4.3 Object List
Object Object
Type
Instance
No.
‘Present Value’
Settings
Notes
On/Off (Setup)
Binary Output
1xxx01
Inactive:Off
Active:On
On/Off (State)
Binary Input
1xxx02
Inactive:Off
Active:On
Error Code
Analog Input
1xxx03
4 digit error code where
8000 = ‘No Error’
Operation Mode (Setup) Multi-State Output 1xxx04
01: Cool
02: Dry
03: Fan
04: Heat
05: Auto
06: Heat Recovery
07: LC_Auto
08: Bypass
Lossnay
Only
09: AutoHeat
10: AutoCool
Not
settable
11: Heating
12: Eco-Heating
13: Hot-Water
14: Anti-Freeze
15: Cooling
Heat-pump
boiler only
Operation Mode (State) Multi-State Input
1xxx05
01: Cool
02: Dry
03: Fan
04: Heat
05: Auto
06: Heat Recovery
07: LC_Auto
08: Bypass
Lossnay
Only
09: AutoHeat
10: AutoCool
See
Section 5
11: Heating
12: Eco-Heating
13: Hot water
14: Anti-Freeze
15: Cooling
Heat-pump
boiler only
Fan Speed (Setup)
Multi-State Output 1xxx06
01: Low
02: Mid2
03: Mid1
04: High
Fan Speed (State)
Multi-State Input
1xxx07
01: Low
02: Mid2
03: Mid1
04: High
Room Temperature
Analog Input
1xxx08