4. BACnet Specification

The Procon BAC-IP/50 is designed to work with a BACnet/IP network as 
described in the ANSI/ASHRAE Standard 135-2004. 

 

Property Setting 

Segmentation Not 

Supported 

Maximum APDU length supported 

206 octets 

Object List 

Supported 

Device ID 

User settable 

(1)

 

Device Name 

User settable 

(1)

 

Object Names 

User settable 

(1)

 

Notes:  (1)   Only settable via PC configuration program. 

 

4.2 Service List

Supported Services 

Read Property 

12 

Read Property Multiple 

14 

Write Property 

15 

Write Property Multiple 

16 

Who-Has 33 
I-Have 27 
Who-Is 34 
I-Am 36 

4.1 Object Types

Object Type 

Supported

Analog Input 

Yes 

Analog Output 

Yes 

Analog Value 

 

Binary Input 

Yes 

Binary Output 

Yes 

Binary Value 

Yes 

Calendar 6 

 

Command 7 

 

Device 8 

Yes 

Event Enrollment 

 

File 10 

 

Group 11 

 

Loop 12 

 

Multi-State Input 

13 

Yes 

Multi-State Output 

14 

Yes 

Notification Class 

15 

 

Program 16 

 

Schedule 17 

 

Averaging 18 

 

Multi-State Value 

19 

 

Trend Log 

20 

 

Содержание Procon BAC-IP50

Страница 1: ...Procon BAC IP 50 Installation and User Guide MITSUBISHI ELECTRIC ...

Страница 2: ...BACnetTM is a registered trademark of ASHRAE American Society of Heating Refrigerating and Air Conditioning Engineers Inc ...

Страница 3: ...e G 50 up to 50 groups can be monitored controlled The error state of up to 50 OC BC units can also be monitored BACNET IP Procon BAC IP 50 G 50A Ethernet Hub Switch Outdoor Units Indoor Units BACnet BMS System Fig 1 System Configuration Example 1 Product Overview 1 1 Supplied Parts No Part Name Quantity 1 Procon BAC IP 50 1 2 Cat 5 Straight Through Patch Lead 1 3 Din Rail Clips 2 4 Self Tapping S...

Страница 4: ...se T Ethernet Configuration Port Reset Button Power Supply Enable Link To Ethernet Configure via RS485 RS232 Tx Common RS232 Rx N C Configure or upgrade firmware via RS232 2 Connection Details Fig 2 Connection Details All electrical work should be carried out by a competent person and wiring must be in accordance with the national electrical installation regulations Note a The Procon BAC IP 50 and...

Страница 5: ...sabled Upon detection of the open contact the Procon unit sends the Forced Off Set command to the G 50 and resends at 5 seconds intervals while the contact is open As soon as the contact closes the Procon unit sends the Forced Off Reset command to the G 50 once only This ensures that any subsequent Forced Off commands sent via the BACnet BMS system are not overridden Configuration Port Pin 5 Pin 3...

Страница 6: ...f 8VA The unit is shipped setup for 24v AC The internal fuse is rated T500mA THIS EQUIPMENT MUST BE EARTHED 24v AC 12v AC Disconnect the supply and remove the top cover Fit the 2 shorting links and the fuse in the appropriate positions detailed above Shorting Links Fuse Changing The Supply Voltage ...

Страница 7: ...hin that group than can accept commands The other units within a group can be classed as slave units and contain the same status parameter values as the master apart from the Error Code which is unique to each unit In the example above addresses 01 03 06 and 08 are the master units and 02 04 05 and 07 are the slave units IC 01 IC 02 IC 03 IC 04 IC 05 IC 06 IC 07 IC 08 G 50 Group 01 Group 03 Group ...

Страница 8: ...PC configuration program 4 2 Service List Supported Services Read Property 12 Read Property Multiple 14 Write Property 15 Write Property Multiple 16 Who Has 33 I Have 27 Who Is 34 I Am 36 4 1 Object Types Object Type Supported Analog Input 0 Yes Analog Output 1 Yes Analog Value 2 Binary Input 3 Yes Binary Output 4 Yes Binary Value 5 Yes Calendar 6 Command 7 Device 8 Yes Event Enrollment 9 File 10 ...

Страница 9: ...ass Lossnay Only 09 AutoHeat 10 AutoCool Not settable 11 Heating 12 Eco Heating 13 Hot Water 14 Anti Freeze 15 Cooling Heat pump boiler only Operation Mode State Multi State Input 1xxx05 01 Cool 02 Dry 03 Fan 04 Heat 05 Auto 06 Heat Recovery 07 LC_Auto 08 Bypass Lossnay Only 09 AutoHeat 10 AutoCool See Section 5 11 Heating 12 Eco Heating 13 Hot water 14 Anti Freeze 15 Cooling Heat pump boiler only...

