background image

OPERATING PROCEDURE

78

PHOTOS

  4. Removing the thermistor <Outdoor 2-phase pipe> (TH6)

 

(1) Remove the service panel. (See Figure 1)

 

(2) Remove the top panel. (See Figure 1)

 (3) 

 

Disconnect the connector TH3/TH6 (red) on the controller 
circuit board in the electrical parts box.

 (4) 

 

Loosen the clamp for the lead wire in the rear of the 
electrical parts box.

 (5) 

 

Pull out the thermistor <Outdoor 2-phase pipe> (TH6) 
from the sensor holder.

  Note:  When replacing thermistor <Outdoor 2-phase pipe> 

(TH6), replace it together with thermistor <Outdoor 
pipe> (TH3), since they are combined together. 
Refer to procedure 5 below to remove thermistor 
<Outdoor pipe>.

  <Except PU(H)-P125, 140YHAR4.UK>

 5.  

Removing the thermistor <Outdoor pipe> (TH3) and 
thermistor <Discharge> (TH4)

 

(1) Remove the service panel. (See Figure 1)

 (2) 

 

Disconnect the connectors, TH3/TH6 (red) and TH4 (white), 
on the controller circuit board in the electrical parts box.

 

(3) Loosen the clamp for the lead wire. 

 (4) 

 

Pull out the thermistor <Outdoor pipe> (TH3) and 
thermistor <Discharge> (TH4) from the sensor holder.

 Note:  When replacing thermistor <Outdoor pipe> (TH3), 

replace it together with thermistor <Outdoor 2-phase 
pipe> (TH6), since they are combined together. 
Refer to procedure 4 above to remove thermistor 
<Outdoor 2-phase pipe>.

Photo 5

Thermistor 
<Discharge> 
 (TH4)

Thermistor <Outdoor pipe> 
(TH3)

Photo 4

Thermistor 
<Outdoor 2-phase pipe>
(TH6)

Clamp

Electrical 
parts box

 <PU(H)-P125, 140YHAR4.UK>

 5.  

Removing the thermistor <Compressor surface> (TH4)

 

(1) Remove the service panel. (See Figure 1)

 (2) 

 

Disconnect the connectors, TH3/TH6 (red) and TH4 (white), 
on the controller circuit board in the electrical parts box.

 

(3) Loosen the clamp for the lead wire. 

 (4) 

 

Pull out the thermistor <Compressor surface> (TH4) from 
the sensor holder.

Note:  When replacing thermistor <Outdoor pipe> (TH3), 

replace it together with thermistor <Outdoor 2-phase 
pipe> (TH6), since they are combined together. 

Refer to procedure 4 above to remove thermistor 
<Outdoor 2-phase pipe>.

Thermistor <Compressor surface> 
(TH4)

<Except PU(H)-P125, 140YHAR4.UK>

<PU(H)-P125, 140YHAR4.UK>

OC379F

Содержание PU-P100VHA

Страница 1: ...oor unit Model names PU P71VHA PUH P71VHA PU P71YHA PUH P71YHA PU P100VHA PUH P100VHA PU P100YHA PUH P100YHA PU P125YHA PUH P125YHA PU P140YHA PUH P140YHA PU H P71VHA 1 UK PU H P71VHA 2 UK PU H P71YHA 1 UK PU H P71YHA 2 UK PU H P100VHA 1 UK PU H P100VHA 2 UK PU H P100YHA 1 UK PU H P100YHA 2 UK Note This manual describes only service data of the outdoor units RoHS compliant products have G mark on ...

Страница 2: ... PU P71YHA1 UK PU P100YHA1 UK PU P71YHA 2 UK PU P100YHA 2 UK PU P71YHAR3 UK PU P100YHAR3 UK PUH P71VHA UK PUH P100VHA UK PUH P125YHA UK PUH P140YHA UK PUH P71VHA1 UK PUH P100VHA1 UK PUH P125YHA1 UK PUH P140YHA1 UK PUH P71VHA 2 UK PUH P100VHA 2 UK PUH P125YHA 2 UK PUH P140YHA 2 UK PUH P71VHAR3 UK PUH P100VHAR3 UK PUH P125YHAR3 UK PUH P140YHAR3 UK PUH P71YHA UK PUH P100YHA UK PUH P125YHAR4 UK PUH P1...

Страница 3: ... UK PUH P100VHA 2 UK PUH P100VHAR3 UK PUH P100YHA 2 UK PUH P100YHAR3 UK PUH P125YHA 2 UK PUH P125YHAR3 UK PUH P140YHA 2 UK PUH P140YHAR3 UK Fan grille has been changed Structural parts have been changed Munsell 5Y 7 1 3Y 7 8 1 1 PU P71VHA UK PU P71VHA1 UK PU P71YHA UK PU P71YHA1 UK PU P100VHA UK PU P100VHA1 UK PU P100YHA UK PU P100YHA1 UK PU P125YHA UK PU P125YHA1 UK PU P140YHA UK PU P140YHA1 UK P...

Страница 4: ... PEAD RP60 71 100GA PEAD RP60 71 100GA 1 UK HWE0506 PEAD RP50 60 71 125 140EA PEAD RP35 100EA2 PEAD RP50 60 71 125 140EA 1 UK PEAD RP35 100EA2 1 UK HWE0521 2 2 TECHNICAL DATA BOOK Manual No OCS07 PKA RP35 50HAL OCH453 OCB453 OCH452 OCB452 OCH454 OCB454 HWE08130 BWE08240 PKA RP35 50HAL PKA RP60 71 100KAL PCA RP50 60 71 100 125 140KA PEAD RP35 50 60 71 100 125 140JA L PKA RP60 71 100KAL TH PCA RP50 ...

Страница 5: ...rant Handle tools with care If dirt dust or moisture enter into refrigerant cycle that can cause deterioration of refrigerant oil or malfunction of com pressor Do not use a charging cylinder If a charging cylinder is used the composition of refrigera nt will change and the efficiency will be lowered Flare tool Electronic refrigerant charging scale Vacuum pump adaptor Size adjustment gauge Gauge ma...

Страница 6: ... Specifications 1 Gauge manifold Only for R410A Use the existing fitting specifications UNF1 2 Use high tension side pressure of 5 3MPa G or over 2 Charge hose Only for R410A Use pressure performance of 5 09MPa G or over 3 Electronic scale 4 Gas leak detector Use the detector for R134a R407C or R410A 5 Adaptor for reverse flow check Attach on vacuum pump 6 Refrigerant charge base 7 Refrigerant cyl...

Страница 7: ... Tool exclusive for R410A Tool exclusive for R410A Tools for other refrigerants can be used if equipped with adop ter for reverse flow check Tools for other refrigerants can be used by adjusting flaring dimension Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrige...

Страница 8: ...problems Heretofore it is completely eliminated This unique system improves the quality and reliability of the work done It also helps to speed up the installation time PU H P71VHA 1 UK PU H P71VHA 2 UK PU H P71YHA 1 UK PU H P71YHA 2 UK PU H P100VHA 1 UK PU H P100VHA 2 UK PU H P100YHA 1 UK PU H P100YHA 2 UK PU H P125YHA 1 UK PU H P140YHA 1 UK PU H P125YHA 2 UK PU H P140YHA 2 UK 4 FEATURES PU H P71...

Страница 9: ...Heating 11 98 4 28 Cooling 15 07 5 39 Heating 14 48 5 18 Single 50Hz 230V 3Phase 50Hz 400V 4wires OUTDOOR UNIT REFRIGERANT PIPING A A A kW W kW min CFM dB dB mm in mm in mm in kg lbs kg lbs L mm in mm in Power supply phase cycle voltage Running current Max current Protection current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices Crankcase heater H...

Страница 10: ...e thermo 25 0 110 65 2290 50 94 207 4 4 9 7 Single 50Hz 230V 3Phase 50Hz 400V 4wires OUTDOOR UNIT REFRIGERANT PIPING A A A kW W kW min CFM dB dB mm in mm in mm in kg lbs kg lbs L mm in mm in Power supply phase cycle voltage Running current Max current Protection current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices Crankcase heater Heat exchanger...

Страница 11: ...3YCAMT at 20 C 4 64 4 64 4 64 0 63 1 55 3 32 3 32 3 32 NN33VAAMT 0 68 1 80 PU H P71VHA UK PU H P71VHA1 UK PU H P71VHA 2 UK PU H P71VHAR3 UK PU H P71YHA UK PU H P71YHA1 UK PU H P71YHA 2 UK PU H P71YHAR3 UK NN40YCAMT NN40VAAMT PU H P100VHA UK PU H P100VHA1 UK PU H P100VHA 2 UK PU H P100VHAR3 UK PU H P100YHA UK PU H P100YHA1 UK PU H P100YHA 2 UK PU H P100YHAR3 UK U V U W W V Unit Compressor model Win...

Страница 12: ...PL dB 52 LINE PU H P125YHA UK PU H P125YHA1 UK PU H P125YHA 2 UK PU H P125YHAR3 UK PU H P125YHAR4 UK 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 μbar BAND CENTER FREQUENCIES Hz PU H P71YHA UK PU H P71YHA1 UK PU H P71YHA 2 UK PU H P71YHAR3 UK PU...

Страница 13: ... 07 5 39 3 16 32 2 0 91 9 3 78 2 49 9 4 2 5 27 19 13 4 35 24 0 78 0 06 14 48 5 18 2 67 27 2 0 74 7 5 81 4 40 9 4 0 5 20 15 42 2 7 6 6 79 3 00 30 6 0 75 7 7 80 5 38 7 2 4 5 27 19 12 3 35 24 0 74 0 05 6 57 2 97 30 3 0 74 7 5 78 1 46 2 0 5 5 20 15 46 1 7 6 8 55 3 05 31 1 0 94 9 6 78 0 49 9 0 8 5 27 19 11 2 35 24 0 70 0 08 8 45 3 68 37 5 0 61 6 2 82 4 56 3 1 2 5 20 15 51 6 7 6 1 50 230 0 79 1 3 50 230...

Страница 14: ...e Intake air temperature Cooling 8 000 2 83 1 50 230 0 79 1 3 50 230 400 12 03 4 29 2 99 30 4 0 79 8 0 76 9 49 7 3 8 5 27 19 12 8 35 24 0 74 0 11 Cooling 10 000 3 53 1 50 230 0 92 1 3 50 230 400 15 07 5 39 3 16 32 2 0 91 9 3 78 2 49 9 4 2 5 27 19 13 4 35 24 0 78 0 06 Cooling 12 300 4 36 1 50 230 0 92 3 50 400 6 79 3 00 30 6 0 75 7 7 80 5 38 7 2 4 5 27 19 12 3 35 24 0 74 0 05 Cooling 14 200 5 41 1 ...

Страница 15: ...ar details are given in the installation manuals etc O v e r 1 0 m m O v e r 1 0 0 m m FREE Over10 500 500 Over100 Dimensions of space needed for service access are shown in the below diagram Service space 30 Please secure the unit firmly with 4 foundation M10 bolts Bolts and washers must be purchased locally Foundation bolt height Handle for moving Side Air Intake Front piping cover Rear piping c...

Страница 16: ...nt LIQUID pipe connection FLARE W 9 52 3 8F 1 Indication of STOP VALVE connection location Example of Notes Piping Knockout Hole Details 1 FREE SPACE Around the unit 2 SERVICE SPACE 3 FOUNDATION BOLTS 4 PIPING WIRING DIRECTIONS Piping and wiring connections can be made from 4 directions Front Right Rear and Below O v e r 1 0 0 0 m m O v e r 1 5 0 m m O v e r 1 0 m m O v e r 1 0 m m FREE 30 FOUNDAT...

Страница 17: ...W 9 2 40 45 65 92 27 55 23 73 63 Rear piping hole Knockout Rear trunking hole Knockout Power supply wiring hole 2 W27Knockout W 9 2 Over Over Less than Piping and wiring connections can be made from 4 directions front right rear and below 4 PIPING WIRING DIRECTIONS 3 FOUNDATION BOLTS 2 SERVICE SPACE 1 FREE SPACE Around the unit The diagram below shows a basic example Explantion of particular detai...

Страница 18: ...PACE 3 FOUNDATION BOLTS 4 PIPING WIRING DIRECTIONS Piping and wiring connections can be made from 4 directions front right rear and below 30 FOUNDATION 150 500 500 10 Service space 600 175 175 330 417 42 66 53 56 45 19 28 370 2 U Shaped notched holes Foundation Bolt M10 2 12 36 Oval holes Foundation Bolt M10 Installation Feet 30 45 40 65 92 27 55 23 73 63 Rear piping hole Knockout Rear trunking ho...

Страница 19: ... C5 CH 52C 21S4 63H 49C TB1 LEV O B COMPRESSOR INNER THERMOSTAT FAN MOTOR INNER THERMOSTAT THERMISTOR MF CAPACITOR MC CAPACITOR CRANKCASE HEATER MC CONTACTOR 4 WAY VALVE SOLENOID COIL HIGH PRESSURE PROTECT SWITCH INNER THERMOSTAT FOR MC TERMINAL BLOCK LINEAR EXPANSION VALVE OUTDOOR CONTROLLER BOARD SYMBOL FUSE1 O B FUSE2 O B FUSE3 O B FUSE4 O B X51 O B X52 O B F C O B SW1 O B SW4 O B SW5 O B JA JB...

Страница 20: ...C A1 A2 B1 A1 A2 B1 S C R R E D W H T B L U C5 2 T 1 6 T 3 1 L 1 5 L 3 52C B L U R E D L N TB1 POWER SUPPLY N 230V 50Hz Y L W S1 S2 S3 O R N B R N S1 S2 S3 TB4 INDOOR UNIT C3 MF MF3 WHT 52C A1 A2 63H CH 21S4 52C PNK CH BLU 21S4 GRN X51 X52 1 1 1 1 3 3 3 1 3 CN31 CNM ON OFF F C CT SW5 SW1 SW4 1413121110 9 8 7 6 5 4 3 2 1 LED1 GRN LED2 RED CNVMNT WHT CNMNT WHT CNVEV WHT TH4 WHT TH3 TH6 RED 3 2 1 1 2...

Страница 21: ...t MC MF TH3 TH4 TH6 C3 C4 CH 52C 21S4 SV 63H 51C TB1 LEV TB2 63L O B COMPRESSOR FAN MOTOR INNER THERMOSTAT THERMISTOR MF CAPACITOR MF CAPACITOR CRANKCASE HEATER MC CONTACTOR 4 WAY VALVE SOLENOID COIL BYPASS VALVE SOLENOID COIL HIGH PRESSURE PROTECT SWITCH THERMAL RELAY TERMINAL BLOCK LINEAR EXPANSION VALVE TERMINAL BLOCK LOW PRESSURE PROTECT SWITCH OUTDOOR CONTROLLER BOARD SYMBOL FUSE1 O B FUSE2 O...

Страница 22: ...ON NAME MODEL J1 J2 J3 J4 J5 J6 PUH P71YHA PU P71YHA PUH P100YHA PU P100YHA PUH P125YHA PU P125YHA PUH P140YHA PU P140YHA with jumper wire without jumper wire 1 14 CN31 J1 FUSE3 E E S3 L1 L2 L3 4 S S2 S1 POWER SUPPLY 3N 400V 50Hz INDOOR UNIT TB2 S1 S2 S3 TB1 L1 L2 L3 N RED CN5 WHT 3 LED2 SW1 LED3 LED4 TB7 LED1 LED5 2 1 1 CND WHT CN2M WHT GRN M NET A B S When M NET adaptor is connected 5 5 1 1 2 3 ...

Страница 23: ...Power supply Outdoor unit input capacity 1 Main switch Breaker Max Permissive System Impedance Outdoor unit power supply Outdoor unit power supply earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit earth Remote controller Indoor unit 3 Outdoor unit L N 4 Outdoor unit L1 N L2 N L3 N Indoor unit Outdoor unit S1 S2 4 Indoor unit Outdoor unit S2 S3 4 Remote controller Indoor unit 4 Wiring Wire ...

Страница 24: ...e 50 Hz 230 V 16 A 2 Min 1 5 1 Min 1 5 2 Min 0 3 2 0 3 Non polar AC 230 V DC24 V DC12 V Circuit rating Wiring Wire No size mm 2 If the indoor and outdoor units have separate power supplies refer to the table below Change the indoor unit electrical box wiring referring to the figure in the right and the Jumper wire JB settings of the outdoor unit control board Please turn on the power supply of the...

Страница 25: ... S1 S2 S3 Open Connect S1 and S3 to the opposite angle Not applicable Because center wire has no cover finish From left to right S1 Open S2 S3 Polarity L m 5 3C Flat cable 2 S1 S2 S3 The Max cable length may vary depending on the condition of installation humidity or materials etc Indoor unit Outdoor unit Outdoor power supply Max 45m 3 1 5 polar 1 Min 1 5 Max 50m 3 2 5 polar 1 Min 2 5 Max 80m 3 2 ...

Страница 26: ...ts on the shield wire noise may enter into the shield wire because the earth wire and shield wire form one circuit and the electric potential difference occurs due to the impedance difference among earth ing spots In case of single spot earthing noise does not enter into the shield wire because the earth wire and shield wire do not form one circuit To avoid communication errors caused by noise mak...

Страница 27: ...resses are 00 1 2 34 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 50 M NET Address No Setting example Switch setting SW11 ones digit SW12 tens digit OFF ON 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3...

Страница 28: ...ooling Refrigerant flow in heating Linear expansion valve Thermistor TH4 Muffler Ball valve 50 Strainer 100 Strainer Strainer 40 100 Strainer PUH P125YHA UK PU P125YHA UK PUH P125YHA1 UK PU P125YHA1 UK PUH P140YHA UK PU P140YHA UK PUH P140YHA1 UK PU P140YHA1 UK PUH P125YHA 2 UK PU P125YHA 2 UK PUH P140YHA 2 UK PU P140YHA 2 UK PUH P125YHAR3 UK PU P125YHAR3 UK PUH P140YHAR3 UK PU P140YHAR3 UK Bypass...

Страница 29: ... W3 8 4 way valve Service port check High pressure protect switch Linear expansion valve Muffler Thermistor TH4 Refrigerant flow in cooling Refrigerant flow in heating Ball valve 50 Strainer Strainer 100 Strainer 100 Strainer 100 Stop valve with service port Low pressure protect switch Strainer 40 Thermistor TH3 Capillary tube 4 0 3 0 L200 2 Thermistor TH6 Distributor Unit mm OC379F ...

Страница 30: ...finishing service There is no abnormality concerning of parts such as electrical component controller board remote controller and etc Re check the abnormal symptom Conduct trouble shooting and ascertain the cause of the inferior phenomenon according to 11 5 Troubleshooting of problems Continue to operate unit for the time being if the cause is not ascertained There is no abnormality concerning of ...

Страница 31: ...ternately F1 After startup is displayed green once and red twice blink alternately F3 F5 F9 After startup is displayed green twice and red once blink alternately EA Eb After startup is displayed only green lights up 00 After startup is displayed only green lights up 00 indicates digital display 2 Press TEST button twice 1 Turn on the main power supply 3 Press OPERATION SWITCH button 4 Press AIR DI...

Страница 32: ... digital indicator LED 1 on the outdoor substrate If this happens rewire correctly Measure the impedance between power terminals Single phase L N 3 phase L1 L2 L3 and the ground with a 500V Megger and check that it is 1 0M or more Do not operate the equipment if measurement is less than 1 0m Never conduct this operation on the out door connection wiring terminals S1 S2 S3 as this causes damage Whe...

Страница 33: ...hat stores error codes the latest check code can be recalled even if it is cancelled by the remote controller or power is shut off Check the error code history for each unit using the remote controller Switch to self diagnosis mode Press the CHECK button twice within 3 seconds The display content will change as shown below Set the unit number or refrigerant address you want to diagnose Press the T...

Страница 34: ...ycontentwill change as shown below Press the FILTER button to start self diagnosis Remote controller self diagnosis result When the remote controller is functioning correctly Check for other possible causes as there is no problem with the remote controller When the remote controller malfunctions Error display 1 NG flashes The remote controller s transmitting receiv ing circuit is defective The rem...

Страница 35: ...celled Procedure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor to the indoor unit and press the HOUR button 4 Point the remote controller at the sensor to the indoor unit and press the ON OFF button Malfunction diagnosis method at maintenance service 11 3 4 Malfunction diagnosis method by wireless remote controller In case of trouble dur...

Страница 36: ...heck codes Output pattern A Beeper sounds OPERATION INDICATOR lamp blinks Check code Symptom Remark Number of times Wireless remote controller Wired remote controller Beeper sounds OPERATION INDICATOR lamp blinks Check code Number of times Wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit comm...

Страница 37: ...controller board 2 Disconnection or contact failure of 51CM 3 Defective 51CM defective parts 4 Defective outdoor controller 1 Check connecting wire 2 Check connecting wire 3 Check continuity by tester Replace the parts if the parts are defective 4 Replace outdoor controller board None 1 No voltage is supplied to terminal block TB1 of indoor unit a Power supply breaker is off b Contact failure or d...

Страница 38: ... twin triple or quadruplet units 8 Two or more outdoor units has refrigerant address 0 In case of group control 9 Outdoor power supply board is defective Indoor outdoor unit connector mis wiring excessive number of units 5 units or more 1 Outdoor controller board can automatically check the number of connected indoor units Abnormal if the number of connected indoor units can not be set within 4 mi...

Страница 39: ...has detected a current which is lower than the detected current specified in the table below for 0 4 0 5 second 1 Shortage of refrigerant 2 Abnormal pressure degrada tion by pump down operation 3 V phased open phase of com pressor 4 Abnormal compressor Not abnormal if V is instantly displayed when the main power is off 1 Check if refrigerant pressure is not degraded 2 Check current of compressor o...

Страница 40: ...rotection over load opera tion protection abnormal fan Abnormal if pipe thermistor detects the value that exceeds set value during com pressor operation P71 P140 70 1 In cooling mode defective outdoor fan fan motor or short cycle of air path 2 Defective thermistor 3 Defective outdoor controller board 1 Check outdoor fan fan motor Refer to 11 6 24 Turn the power off and operate again to check if U4...

Страница 41: ...eceive anything normally for 3 minutes 1 Contact failure of indoor out door unit connecting wire 2 Defective communication cir cuit of indoor controller board 3 Defective communication cir cuit of indoor controller board 4 Noise has entered indoor out door unit connecting wire 1 Check disconnection or looseness of indoor outdoor unit connecting wire of indoor or out door units 234 Turn the power o...

Страница 42: ...ntroller that detected abnormality 1 Transmission processor could not transmit because short cycle voltage of noise and the like have entered into transmission wire continuously 2 Transmission quantity has increased and transmission is not possible because there was wiring mistake of terminal block for transmission wire TB3 and terminal block for central control TB7 in outdoor unit 3 Transmission ...

Страница 43: ...ective then turn off the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for 2 minutes or more and turn the power on again If there was no trouble with 1 5 above in single refrigerant system one outdoor unit controller of displayed address or attribute is defective If there was no trouble with 1 5 above in dif ferent refrigerant system two or more outdoor ...

Страница 44: ... or LOSSNAY 7 If displayed address or attribute is non existent 1 The unit of former address does not exist as address switch has changed while the unit was energized 2 Abnormality is detected when indoor unit transmit ted because the address of FRESH MASTER and LOSSNAY are changed after sequential operation of FRESH MASTER and LOSSNAY by remote controller M NET NO RESPONSE Abnormal if a message w...

Страница 45: ...tion from the remote controller the remote controller operation switch will be not accepted for approx 30 seconds Normal operation 4 Even controlling by the wireless remote controller no beep and not working Display is available on the wireless remote controller 1 The pair number settings of the wireless remote controller and indoor control PCB are mismatched 2 Disconnecting of wireless receiving ...

Страница 46: ...and remove dust or dirt away 2 Clean the heat exchanger Rising the indoor piping temperature and outlet pressure means clogging in the heat exchanger 3 Remove screen in the air duct air outlet intake 4 Check if gas leaks or not in the piping joint 5 Operating condition check in the refriger ant cycle 6 Since outlet temperature and indoor heat exchanger temperature does not rise measure the outlet ...

Страница 47: ...l that the outdoor unit performs to maintain the optimum operation status Problem Solution A ticking noise is heard from inside of the unit This sound is made when internal parts of the unit expand or contract when the temperature changes An odour is detected in the room This is caused when the unit expels odours that have been absorbed from the walls carpets furniture or clothing A white mist is ...

Страница 48: ...g felt at this time the up down vane is automatically set to horizontal blow When STAND BY is released the up down vane returns to the setting specified by the remote controller Problem Solution DEFROST is displayed no air comes out the unit Frost adheres to the outdoor unit when the outside air temperature is low and the humidity is high This display indicates that the DEFROST operation is being ...

Страница 49: ...red see NOTE below Wait until power is restored then press the POWER ON OFF button to turn the unit on Unit discharges air well but fails to cool or heat the room well Liquid crystal display indicates that the unit operates Improper temperature setting After checking the temperature setting Filters are clogged Clean the filter and resume opera tion Outdoor unit s intake or outlet is obstructed Rem...

Страница 50: ...ER CH Measure the resistance between the terminals with a tester Surrounding temperature 20 Normal 1450 150 Abnormal Open or short Solenoid valve coil SV Bypass valve For P125 P140 1500 150 1435 150 Refer to 6 2 Measure the resistance between the terminals with a tester Winding temperature 20 Normal Abnormal Open or short W V U Measure the resistance between the terminals with a tester Surrounding...

Страница 51: ...H6 0 15k 10 9 6k 20 6 3k 25 5 2k 30 4 3k 40 3 0k 1 1 Thermistor R120 7 465k 2 B constant 4057 2 Rt 7 465exp 4057 273 t 393 1 1 20 250k 30 160k 40 104k 50 70k 60 48k 70 34k 80 24k 90 17 5k 100 13 0k 110 9 8k High temperature thermistor Thermistor Discharge Compressor surface TH4 0 10 20 30 40 50 20 10 0 10 20 30 40 50 Temperature Resistance k 500 400 300 200 100 0 25 50 75 100 120 Temperature Resis...

Страница 52: ...more noise can be heard than normal situation No noise is heard when the pulse number moves from B to A in case coil is burn out or motor is locked by open phase Noise can be detected by placing the ear against the screw driv er handle while putting the screw driver to the linear expansion valve LEV M 1 6 4 4 3 2 1 1 Gray Orange Red Yellow Black 3 4 5 6 Connector CNLEV DC12V Outdoor controller boa...

Страница 53: ...Be sure to attach the stopper A How to attach the coil Hold the lower part of the main body shown as A firmly so that the main body does not move and attach the coil by inserting it downward into the main body Then securely attach the coil stop per to main body At this time be careful that stress is not added to lead wire and main body is not wound by lead wire If the stopper is not firmly attache...

Страница 54: ...n 1 and 3 220V 240V AC CH Crankcase heater Between 1 and 3 220V 240V AC SV Baypass valve solenoid coil Between 1 and 3 220V 240V AC 2 21S4 R V coil Between 1 and 3 220V 240V AC 1 63L Low pressure switch 3 1 21S4 is only for PUH type 2 SV is only for PUH P125 P140 3 63L is only for PU H P125 P140 4 Themal relay is only for PU H P71 P100 P125 P140Y Communication power supply D71 Voltage developed ac...

Страница 55: ... operation during heating emergency operation 5 Cool emergency operation must be within 10 hours at most It may cause heat exchanger frosting in the indoor unit 6 After completing the emergency operation return the switch setting etc in former state 3 How to operate the emergency operation 1 Turn off the main power supply 2 Turn on the emergency switch SWE in the indoor controller board 3 Short ci...

Страница 56: ... 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 8 9 10 11 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 12 13 14 15 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 Compulsory defrosting should be done as follows 1Change the DIP SW1 1 in the outdoor controller board OFF ON compulsory defrosting start According to the 1 operation Heat mode setting Compressor operating The defrosting starts wh...

Страница 57: ...N31 JA JB No Function Effective timing Action by the switch operation Switch of single phase and 3 phase power supply Switch of cooling only heat pump When power supply ON When power supply ON Single phase 3 phase When power supply ON Heat pump Cooling only Capacity switch Emergency operation Emergency operation Normal Normal When power supply ON Separate inoor outdoor power supply When power supp...

Страница 58: ...ode The units digit Relay output O C H d Display 0 1 2 3 4 5 6 7 Compressor 4 way valve Bypass solenoid valve ON ON ON ON ON ON ON ON ON ON ON ON OFF COOL HEAT DEFROSTING Display Inspection unit 0 1 2 3 4 Outdoor unit Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 1 second interval Abnormal unit number Abnormal code 2Error postponing display Compressor stop by the protection device workin...

Страница 59: ...cond interval 1 50 Step 100 times 10 hours 0 16 0 9999 When the number of times is 100 or more the hundreds digit and tens unit digits are displayed by turns Example When 42500 times One second interval 4 25 0 9999 When the time is 100 or more the hundreds digit and tens unit digits are displayed by turns Example When 2450 hours One second interval 2 45 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6...

Страница 60: ... of error unit number and code 0 216 When the temperature is 100 or more the hundreds digit and tens unit digits are displayed by turns Example When 130 One second interval 1 30 A Code display Code display 0 40 When no error history 0 and and displayed by turns When no error history 0 and and displayed by turns 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Thermo ON time 0 999 Trial run elapsed time 0 120 0 999 W...

Страница 61: ...e Display details 0 H P 1 Cooling only 0 Single phase 2 3 phase Setting details Defrosting switch Display details 0 Normal 1 High humidity region Example When switching cooling and heat pump three phase defrosting normal 20 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Indoor unit piping temperature LIQUID TH2 Indoor 2 39 88 39 88 When the temperature is 0 or less and temperature are displayed by turns When no in...

Страница 62: ... are displayed by turns Step Fan step on error occurring 0 16 0 16 0 255 When the capacity is 100 or more the hundreds digit and tens unit digits are displayed by turns Example When 100 One second interval 1 00 1 ON 2 3 4 5 6 LEV opening on error occurring 0 500 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 0 500 Pulse 39 88 When the thermistor is 0 and less and temperature are displayed by turns Example When 15 ...

Страница 63: ...ndoor unit 00 is displayed 1 ON 2 3 4 5 6 C Indoor unit piping temperature cond Eva TH5 indoor 3 39 88 39 88 When the temperature is 0 C or less and temperature are displayed by turns When no indoor unit 00 is displayed 1 ON 2 3 4 5 6 C Indoor unit piping temperature cond Eva TH5 indoor 4 39 88 39 88 When the temperature is 0 C or less and temperature are displayed by turns When no indoor unit 00 ...

Страница 64: ... of indoor outdoor units Check if a single outdoor unit connects 5 or more indoor units Check if the connectors of 51CM 51C on outdoor controller board are disconnected Check the continuity of connector 51CM 51C with a tester 63L connector open Check connection of 63L 63L connector on outdoor controller board Check the 63L side of connecting wire Check refrigerant pressure Charge additional refrig...

Страница 65: ...oard are disconnected Measure the resistance values of each thermistor TH1 TH2 and TH5 Check if the unit fills the refrigerant at the same amount as specified Check if indoor outdoor units have a short cycle on their air ducts Abnormal low pressure Low pressure switch 63L operated Check stop valve Turn the power off and on again to check if F3 is displayed on restarting If F3 is displayed follow t...

Страница 66: ...aning of Function setting mode02 indoor temperature detecting No Indoor temperature ta No1 Average data of the sensor on all the indoor units Initial setting ta A B 2 ta A B 2 ta A ta A No2 The data of the sensor on the indoor unit that connected with remote controller ta A ta B ta A ta A No3 The data of the sensor on main remote controller ta C ta C ta C ta C OUTDOOR INDOOR REMOTE MAIN REMOTE SUB...

Страница 67: ... Triple indoor unit system set the unit number to 01 to 03 for each indoor unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number When setting the same functions for an entire simultaneous Twin Triple indoor unit system set refrigerant address to AL 07 in case of wireless remote controller referring to 4 setting the indoor unit number PEAD RP JA L...

Страница 68: ...Specify unit No 00 indoor unit Use and Enter the setting Press Specified indoor unit FAN operation Change refrigerant address unit No Switch to function setting mode Press and at the same time with the remote controller stopped 12 1 1 Selecting functions using the wired remote controller First try to familiarize yourself with the flow of the function selection procedure In this section an example ...

Страница 69: ...refrigerant address and unit number may be incorrect so repeat steps and to set the correct ones When grouping different refrigerant systems if an indoor unit other than the one to which the refrigerant address has been set performs fan operation there may be another refrigerant address that is the same as the specified one In this case check the DIP switch of the outdoor unit to see whether such ...

Страница 70: ...controller toward the receiver of the indoor unit and press the button 3 Set the unit number Press the temp button to set the unit number Press 01 to specify the indoor unit whose unit number is 01 Direct the wireless remote controller toward the receiver of the indoor unit and press the button If a unit number that cannot be recognized by the unit is entered 3 beeps of 0 4 seconds will be heard R...

Страница 71: ...itial setting value The automatic mode is displayed when the operation mode is selected OFF The automatic mode is not displayed when the operation mode is selected 4 3 Mode selection setting 1 Remote controller main sub setting To switch the setting press the ON OFF button Main The controller will be the main controller Sub The controller will be the sub controller 2 Use of clock setting To switch...

Страница 72: ... when the operation mode is selected Initial setting value The automatic mode is not displayed when the operation mode is selected The temperature range limit is not active Initial setting value The temperature range can be changed on cooling dry mode The temperature range can be changed on heating mode The temperature range can be changed on automatic mode The remote controller will be the main c...

Страница 73: ...5 10 of the top panel and remove it Figure 1 Top panel fixing screws Top panel Service panel fixing screws Service panel Grill fixing screws Fan grille 2 Removing the fan motor MF 1 Remove the service panel See Figure 1 2 Remove the top panel See Figure 1 3 Remove 5 fan grille fixing screws 5 10 to detach the fan grille See Figure 1 4 Remove a nut for right handed screw of M6 to detach the propell...

Страница 74: ...ipe TH3 Photo 3 Electrical parts box Controller circuit board O B Electrical parts box fixing screws Cover panel Front Cover panel fixing screws Terminal block TB1 Valve bed 3 Removing the electrical parts box 1 Remove the service panel See Figure 1 2 Remove the top panel See Figure 1 3 Disconnect the indoor outdoor connecting wire from termi nal block 4 Remove all the following connectors from co...

Страница 75: ...g screw 5 10 in the rear of the unit and then remove the right side panel 6 Remove the linear expansion valve coil 7 Collect the refrigerant 8 Remove the welded part of linear expansion valve Note 1 Recover refrigerant without spreading it in the air Note 2 The welded part can be removed easily by removing the right side panel Note 3 When installing the linear expansion valve cover it with a wet c...

Страница 76: ... 4 10 and 4 ball valve and stop valve fixing screws 5 16 and then remove the valve bed 7 Remove 3 right side panel fixing screws 5 10 in the rear of the unit and then remove the right side panel 8 Remove 3 separator fixing screws 4 10 and remove the separator 9 Collect the refrigerant 10 Remove the 3 points of the motor for compressor fixing nut using a spanner or a monkey wrench 11 Remove the wel...

Страница 77: ...ure 1 3 Disconnect the indoor outdoor connecting wire from terminal block 4 Remove all the following connectors from controller circuit board fan motor linear expansion valve thermistor Outdoor pipe thermistor Discharge thermistor Outdoor 2 phase pipe high pressure switch solenoid valve coil Four way valve and solenoid valve coil Bypass valve Then remove a screw 4 8 from the valve bad to remove th...

Страница 78: ... the lead wire 4 Pull out the thermistor Outdoor pipe TH3 and thermistor Discharge TH4 from the sensor holder Note When replacing thermistor Outdoor pipe TH3 replace it together with thermistor Outdoor 2 phase pipe TH6 since they are combined together Refer to procedure 4 above to remove thermistor Outdoor 2 phase pipe Photo 5 Thermistor Discharge TH4 Thermistor Outdoor pipe TH3 Photo 4 Thermistor...

Страница 79: ...e bed 4 Remove 4 right side panel fixing screws 5 10 in the rear of the unit and then remove the right side panel 5 Remove the solenoid valve coil Four way valve 6 Collect the refrigerant 7 Remove the welded part of four way valve Note 1 Recover refrigerant without spreading it in the air Note 2 The welded part can be removed easily by removing the right side panel Note 3 When installing the four ...

Страница 80: ...ily by removing the right side panel Note 3 When installing the high pressure switch cover it with a wet cloth to prevent it from heating 100 C or more then braze the pipes so that the inside of pipes are not oxidized Lead wire of high pressure switch High pressure switch 63H Photo 8 11 Removing the low pressure switch 1 Remove the service panel See Photo 1 2 Remove the top panel See Photo 1 3 Rem...

Страница 81: ...otor for compressor inlet and outlet and then remove the compressor Note Recover refrigerant without spreading it in the air 13 Removing the Accumulator 1 Remove the service panel See Figure 1 2 Remove the top panel See Figure 1 3 Remove 2 front cover panel fixing screws 5 10 and remove the front cover panel See Photo 3 4 Remove 2 back cover panel fixing screws 5 10 and remove the back cover panel...

Страница 82: ... 17 31 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 5 10 S70 E10 662 S70 E20 675 S70 E10 668 S70 E30 686 S70 E50 130 S70 30L 655 S70 E10 658 S70 E20 658 S70 E30 662 S70 E30 661 S70 001 699 S70 E10 698 S70 E10 641 S70 E10 655 F ST SCREW SIDE PANEL L FAN GRILLE FRONT PANEL SEPARATOR BASE ASSY MOTOR SUPPORT VALVE BED ASSY HANDLE COVER PANEL FRONT COVER PANEL REAR SIDE PANEL R SERVICE PANEL LABEL REAR GUARD TOP PA...

Страница 83: ...SE ASSY MOTOR SUPPORT VALVE BED ASSY HANDLE COVER PANEL FRONT COVER PANEL REAR SIDE PANEL R SERVICE PANEL LABEL REAR GUARD TOP PANEL HANDLE 5 10 Remarks Drawing No S70 E20 662 S70 E20 675 S70 E20 668 S70 E40 686 S70 E60 130 S70 30L 655 S70 E10 658 S70 E20 658 S70 E40 662 S70 E40 661 S70 001 699 S70 E20 698 S70 E10 641 S70 E10 655 1 15 2 4 5 9 11 14 12 13 6 7 8 10 9 17 3 16 STRUCTURAL PARTS PUH P12...

Страница 84: ...17 TH6 17 TH3 19 20 18 10 11 12 13 14 15 16 FUNCTIONAL PARTS PUH P71VHA YHA UK PUH P100VHA YHA UK PU P71VHA YHA UK PU P100VHA YHA UK 21 26 25 23 24 21 22 25 23 24 P71 P100VHA P71 P100YHA PARTS LIST non RoHS compliant OC379F ...

Страница 85: ...6 S70 E30 401 S70 500 418 S70 E04 411 S70 E41 440 S70 36L 450 S70 E02 413 S70 E10 403 S70 E41 242 S70 E80 401 S70 E90 401 S70 E91 402 S70 E42 202 S70 42H 467 S70 E10 208 S70 E41 408 S70 E51 408 S70 E05 716 S70 E10 716 S70 E04 716 S70 E41 255 S70 E51 255 S70 FV1 315 S70 FY2 315 S70 330 708 S70 440 708 S70 331 708 S70 E41 723 S70 E51 723 PROPELLER FAN NUT FAN MOTOR FAN MOTOR THERMISTOR DISCHARGE COM...

Страница 86: ...3 4 5 8 9 10 11 12 TH4 13 14 15 17 16 TH3 18 19 17 20 21 22 23 24 25 16 TH6 26 6 7 31 30 27 28 29 FUNCTIONAL PARTS PUH P125YHA UK PUH P140YHA UK PU P125YHA UK PU P140YHA UK PARTS LIST non RoHS compliant OC379F ...

Страница 87: ...60 763 S70 E02 004 S70 E20 236 S70 E76 400 S70 E77 400 S70 E04 411 S70 500 418 S70 E43 202 S70 36L 450 S70 42H 467 S70 B01 529 S70 E44 202 S70 E02 413 S70 282 403 S70 E03 242 S70 E90 401 S70 E91 401 S70 E03 403 S70 E43 241 S70 E10 208 S70 H20 209 S70 E61 440 S70 E10 716 S70 E04 716 S70 E41 255 S70 31L 255 S70 FY2 315 S70 640 708 S70 540 708 FAN MOTOR HEAT EXCHANGER TOP PROPELLER FAN NUT HEAT EXCHA...

Страница 88: ... 4 5 6 7 8 9 10 11 12 13 14 15 16 17 G G G G G G G G G G G G G G G G G 31 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 5 10 S70 E10 662 S70 E20 675 S70 E10 668 S70 E30 686 S70 E50 130 S70 30L 655 S70 E10 658 S70 E20 658 S70 E30 662 S70 E30 661 S70 001 699 S70 E10 698 S70 E10 641 S70 E10 655 F ST SCREW SIDE PANEL L FAN GRILLE FRONT PANEL SEPARATOR BASE ASSY MOTOR SUPPORT VALVE BED ASSY HANDLE COVER PANEL FRONT ...

Страница 89: ... COVER PANEL REAR SIDE PANEL R SERVICE PANEL LABEL REAR GUARD TOP PANEL HANDLE 5 10 Remarks Drawing No S70 E20 662 S70 E20 675 S70 E20 668 S70 E40 686 S70 E60 130 S70 30L 655 S70 E10 658 S70 E20 658 S70 E40 662 S70 E40 661 S70 001 699 S70 E20 698 S70 E10 641 S70 E10 655 RoHS YHA 2 UK 46 1 2 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 15 2 4 5 9 11 14 12 13 6 7 8 10 9 17 3 16 STRUCTURAL PARTS PUH P125YHA UK PUH ...

Страница 90: ...62 S70 E30 675 S70 E30 668 S70 E21 686 S70 E50 130 S71 0VB 001 S70 30L 655 S70 E30 658 S70 E40 658 S70 E31 662 S70 E50 661 S70 001 699 S70 E10 698 S70 E20 641 S70 E10 655 F ST SCREW SIDE PANEL L FAN GRILLE FRONT PANEL SEPARATOR BASE ASSY MOTOR SUPPORT VALVE BED ASSY HANDLE COVER PANEL FRONT COVER PANEL REAR SIDE PANEL R SERVICE PANEL LABEL REAR GUARD TOP PANEL HANDLE DG12F536H10 BK00C456G13 RoHS V...

Страница 91: ...12 BK00C456G46 F ST SCREW SIDE PANEL L FAN GRILLE FRONT PANEL SEPARATOR BASE ASSY MOTOR SUPPORT VALVE BED ASSY HANDLE COVER PANEL FRONT COVER PANEL REAR SIDE PANEL R SERVICE PANEL LABEL REAR GUARD TOP PANEL HANDLE 5 10 Remarks Drawing No S70 E21 662 S70 E30 675 S70 E40 668 S70 E31 686 S70 E60 130 S71 0VB 001 S70 30L 655 S70 E30 658 S70 E40 658 S70 E41 662 S70 E60 661 S70 001 699 S70 E20 698 S70 E2...

Страница 92: ... 6 8 9 17 TH6 17 TH3 19 20 18 10 11 12 13 14 15 16 FUNCTIONAL PARTS PUH P71VHA YHA UK PUH P100VHA YHA UK PU P71VHA YHA UK PU P100VHA YHA UK 21 26 25 23 24 21 22 25 23 24 P71 P100VHA P71 P100YHA RoHS PARTS LIST OC379F ...

Страница 93: ...0 S70 E73 400 S70 E74 400 S70 E75 400 S70 E10 236 S70 E30 401 S70 500 418 S70 E04 411 S70 E41 440 S70 36L 450 S70 E02 413 S70 E10 403 S70 E41 242 S70 E80 401 S70 E90 401 S70 E91 402 S70 E42 202 S70 42H 467 S70 E10 208 S70 E41 408 S70 E51 408 S70 E05 716 S70 E10 716 S70 E04 716 S70 E41 255 S70 E51 255 S70 FV1 315 S70 FY2 315 S70 330 708 S70 440 708 S70 331 708 S70 E41 723 S70 E51 723 PROPELLER FAN ...

Страница 94: ... 8 9 17 TH6 17 TH3 19 20 18 10 11 12 13 14 15 16 FUNCTIONAL PARTS PUH P71VHA YHA1 UK PUH P100VHA YHA1 UK PU P71VHA YHA1 UK PU P100VHA YHA1 UK 21 26 25 23 24 21 22 25 23 24 P71 P100VHA P71 P100YHA RoHS PARTS LIST OC379F ...

Страница 95: ...E73 400 S70 E74 400 S70 E75 400 S70 E10 236 S70 E30 401 S70 500 418 S70 E04 411 S70 E41 440 S70 36L 450 S70 E02 413 S70 E10 403 S70 E41 242 S70 E80 401 S70 E90 401 S70 E91 402 S70 E42 202 S70 42H 467 S70 E10 208 S70 E41 408 S70 E51 408 S70 E05 716 S70 E10 716 S70 E04 716 S70 E41 255 S70 E51 255 S70 FV8 315 S70 FY9 315 S70 330 708 S70 440 708 S70 331 708 S70 E41 723 S70 E51 723 PROPELLER FAN NUT FA...

Страница 96: ... 9 17 TH6 17 TH3 19 20 18 10 11 12 13 14 15 16 FUNCTIONAL PARTS PUH P71VHA YHA 2 UK PUH P100VHA YHA 2 UK PU P71VHA YHA 2 UK PU P100VHA YHA 2 UK 21 26 25 23 24 21 22 25 23 24 P71 P100VHA P71 P100YHA RoHS PARTS LIST OC379F ...

Страница 97: ...E73 400 S70 E74 400 S70 E75 400 S70 E10 236 S70 E30 401 S70 500 418 S70 E04 411 S70 E41 440 S70 36L 450 S70 E02 413 S70 E10 403 S70 E41 242 S70 E80 401 S70 E90 401 S70 E91 401 S70 E42 202 S70 42H 467 S70 E10 208 S70 E41 408 S70 E51 408 S70 E07 716 S70 E10 716 S70 E04 716 S70 E41 255 S70 E51 255 S70 FV8 315 S70 FY9 315 S70 541 708 S70 542 708 S70 546 708 S70 E41 723 S70 E51 723 PROPELLER FAN NUT FA...

Страница 98: ...22 23 24 25 16 TH6 26 6 7 31 30 27 28 29 FUNCTIONAL PARTS PUH P125YHA UK PUH P140YHA UK PU P125YHA UK PU P140YHA UK PUH P125YHA1 UK PUH P140YHA1 UK PU P125YHA1 UK PU P140YHA1 UK PUH P125YHA 2 UK PUH P140YHA 2 UK PU P125YHA 2 UK PU P140YHA 2 UK RoHS PARTS LIST OC379F ...

Страница 99: ...0 K04 115 S70 K01 097 S70 E82 408 S70 E60 763 S70 E02 004 S70 E20 236 S70 E76 400 S70 E77 400 S70 E04 411 S70 500 418 S70 E43 202 S70 36L 450 S70 42H 467 S70 B01 529 S70 E44 202 S70 E02 413 S70 282 403 S70 E03 242 S70 E90 401 S70 E91 401 S70 E03 403 S70 E43 241 S70 E10 208 S70 H20 209 S70 E61 440 S70 E10 716 S70 E04 716 S70 E41 255 S70 31L 255 S70 FY2 315 S70 FY9 315 S70 640 708 S70 540 708 S70 54...

Страница 100: ...S PUH P71VHA YHAR3 UK PUH P100VHA YHAR3 UK PU P71VHA YHAR3 UK PU P100VHA YHAR3 UK 1 2 3 4 5 7 6 8 9 17 TH6 17 TH3 19 20 18 10 11 12 13 14 15 16 21 26 25 23 24 21 22 25 23 24 P71 P100VHA P71 P100YHA RoHS PARTS LIST OC379F ...

Страница 101: ...400 S70 E74 400 S70 E75 400 S70 E10 236 S70 E30 401 S70 600 418 S70 E04 411 S70 E12 440 S70 36L 450 S70 E02 413 S70 E10 403 S70 E41 242 S70 E80 401 S70 E90 401 S70 E91 401 S70 E42 202 S70 42H 467 S70 E10 208 S70 E41 408 S70 E51 408 S70 E07 716 S70 E10 716 S70 E04 716 S70 E41 255 S70 E51 255 S70 FV8 315 S70 FY9 315 S70 541 708 S70 542 708 S70 546 708 S70 E41 723 S70 E51 723 PROPELLER FAN NUT FAN MO...

Страница 102: ...model 13 14 15 17 16 TH3 18 19 17 20 21 22 23 24 25 16 TH6 26 6 7 31 30 27 28 29 FUNCTIONAL PARTS PUH P125YHAR3 UK PUH P140YHAR3 UK PU P125YHAR3 UK PU P140YHAR3 UK RoHS PARTS LIST PUH P125YHAR4 UK PUH P140YHAR4 UK PU P125YHAR4 UK PU P140YHAR4 UK OC379F ...

Страница 103: ...1 1 1 TH4 13 G S70 36L 450 STRAINER 50 1 1 1 1 1 1 1 1 14 G S70 42H 467 MUFFLER 1 1 1 1 1 1 1 1 15 G S70 B01 529 ACCUMULATOR DRAIN PAN 1 1 1 1 1 1 1 1 16 G S70 E44 202 THERMISTOR 1 1 1 1 1 1 1 1 TH3 6 17 G S70 E02 413 CHARGE PLUG 2 2 2 2 2 2 2 2 18 G S70 282 403 BYPASS VALVE 1 1 1 1 1 1 1 1 19 G S70 E03 242 SOLENOID COIL BYPASS VALVE 1 1 1 1 1 1 1 1 SV 20 G S70 E90 401 EXPANSION VALVE 1 1 1 1 1 1 ...

Страница 104: ...9 No OC379 REVISED EDITION E PDF 6 Distributed in Sep 2008 No OC379 REVISED EDITION D PDF 6 Distributed in Apr 2007 No OC379 REVISED EDITION C PDF 7 Distributed in Jul 2006 No OC379 REVISED EDITION B PDF 7 Distributed in May 2006 No OC379 REVISED EDITION A PDF 8 Distributed in Apr 2006 No OC379 PDF 8 Made in Japan New publication effective Apr 2012 Specifications are subject to change without noti...

Отзывы: