2
2.1 Ethernet
The Procon BAC-IP/50 is a 10Base-T half duplex device and
needs to be connected to the G-50 and the BACnet/IP network.
Fig.1 shows the use of a hub / switch ( not supplied ) to make the
connections, but the Procon unit and the G-50 could just as easily
be connected directly to the BACnet/IP network.
12/24v AC
10Base-T
Ethernet
Configuration
Port
Reset
Button
Power
Supply
Enable
Link
To
Ethernet
Configure via RS485
RS232 Tx
Common
RS232 Rx
N/C
Configure or
upgrade firmware
via RS232
2. Connection Details
Fig.2 Connection Details
All electrical work should be carried out by a competent person
and wiring must be in accordance with the national electrical
installation regulations.
Note: a) The Procon BAC-IP/50 and the G-50 require separate
IP addresses which must be on the same subnet.
b) The BAC-IP/50 does not support Auto-Negotiation.