Страница 10: ...bited Air Direction Setup Multi State Output 1xxx15 01 Horizontal 02 Mid1 03 Mid2 04 Vertical 05 Swing Air Direction State Multi State Input 1xxx16 01 Horizontal 02 Mid1 03 Mid2 04 Vertical 05 Swing Ventilation Setup Multi State Output 1xxx17 01 Off 02 Low 03 High Lossnay OA units only Ventilation State Multi State Input 1xxx18 01 Off 02 Low 03 High Lossnay OA units only Unused 1xxx19 Unused 1xxx2...

Страница 11: ...9 Object Object Type Instance No Present Value Settings Notes Device Device zzz zzz 1 to 4194302 where xxx represents unit address 001 to 050 and yyy represents unit address 051 to 100 ...

Страница 12: ...ilter Sign Setup nnn_FL_w Local Inhibit Setup nnn_LI_w Local Inhibit State nnn_LI_r Air Direction Setup nnn_AD_w Air Direction State nnn_AD_r Ventilation Setup nnn_VN_w Lossnay OA units only Ventilation State nnn_VN_r Lossnay OA units only Unused Unused Unused OC BC Error Code nnn_ECode Mnet Comms State Sys_Mnet_State System Forced Off Setup Sys_Forced_Off_w System Forced Off State Sys_Forced_Off_...

Страница 13: ... AutoCool are reported if active Bank A 2 Preserve Settings Off All BACnet object properties are initialised at power up On All BACnet object properties except Present Value and Priority Array are initialised at power up Also all Input object Present Values are stored in the Present Value of the corresponding Output object 1 2 A Bank A 1 Auto Detail 2 Preserve Settings On Off Disconnect the supply...

Страница 14: ...0Base T Ethernet Configuration Port Reset Button Power Supply Enable Link A A A A B B B B Fig 6 Dimensions The holes marked A should be used when mounting the enclosure on a back panel The holes marked B can be used to attach the supplied din rail clips ...

Страница 15: ...is flashing slowly will activate Level 1 and then reset the unit Settings Restored Configuration via network Enabled Level 2 With the unit already ON press and hold in the reset button After approximately 5 seconds the Device Reset light will start to flash slowly Continue to hold in the reset button until the light starts to flash rapidly Releasing the reset button while the light is flashing rap...

Страница 16: ...n while powering up the unit Continue to hold in the reset button for approx 5 seconds until the Device Reset light begins to flash Long ON Short OFF The unit is now in bootloader mode Note Enabling the bootloader in this way is only necessary if the firmware update software fails to automatically put the unit into bootloader mode ...

Страница 17: ...global on off command System Forced Off State Readable object giving indication of the global on off command G50 Comms State Provides an indication of the communication status between the Procon BAC IP 50 and the G 50 Inactive G 50 not responding Active G 50 comms OK Note G 50 not responding either means the G 50 is switched off or is not connected to the network New_Setting_Compare Selects the wa...

Страница 18: ... Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC BACnet Smart Sensor B SS BACnet Smart Actuator B SA BACnet Interoperability Building Block Supported Data Sharing ReadProperty A DS RP A Data Sharing ReadProperty B DS RP B Data Sharing ReadPropertyMultiple A DS RPM A Data Sharing ReadPropertyMultipl...

Страница 19: ...t name object type present value status flags event state out of service units priority array relinquish default present value Binary Input object identifier object name object type present value status flags event state out of service polarity None Binary Output object identifier object name object type present value status flags event state out of service priority array relinquish default presen...

Страница 20: ...col object types supported object list max APDU length supported segmentation supported apdu timeout number of APDU retries device address binding database revision None Multi State Input object identifier object name object type present value status flags event state out of service number of states state text None Multi State Output object identifier object name object type present value status f...

Страница 21: ...nt EIA 232 Clause 10 baud rate s Point To Point modem Clause 10 baud rate s LON Talk Clause 11 medium Other Device Address Binding Support for Static Address Binding Network Options Router Annex H BACnet Tunnelling BACnet IP Broadcast Management Device BBMD BBMD support of registrations by foreign devices Character Sets Supported ANSI X3 4 non BACnet Equipment Supported by this Unit The unit suppo...

Страница 22: ...ing of section 2 1 RS485 232 port now Configuration Port Updated PIC statement to indicate support for priority arrays 17 11 2008 v1 03 v1 25 mcb Added this line to indicate latest firmware version 25 02 2009 v1 04 v1 30 mcb Included details of updates from v1 26 The main change being the additional of 2 switches to enable disable special functions Altered wording of network specification 20 07 20...

Страница 23: ...Related Links Model Number BAC IP50 BAC IP50 BACnet Specification BAC IP50 Installation Manual and Instruction Book BAC IP50 Declaration of Conformity ...

Отзывы: