27
10-6-2. Indoor controller board
PSA-RP71GA PSA-RP100GA PSA-RP125GA PSA-RP140GA
PSA-RP71GA#1 PSA-RP100GA#1 PSA-RP125GA#1 PSA-RP140GA#1
PSH-P71GAH PSH-P100GAH PSH-P125GAH PSH-P140GAH
FAN
Fan motor output
CNP
Drain-pump output
(DP)
(220~240V AC)
CNC
Dew prevention
heater (H2)
(220~240V AC)
CNDK
Connect to the indoor
power board (CNSK)
(220~240V AC)
FUSE
(6.3A 250V)
CND
Power
supply input
(220~240V AC)
SWE
Emergency operation
SW2
Capacity setting
SW1
Model setting
CN2L
Connector
(LOSSNAY)
CN51
Centrally control
CN6V
Vane motor output
(MV)
CN90
Connect to the
wireless remote
controller board
(CNB)
CN31
Drain sensor (DS)
CN29
Condenser/evaporator
temperature thermistor
(TH5)
CN21
Pipe temperature
thermistor/Liquid
(TH2)
CN20
Room temperature
thermistor (TH1)
CN22
Remote controller
connecting wire
(10.4~14.6V DC)
LED3
Transmission
(Indoor/outdoor)
LED2
Power supply
(R.B)
LED1
Power supply
(I.B)
CN2D
Connector to the indoor
power board (CN2S)
(12.5~13.7V DC)
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
}
}
Non polarity
+
–
+
–
CN41
Connector
(HA terminal-A)
CNL
Louver motor output
(220~240V AC)
Содержание PSA-RP100GA
Страница 43: ...43 ...