates the
operation mode and types of inspection with a two-digit number and symbol.
2. After the inspection, A-control Service Tool shall be removed out of outdoor unit control board.
OC379F