 Connecting 

Z

ater pipes

A

 Indoor unit

B

  Water pipe: From HBC unit

C

  Water pipe: To HBC unit

D

 Strainer (4  mesh or more)

 

( eld supply)

E

  Shut off valve

 

( eld supply)

A

  To outdoor unit

B

  End connection (brazing)

C

 HBC controller

D

 Indoor unit

E

  Twinning pipe ( eld supply)

F

  Up to three units for 1 branch hole; total capacity: below   

(but in same mode, cooling heating)

Fig

 

-

Fig

 

-

D

D

D

D

D

F

D

A B

E

*1

C

Water pipework is screw 
connections

9. HBC water pipe connection sizes

Unit model

Connection size

Pipe size

Water 

volume ( )

Water  

inlet

Water 

outlet

Water  

out

Water 
return

PLF -WP32 BM

Rc 3 4

screw

Rc 3 4

screw

Inner  

diameter

 2  mm

Inner  

diameter

 2  mm

1.5

PLF -WP4

BM

1.5

PLF -WP5

BM

1.5

1 . Please refer to the [Fig. 4-4] when connecting the water supply.
11. Install a shut off valve and strainer in a place that is easy to operate and makes 

maintenance work easy.

12. Apply insulation to the indoor unit pipework, strainer, shut off valve, and pressure 

reducing valve.

13. Please do not use a corrosion inhibitor in the water system.

 Water treat

P

ent and 

T

ualit

\

 control

To preserve water quality, use the closed type of water circuit. When the circulating 
water quality is poor, the water heat exchanger can develop scales, leading to a 
reduction in heat-exchange power and possible corrosion. Pay careful attention to 
water processing and water quality control when installing the water circulation system.

  Removing of foreign ob ects or impurities within the pipes.

  During installation, make sure that foreign ob ects, such as welding fragments, 

sealant particles, or rust, do not enter the pipes.

  Water Quality Processing

1

  Depending on the quality of the cold-temperature water used in the airconditioner, 

the copper piping of the heat exchanger may corrode.

 

Regular water quality processing is recommended.

 

If a water supply tank is installed, keep air contact to a minimum, and keep the 
level of dissolved oxygen in the water no higher than 1mg .

2

  Water quality standard

Items

Low to mid-range  

temperature water 

system

Tendency

Recirculating 

water

[2 T 6 C]

[6 T 14 F]

Make-up 

water

Corrosive

Scale-

forming

Standard items

pH (25 C) [77 F]

7.     .

7.     .

Electric conductivity 

3  or less

[3  or 

less]

3  or less

[3  or 

less]

(mS m) (25 C) [77 F]

(  s cm) (25 C) [77 F]

Chloride ion

(mg Cl- ) 5  or less 5  or less

Sulfate ion

(mg SO4

2

- ) 5  or less 5  or less

Acid consumption (pH4. )

5  or less 5  or less

(mg CaCO

3

)

Total hardness

(mg CaCO

3

) 7  or less 7  or less

Calcium hardness

(mg CaCO

3

) 5  or less 5  or less

Ionic silica

(mg SiO

2

) 3  or less 3  or less

Reference items

Iron

(mg Fe ) 1.  or less .3 or less

Copper

(mg Cu ) 1.  or less .1 or less

Sul de ion

(mg S

2

- ) not to be 

detected

not to be 
detected

Ammonium ion

(mg NH4

) .3 or less .1 or less

Residual chlorine

(mg Cl ) .25 or less .3 or less

Free carbon dioxide

(mg CO

2

) .4 or less 4.  or less

Ryzner stability inde

6.    7.

Reference :  Guideline of Water Quality for Refrigeration and Air Conditioning 

Equipment. ( RA GL 2E-1994)

3

  Consult with a specialist about water quality control methods and calculations 

before using anti-corrosive solutions.

4

  When replacing a previously installed air conditioning device (even when only 

the heat exchanger is being replaced),  rst conduct a water quality analysis and 
check for possible corrosion.

 

Corrosion can occur in cold-water systems even if there has been no prior signs 
of corrosion.

 

If the water quality level has dropped, ad ust water quality before replacing the 
unit.

C

B

E

A

D

E

Note:

 Connection o

I

 

P

ultiple indoor units 

Z

ith one connection (or 

M

oint pipe)

  Total capacity of connectable indoor units: Less than 
  Number of connectable indoor units: Maximum 3 Sets
  Selection of water piping

   Select the size according to the total capacity of indoor units to be installed 

downstream.

  Please group units that operate on 1 branch.

Содержание PLFY-WP VBM-E

Страница 1: ... le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil exté rieur pour une utilisation sûre et correct INSTALLATIEHANDLEIDING Lees deze handleiding en de installatiehandleiding van het buitenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de ...

Страница 2: ...a place that can Zithstand its Zeight Use onl speci ed caEles Ior Ziring The Ziring connections Pust Ee Pade securel Zith no tension applied on the terPinal connections Also neYer splice the caEles Ior Ziring unless otherZise indicated in this docuPent Failure to oEserYe these instructions Pa result in oYerheating or a re Use onl accessories authori ed E MitsuEishi Electric and asN the dealer or a...

Страница 3: ...rePoYe the insulator P that is pasted on the indoor unit A Branch duct hole I ø175 burring hole pitch B Indoor unit J Fresh air intake hole diagram C Fresh air intake hole K 3 ø2 burring hole D Drain pipe L ø125 burring hole pitch E Water pipe M ø1 cut out hole F Branch duct hole diagram view from either side N Ceiling O Detailed gure of removing the insulator G 14 ø2 burring hole P Insulator H ø1...

Страница 4: ...m Fig Fig 2 mm 2 Unit suspension procedures Fig 2 Suspend the main unit as shown in the diagram Figures given in parentheses represent the dimensions in case of installing optional multi function casement 1 In advance set the parts onto the suspension bolts in the order of the washers with insulation washers without insulation and nuts double Fit the washer with cushion so that the insulation face...

Страница 5: ...utlet of the water pipes and on the valve Provide an appropriate treatment on the end surface of the dew proo ng material to keep condensation out When water has been supplied to the water pipework purge the system of air The details of air purging can be found separately in the water circuit maintenance manual 2 Water pipe insulation 1 Connect the water pipes of each indoor unit to the same corre...

Страница 6: ... processing is recommended If a water supply tank is installed keep air contact to a minimum and keep the level of dissolved oxygen in the water no higher than 1mg 2 Water quality standard Items Low to mid range temperature water system Tendency Recirculating water 2 T 6 C 6 T 14 F Make up water Corrosive Scale forming Standard items pH 25 C 77 F 7 7 Electric conductivity 3 or less 3 or less 3 or ...

Страница 7: ...l box cover G MA Remote controller terminal cover H Power supply terminals with earth terminal L N I Transmission terminals M1 M2 S J MA Remote controller terminal 1 2 K Secure with the clamp 2 PoZer suppl Ziring Wiring size must comply with the applicable local and national code Install an earth longer than other cables Power supply codes of appliance shall not be lighter than design 6 245 IEC 53...

Страница 8: ...mpedance 1 The Ground fault interrupter should support inverter circuit The Ground fault interrupter should combine using of local switch or wiring breaker 2 Please take the larger of F1 or F2 as the value for F F1 Total operating maximum current of the indoor units 1 2 F2 1 Quantity of Type1 C 1 Quantity of Type2 C 1 Quantity of Type3 C 1 Quantity of Others C Indoor unit 1 2 Type 1 PLF BM PEF MS ...

Страница 9: ...rooP tePperature Zith the Euilt in sensor in a rePote controller Fig If you want to sense room temperature with the built in sensor in a remote control ler set SW1 1 on the control board to ON The setting of SW1 7 and SW1 as necessary also makes it possible to ad ust the air ow at a time when the heating thermometer is OFF Connecting rePote controller indoor and outdoor transPission caEles Fig Con...

Страница 10: ...tton to con rm the unit The vane of only the target indoor unit is pointing downward Ŷ Con rPation procedure F1 F2 F3 F4 Manual vane angle Input display Cur Address Check M NET address Identify unit Check button F1 F2 F3 F4 Manual vane angle Input display M NET address The air conditioner with the vane pointing downward is the target air conditioner F1 F2 F3 F4 Manual vane angle Input display Ther...

Страница 11: ... With the intake grille in the open position remove the hinge of the intake grille from the grille as indicated by the arrow 2 2 2 RePoYing the corner panel Fig Remove the screw from the corner of the corner panel Slide the corner panel as indicated by the arrow 1 to remove the corner panel Fig A Intake grille B Grille C Intake grille levers D Grille hook E Hole for the grille s hook F Corner pane...

Страница 12: ...tightening the screZ Zith captiYe Zasher 2 tighten it at a torTue oI 8 N P or less NeYer use an iPpact screZdriYer It Pa result in parts daPage Wire connection Fig 8 Remove the 2 screws xing the cover of electrical branch box of the unit and open the cover Be sure to connect the connector white 2 pole for vane motor of the grille to CN connector of controller board of the unit The lead wire of gri...

Страница 13: ... 2 of the fastener 4 so that there is no slack Put the cover back on the electrical box with 3 screws Make sure wires are not caught in the cover of electric box If they are caught they will be cut Adverse procedure of 6 2 Preparing to attach the grille will be taken for installing the i see sensor corner panel The i see sensor corner panel should be xed onto the grille 1 with screw 6 LocNing the ...

Страница 14: ...eness in the poZer suppl or control Ziring Zrong polarit and no disconnection oI phase in the suppl Ź Use a Yolt PegohPPeter to checN that the resistance EetZeen the poZer suppl terPinals and ground is at least M Ź Do not carr out this test on the control Ziring loZ Yoltage circuit terPinals Warning Do not use the air conditioner iI the insulation resistance is less than M Caution Turn on the poZe...

Страница 15: ... B Water about 1 cc C Drain plug D Pour water through outlet Be carefule not to spray water into the drain pump mechanism Step SZitch the rePote controller to Test run 1 Select Service from the Main menu and press the button 2 When the Service menu is selected a window will appear asking for the password Fig 7 3 To enter the current maintenance password 4 numerical digits move the cursor to the di...

Страница 16: ...ɬɜɟ ɩɨ ɭɫɬɚɧɨɜɤɟ ȼɫɟ ɷɥɟɤɬɪɨɪɚɛɨɬɵ ɞɨɥɠɧɵ ɜɵɩɨɥɧɹɬɶɫɹ ɤɜɚɥɢɮɢɰɢɪɨɜɚɧɧɵɦ ɷɥɟɤɬɪɢ ɤɨɦ ɢɦɟɸɳɢɦ ɫɨɨɬɜɟɬɫɬɜɭɸɳɭɸ ɥɢɰɟɧɡɢɸ ɜ ɫɨɨɬɜɟɬɫɬɜɢɢ ɫ ɦɟɫɬɧɵɦɢ ɧɨɪɦɚɬɢɜɚɦɢ ɍɫɬɚɧɨɜɤɭ ɧɟɨɛɯɨɞɢɦɨ ɜɵɩɨɥɧɹɬɶ ɜ ɫɨɨɬɜɟɬɫɬɜɢɢ ɫ ɞɟɣɫɬɜɭɸɳɢɦɢ ɩɪɚɜɢɥɚɦɢ ɷɥɟɤɬɪɨɛɟɡɨɩɚɫɧɨɫɬɢ ɉɨɜɪɟɠɞɟɧɧɵɣ ɤɚɛɟɥɶ ɢɡ ɤɨɦɩɥɟɤɬɚ ɩɨɫɬɚɜɤɢ ɞɨɥɠɟɧ ɛɵɬɶ ɡɚɦɟɧɟɧ ɜ ɰɟɥɹɯ ɛɟɡɨɩɚɫɧɨɫɬɢ ɩɪɨɢɡɜɨɞɢɬɟɥɟɦ ɫɟɪɜɢɫɧɵɦ ɚɝɟɧɬɨɦ ɢɥɢ ɥɢɰɚɦɢ ɨɛɥɚɞɚɸɳɢɦɢ ɧɟɨɛɯɨɞɢɦɨɣ ɤɜɚ...

Страница 17: ...ɜɶɬɟ 135 ɦɦ ɤ ɪɚɡɦɟɪɚɦ ɨɛɨɡɧɚɱɟɧɧɵɦ ɧɚ ɪɢɫɭɧɤɟ ɉɪɢɭɫɬɚɧɨɜɤɟɨɬɜɟɬɜɥɟɧɢɣɜɟɧɬɢɥɹɰɢɨɧɧɨɝɨɤɚɧɚɥɚɬɳɚɬɟɥɶɧɨɨɛɟɪɧɢɬɟɢɯɢɡɨɥɹɰɢɟɣ ȼ ɩɪɨɬɢɜɧɨɦ ɫɥɭɱɚɟ ɜɨɡɦɨɠɧɨ ɨɛɪɚɡɨɜɚɧɢɟ ɤɨɧɞɟɧɫɚɰɢɢ ɢ ɤɚɩɚɧɢɟ ɜɨɞɵ ȼɨ ɜɪɟɦɹ ɫɨɡɞɚɧɢɹ ɜɯɨɞɧɨɝɨ ɨɬɜɟɪɫɬɢɹ ɞɥɹ ɫɜɟɠɟɝɨ ɜɨɡɞɭɯɚ ɭɛɟɞɢɬɟɫɶ ɱɬɨ ɜɵ ɭɞɚɥɢɥɢ ɢɡɨɥɹɰɢɨɧɧɵɣ ɦɚɬɟɪɢɚɥ P ɤɨɬɨɪɵɣ ɧɚɥɨɠɟɧ ɧɚ ɜɧɭɬɪɟɧɧɢɣ ɩɪɢɛɨɪ A I ø175 B J C K 3 ø2 8 D L ø125 E M ø100 F G 14 ø2 8 N O P H ø150 2 4...

Страница 18: ... ɢɥɢ ɩɪɢ ɧɚɧɟɫɟɧɢɢ ɩɨɬɨɥɨɱɧɵɯ ɦɚɬɟɪɢɚɥɨɜ 2 6 ɉɪɨɜɟɪɤɚ ɪɚɫɩɨɥɨɠɟɧɢɹ ɝɥɚɜɧɨɝɨ ɩɪɢɛɨɪɚ ɢ ɡɚɬɹɝɢɜɚɧɢɟ ɧɚɜɟɫɧɵɯ ɛɨɥɬɨɜ Fig 2 7 3 ɉɨɞɫɨɟɞɢɧɟɧɢɟ ɞɪɟɧɚɠɧɨɣ ɬɪɭɛɵ 30 3 1 Ⱦɪɟɧɚɠɧɵɟ ɬɪɭɛɵ Fig 3 1 VP25 O D ø32 PVC TUBE 1 100 1 2 A 9 B 1 100 C K L M D O D ø32 PVC TUBE E F G H 1 100 I O D ø38 PVC TUBE 9 J 85 1 Fig 3 2 2 O D ø32 3 O D ø32 4 5 A B C D E F G O D ø32 H I J O D ø32 1 100 K L 11 25 25 25 Max 20m 1 5 ...

Страница 19: ...ɤɟ ɫɢɫɬɟɦɵ ɜɨ ɞɹɧɨɝɨ ɬɪɭɛɨɩɪɨɜɨɞɚ 1 0 145 HBC HBC HBC 5102 1 2 3 1 5 2 4 ɉɨɞɫɨɟɞɢɧɟɧɢɟ ɜɨɞɹɧɵɯ ɬɪɭɛ 40 40 4 2 Ɍɟɩɥɨɢɡɨɥɹɰɢɹ ɜɨɞɹɧɨɣ ɬɪɭɛɵ 1 HBC 2 HBC HBC 3 Fig 4 1 HBC 20 4 5 6 7 8 A B C D 40 E F F E D C B A B A Fig 4 1 Fig 4 2 A HBC B HBC ...

Страница 20: ...ɨɞɵ ɢ ɤɨɧɬɪɨɥɶ ɡɚ ɤɚɱɟɫɬɜɨɦ ɜɨɞɵ 1 1 mg 2 20 T 60 C pH 25 C 7 0 8 0 7 0 8 0 30 300 30 300 mS m 25 C s cm 25 C mg Cl 50 50 mg SO42 50 50 pH4 8 mg CaCO3 50 50 mg CaCO3 70 70 mg CaCO3 50 50 mg SiO2 30 30 mg Fe 1 0 0 3 mg Cu 1 0 0 1 mg S2 mg NH4 0 3 0 1 mg Cl 0 25 0 3 mg CO2 0 4 4 0 6 0 7 0 JRA GL02E 1994 3 4 C B E A D E ɉɪɢɦɟɱɚɧɢɟ 1 ɉɨɞɫɨɟɞɢɧɟɧɢɟ ɧɟɫɤɨɥɶɤɢɯ ɜɧɭɬɪɟɧɧɢɯ ɩɪɢɛɨɪɨɜ ɨɞɧɢɦ ɫɨɟɞɢɧɟɧɢɟɦ ɢɥɢ ɫ...

Страница 21: ... 5 2 ɗɥɟɤɬɪɨɩɪɨɜɨɞɤɚ ɞɥɹ ɩɨɞɜɨɞɚ ɩɢɬɚɧɢɹ 60245 IEC 53 60227 IEC 53 3 Fig 5 2 A B C D ɉɪɟɞɭɩɪɟɠɞɟɧɢɟ ɇɢɤɨɝɞɚ ɧɟ ɩɨɞɫɨɟɞɢɧɹɣɬɟ ɜɧɚɯɥɟɫɬ ɫɢɥɨɜɨɣ ɤɚɛɟɥɶ ɢɥɢ ɫɨɟɞɢɧɢɬɟɥɶɧɵɣ ɤɚɛɟɥɶ ɜɧɟɲɧɟɝɨ ɩɢɬɚɧɢɹ ɗɬɨ ɦɨɠɟɬ ɩɪɢɜɟɫɬɢ ɤ ɡɚɞɵɦɥɟɧɢɸ ɜɨɡɝɨɪɚɧɢɸ ɢɥɢ ɧɟɢɫɩɪɚɜɧɨɫɬɢ Fig 5 1 Fig 5 2 1 2 M1M2 S TB2 TB5 TB15 L N A B C D E F G K ...

Страница 22: ... 5 1 5 20A 3 16 16 20 F0 25 A 2 2 5 2 5 2 5 30A 3 25 25 30 F0 32 A 2 4 0 4 0 4 0 40A 3 32 32 40 IEC61000 3 3 1 2 F0 F1 F2 F1 1 2 F2 V1 1 C V1 2 C V1 3 C V1 C V1 V2 1 PLFY VBM PEFY VMS PFFY VLRMM 18 6 2 4 2 PEFY VMA 38 1 6 C 0 01 C F2 PEFY VMS 4 PEFY VMA 1 C 8 F2 18 6 4 8 38 1 8 14 05 16 A 8 16 A 0 01 3 G1 V2 1 V2 2 V2 3 V2 V3 G1 30 30 0 1 100 100 0 1 V3 1 5 2 48 2 5 2 56 4 0 2 66 1 2 3 4 6 8 10 20...

Страница 23: ...2 S M1M2 TB3 M1M2 2 1 2 1 5 6 ɍɫɬɚɧɨɜɤɚ ɩɟɪɟɤɥɸɱɚɬɟɥɟɣ ɩɪɢ ɜɵɫɨɤɨɦ ɩɨ ɬɨɥɤɟ ɢɥɢ ɩɪɢ ɢɦɟɧɟɧɢɢ ɱɢɫɥɚ ɜɵɯɨɞɨɜ ɜɨɡ ɞɭɯɚ Fig 5 4 SWA SWB SWA SWB PLFY WP32 WP40 WP50VBM SWA SWB 1 2 3 4 4 2 5 2 7 3 5 3 3 2 7 3 0 3 5 2 2 3 0 3 3 3 5 5 7 Ɉɩɪɟɞɟɥɟɧɢɟ ɬɟɦɩɟɪɚɬɭɪɵ ɜ ɩɨɦɟɳɟɧɢɢ ɜɫɬɪɨ ɟɧɧɵɦ ɞɚɬɱɢɤɨɦ ɩɭɥɶɬɚ ɞɢɫɬɚɧɰɢɨɧɧɨɝɨ ɭɩɪɚɜ ɥɟɧɢɹ Fig 5 4 SW1 1 SW1 7 SW1 8 5 5 ɍɫɬɚɧɨɜɤɚ ɚɞɪɟɫɨɜ Fig 5 4 1 9 10 1 3 SW12 10 0 SW1...

Страница 24: ...3 F4 Manual vane angle Input display Cur Address Check M NET address Identify unit Check button 1 Maintenance 2 F1 F2 Manual vane angle 3 M NET address M NET F2 F3 F4 Ŷ ɉɪɨɰɟɞɭɪɚ ɩɨɞɬɜɟɪɠɞɟɧɢɹ F1 F2 F3 F4 Manual vane angle Input display Cur Address Check M NET address Identify unit Check button F1 F2 F3 F4 Manual vane angle Input display M NET address The air conditioner with the vane pointing dow...

Страница 25: ...ɧɧɨɣ ɪɟɲɟɬ ɤɢ Fig 6 2 3 860 860 910 910 17 22 A B C 3 D 6 2 1 ɍɞɚɥɟɧɢɟ ɜɨɡɞɭɯɨɡɚɛɨɪɧɨɣ ɪɟɲɟɬɤɢ Fig 6 3 1 2 6 2 2 ɍɞɚɥɟɧɢɟ ɭɝɥɨɜɨɣ ɩɚɧɟɥɢ Fig 6 4 1 Fig 6 3 6 4 A B C D E F G H 6 3 ȼɵɛɨɪ ɜɵɬɹɠɧɵɯ ɨɬɜɟɪɫɬɢɣ 11 1 1 2 ɉɪɢɦɟɱɚɧɢɟ Ⱦɥɹ 3 ɧɚɩɪɚɜɥɟɧɧɨɝɨ ɢ 2 ɧɚɩɪɚɜɥɟɧɧɨɝɨ ɜɵɞɭɜɚ ɩɨɠɚɥɭɣɫɬɚ ɢɫɩɨɥɶɡɭɣɬɟ ɩɥɚɫɬɢɧɤɭ ɡɚɫɥɨɧɤɢ ɜɵɬɹɠɧɨɝɨ ɨɬɜɟɪɫɬɢɹ ɨɩɰɢɹ Fig 6 1 Fig 6 2 2 0 A 17 5 0 Fig 6 3 Fig 6 4 1 4 3 1 4 1 2 6 2 ...

Страница 26: ...ɨɧɧɨɣ ɪɟɲɟɬɤɨɣ ɢ ɩɨɬɨɥɤɨɦ Ɉɫɬɨɪɨɠɧɨ Ɂɚɬɹɝɢɜɚɹ ɜɢɧɬ ɫ ɩɪɭɠɢɧɧɨɣ ɡɭɛɱɚɬɨɣ ɲɚɣɛɨɣ 2 ɫɥɟɞɭɟɬ ɩɪɢɤɥɚɞɵɜɚɬɶ ɦɨɦɟɧɬ ɧɟ ɛɨɥɟɟ 4 8 ɇ ɦ ɇɢɤɨɝɞɚ ɧɟ ɢɫɩɨɥɶɡɭɣɬɟ ɭɞɚɪɧɵɣ ɝɚɣɤɨɜɺɪɬ ɗɬɨ ɦɨɠɟɬ ɩɪɢɜɟɫɬɢ ɤ ɩɨɜɪɟɠɞɟɧɢɸ ɞɟɬɚɥɟɣ 6 4 4 ɋɨɟɞɢɧɟɧɢɟ ɩɪɨɜɨɞɨɜ Fig 6 8 2 20 CNV 2 ɉɪɢɦɟɱɚɧɢɟ ɇɟ ɨɫɬɚɜɥɹɣɬɟ ɢɡɥɢɲɟɤ ɩɪɨɜɨɥɨɱɧɨɝɨ ɜɵɜɨɞɚ ɜ ɷɥɟɤɬɪɢɱɟɫɤɨɣ ɨɬ ɜɟɬɜɢɬɟɥɶɧɨɣ ɤɨɪɨɛɤɟ ɩɪɢɛɨɪɚ 6 ɍɫɬɚɧɨɜɤɚ ɜɟɧɬɢɥɹɰɢɨɧɧɨɣ ɪɟɲɟɬɤɢ Fig 6 5 Fig...

Страница 27: ...ɤɟ ɫ ɩɨɦɨɳɶɸ ɜɢɧɬɚ 4 ɲɬ 4 8 ɤɚɤ ɩɨɤɚɡɚɧɨ ɧɚ ɢɥɥɸɫɬɪɚɰɢɢ 6 2 D E F G H i see sensor PLP 6BAE 6 6 ɍɫɬɚɧɨɜɤɚ ɭɝɥɨɜɨɣ ɩɚɧɟɥɢ i see sensor Fig 6 10 PLP 6BAE CN4Y CN6Y i see sensor 7 i see sensor 7 4 2 4 3 i see sensor 6 2 i see sensor 1 6 6 7 Ȼɥɨɤɢɪɨɜɤɚ ɧɚɩɪɚɜɥɟɧɢɹ ɜɨɡɞɭɲɧɨɝɨ ɩɨɬɨɤɚ ɜɜɟɪɯ ɜɧɢɡ Fig 6 11 1 2 5 7 6 8 ɉɪɨɜɟɪɤɚ PLP 6BAE i see sensor i see sensor 6 6 i see sensor Fig 6 9 Fig 6 11 Fig 6 10 A ...

Страница 28: ...ɪɨɠɧɨ ɉɨɞɤɥɸɱɢɬɟ ɷɥɟɤɬɪɨɩɢɬɚɧɢɟ ɩɪɢɛɨɪɚ ɧɟ ɦɟɧɟɟ ɱɟɦ ɡɚ 12 ɱɚɫɨɜ ɞɨ ɧɚɱɚɥɚ ɪɚɛɨɬɵ ɇɟ ɩɪɢɤɚɫɚɣɬɟɫɶ ɤ ɜɵɤɥɸɱɚɬɟɥɹɦ ɦɨɤɪɵɦɢ ɪɭɤɚɦɢ ɇɟ ɢɫɩɨɥɶɡɭɣɬɟ ɤɨɧɞɢɰɢɨɧɟɪ ɜɨɡɞɭɯɚ ɟɫɥɢ ɟɝɨ ɩɚɧɟɥɢ ɢ ɤɪɵɲɤɢ ɫɧɹɬɵ ɇɟ ɨɬɤɥɸɱɚɣɬɟ ɩɢɬɚɧɢɟ ɧɟɦɟɞɥɟɧɧɨ ɩɨɫɥɟ ɜɵɤɥɸɱɟɧɢɹ ɩɪɢɛɨɪɚ ɉɨɫɥɟ ɩɨɞɚɱɢ ɜɨɞɵ ɜ ɫɢɫɬɟɦɭ ɜɨɞɹɧɵɯ ɬɪɭɛɨɩɪɨɜɨɞɨɜ ɭɞɚɥɢɬɟ ɜɨɡɞɭɯ ɢɡ ɫɢɫɬɟɦɵ ɉɨɞɪɨɛɧɨɫɬɢ ɩɨ ɭɞɚɥɟɧɢɸ ɜɨɡɞɭɯɚ ɩɪɢɜɟɞɟɧɵ ɨɬɞɟɥɶɧɨ ɜ ɪɭɤɨɜɨɞɫɬɜɟ ɩɨ ɨɛɫɥ...

Страница 29: ...u Cursor Service menu Test run Drain pump test run Fig 7 5 F1 F2 F3 F4 Service menu Cursor Select Enter maintenance password Fig 7 3 7 4 ɉɪɨɜɟɪɤɚ ɞɪɟɧɚɠɚ Fig 7 8 ɉɨɫɥɟ ɡɚɜɟɪɲɟɧɢɹ ɷɥɟɤɬɪɢɱɟɫɤɢɯ ɪɚɛɨɬ Ⱦɨ ɡɚɜɟɪɲɟɧɢɹ ɷɥɟɤɬɪɢɱɟɫɤɢɯ ɪɚɛɨɬ 220 240 L N SWE Fig 7 8 A B 1000 C D F1 F2 F3 F4 Cool Pipe Auto Switch disp Mode Fan Remain Test run Fig 7 6 F1 F2 F3 F4 Remain Vane Fig 7 7 ɒɚɝ 2 ȼɵɩɨɥɧɢɬɟ ɩɪɨɛɧɵɣ ɩɭ...

Страница 30: ...is manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in UNITED KINGDOM BH79D500K02 ...

Отзывы: