- 20 -
Indoor
Heat source
Heating
63.0
kW
16.02
kW
28.1 / 26.6 / 25.7
A
-
kW
A
m / min
3
Pa
kW
mm
Liquid pipe
Gas pipe
m
dB(A)
kg
Heating
Indoor : 15°CDB ~ 28°CDB
Circulating water
: -5°CDB ~ 45°CDB
PFD-P500VM-E
PQHY-P250YHM-A(For Ground source)×2
Model Name
Cooling
56.0
System capacity
15.9
27.9 / 26.4 / 25.5
System current
System Power input
3N ~ 380 / 400 / 415 V(50Hz), 400 / 415 V(60Hz)
Power source
R410A
Protection
Fan
9.5 / 9.0 / 8.7
Sirocco fan × 1
Current
Fan
Refrigerant
320
Thermal switch
120
Power input
165
Ø9.52 Brazed (Ø12.7 for over 90m)
Ø22.2 Brazed
5.0
Galvanized steel plate (with polyester coating)
<MUNSEL 2.9GY 8.6 / 0.3(White) 7.2GB 3.2 / 5.3(Blue) or similar>
1950(H)×1980(W)×780(D)
63
Refrigerant piping allowable
Noise level
Type×Quantity
Airflow rate
External static pressure
Motor output
External dimension
External finish
4.4
Operating temperature range
520
Net weight
Cross fin (Aluminum plate fin and copper tube)
PP Honeycomb fabric (washable)
Operating Circulating water volume range
4.5 ~ 7.2m / h ×2
3
Heat exchanger
Air filter
Refrigerant piping diameter
Cooling
Indoor : 12°CWB ~ 24°CWB
Circulating water
: -5°CDB ~ 45°CDB
1. Cooling / Heating capacity indicates the nominal value at operation
under the following conditions.
<Cooling> Indoor : 27°CDB / 19°CWB Circulating water : 30°CDB
<Heating> Indoor : 20°CDB Circulating water : 20°CDB
Pipe length : 7.5m Height difference : 0m
Brine concentration : 0%
2. The noise level is measured in an anechoic room.
3. Heating can be used only by the indoor warming-up.
Note
4. Works not included : Installation / foundation work, electric connection work,
duct work, insulation work, The power source switch and other items are
not specified in the specifications.
At factory shipment, this model of indoor unit is designed and set to accommodate a single refrigerant
circuit. Connection of two refrigerant circuits to the indoor unit requires setting change and pipe work.
5. Add brine to circulating water for heat source unit when operating at water temperature below 10°C.