2

GB

  Installing the grille

 Preparations (Fig

 

-

)

  Install the 2 enclosed screws with washer 

2

 

in the main unit (at the corner drain 

pipe area and at the opposite corner) as shown in the diagram.

2

  Te

P

porar

\

 installation o

I

 the grille (Fig

 

-

)

  Temporarily secure the grille using the bell shaped holes by putting the socket of 

the grille marked 

G

 on the corner drain pipe area of the main unit.

*  Make sure that the lead wiring of the grille does not get pinched between the 

grille and the main unit.

  Securing the grille (Fig

 

-

)

  Secure the grille to the main unit by tightening the previously installed 2 screws 

(with captive washer) as well as the 2 remaining screws (with captive washer). 

*  Make sure that there are no gaps between the main unit and the grille or the 

grille and the ceiling.

Fi

[

ing gaps 

E

et

Z

een the grille and the ceiling

With the grille attached, ad ust the height of the main unit to close the gap.

 Caution:

When tightening the scre

Z

 

Z

ith capti

Y

Z

asher 

2

 tighten it at a tor

T

ue o

I

 

N

‡P

 or less

 Ne

Y

er use an i

P

pact scre

Z

dri

Y

er

 

‡

 It 

P

a

\

 result in parts da

P

age

  Wire connection (Fig

 

-8)

 Remove the 2 screws  xing the cover of electrical branch box of the unit and open 

the cover.

 Be sure to connect the connector (white, 2 -pole) for vane motor of the grille to 

CN  connector of controller board of the unit.

The lead wire of grille is passed through the catch for bell mouth of the unit 
perfectly. The remaining lead wire is tied with clamp of the unit and put the cover of 
the unit again with 2 screws.

Note: 
Do not put the re

P

aining lead 

Z

ire in electrical 

E

ranch 

E

o

[

 o

I

 the unit

  Installing the grille

Fig

 

-

Fig

 

-

Fig

 

-

A

 Main unit

C

 Corner drain pipe area

D

 Screw with washer 

2

 (for temporary 

use)

E

 Grille

F

 Screw with washer 

2

G

 Socket

H

 Bell shaped hole

A

 Ceiling

B

 Main unit

C

 Grille

D

 Make sure that there are no gaps

E

 Ad ust the nut of the main unit using 

a wrench, etc.  

15

-20

A

 Main unit

B

 Screw with captive washer

Fig

 

-8

A

 Clamp of the main unit

B

 Electrical box

C

 Indoor controler board

D

 Catch for bell mouth

E

 Lead wire of grille

Содержание PLFY-WP VBM-E

Страница 1: ... le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil exté rieur pour une utilisation sûre et correct INSTALLATIEHANDLEIDING Lees deze handleiding en de installatiehandleiding van het buitenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de ...

Страница 2: ...a place that can Zithstand its Zeight Use onl speci ed caEles Ior Ziring The Ziring connections Pust Ee Pade securel Zith no tension applied on the terPinal connections Also neYer splice the caEles Ior Ziring unless otherZise indicated in this docuPent Failure to oEserYe these instructions Pa result in oYerheating or a re Use onl accessories authori ed E MitsuEishi Electric and asN the dealer or a...

Страница 3: ...rePoYe the insulator P that is pasted on the indoor unit A Branch duct hole I ø175 burring hole pitch B Indoor unit J Fresh air intake hole diagram C Fresh air intake hole K 3 ø2 burring hole D Drain pipe L ø125 burring hole pitch E Water pipe M ø1 cut out hole F Branch duct hole diagram view from either side N Ceiling O Detailed gure of removing the insulator G 14 ø2 burring hole P Insulator H ø1...

Страница 4: ...m Fig Fig 2 mm 2 Unit suspension procedures Fig 2 Suspend the main unit as shown in the diagram Figures given in parentheses represent the dimensions in case of installing optional multi function casement 1 In advance set the parts onto the suspension bolts in the order of the washers with insulation washers without insulation and nuts double Fit the washer with cushion so that the insulation face...

Страница 5: ...utlet of the water pipes and on the valve Provide an appropriate treatment on the end surface of the dew proo ng material to keep condensation out When water has been supplied to the water pipework purge the system of air The details of air purging can be found separately in the water circuit maintenance manual 2 Water pipe insulation 1 Connect the water pipes of each indoor unit to the same corre...

Страница 6: ... processing is recommended If a water supply tank is installed keep air contact to a minimum and keep the level of dissolved oxygen in the water no higher than 1mg 2 Water quality standard Items Low to mid range temperature water system Tendency Recirculating water 2 T 6 C 6 T 14 F Make up water Corrosive Scale forming Standard items pH 25 C 77 F 7 7 Electric conductivity 3 or less 3 or less 3 or ...

Страница 7: ...l box cover G MA Remote controller terminal cover H Power supply terminals with earth terminal L N I Transmission terminals M1 M2 S J MA Remote controller terminal 1 2 K Secure with the clamp 2 PoZer suppl Ziring Wiring size must comply with the applicable local and national code Install an earth longer than other cables Power supply codes of appliance shall not be lighter than design 6 245 IEC 53...

Страница 8: ...mpedance 1 The Ground fault interrupter should support inverter circuit The Ground fault interrupter should combine using of local switch or wiring breaker 2 Please take the larger of F1 or F2 as the value for F F1 Total operating maximum current of the indoor units 1 2 F2 1 Quantity of Type1 C 1 Quantity of Type2 C 1 Quantity of Type3 C 1 Quantity of Others C Indoor unit 1 2 Type 1 PLF BM PEF MS ...

Страница 9: ...rooP tePperature Zith the Euilt in sensor in a rePote controller Fig If you want to sense room temperature with the built in sensor in a remote control ler set SW1 1 on the control board to ON The setting of SW1 7 and SW1 as necessary also makes it possible to ad ust the air ow at a time when the heating thermometer is OFF Connecting rePote controller indoor and outdoor transPission caEles Fig Con...

Страница 10: ...tton to con rm the unit The vane of only the target indoor unit is pointing downward Ŷ Con rPation procedure F1 F2 F3 F4 Manual vane angle Input display Cur Address Check M NET address Identify unit Check button F1 F2 F3 F4 Manual vane angle Input display M NET address The air conditioner with the vane pointing downward is the target air conditioner F1 F2 F3 F4 Manual vane angle Input display Ther...

Страница 11: ... With the intake grille in the open position remove the hinge of the intake grille from the grille as indicated by the arrow 2 2 2 RePoYing the corner panel Fig Remove the screw from the corner of the corner panel Slide the corner panel as indicated by the arrow 1 to remove the corner panel Fig A Intake grille B Grille C Intake grille levers D Grille hook E Hole for the grille s hook F Corner pane...

Страница 12: ...tightening the screZ Zith captiYe Zasher 2 tighten it at a torTue oI 8 N P or less NeYer use an iPpact screZdriYer It Pa result in parts daPage Wire connection Fig 8 Remove the 2 screws xing the cover of electrical branch box of the unit and open the cover Be sure to connect the connector white 2 pole for vane motor of the grille to CN connector of controller board of the unit The lead wire of gri...

Страница 13: ... 2 of the fastener 4 so that there is no slack Put the cover back on the electrical box with 3 screws Make sure wires are not caught in the cover of electric box If they are caught they will be cut Adverse procedure of 6 2 Preparing to attach the grille will be taken for installing the i see sensor corner panel The i see sensor corner panel should be xed onto the grille 1 with screw 6 LocNing the ...

Страница 14: ...eness in the poZer suppl or control Ziring Zrong polarit and no disconnection oI phase in the suppl Ź Use a Yolt PegohPPeter to checN that the resistance EetZeen the poZer suppl terPinals and ground is at least M Ź Do not carr out this test on the control Ziring loZ Yoltage circuit terPinals Warning Do not use the air conditioner iI the insulation resistance is less than M Caution Turn on the poZe...

Страница 15: ... B Water about 1 cc C Drain plug D Pour water through outlet Be carefule not to spray water into the drain pump mechanism Step SZitch the rePote controller to Test run 1 Select Service from the Main menu and press the button 2 When the Service menu is selected a window will appear asking for the password Fig 7 3 To enter the current maintenance password 4 numerical digits move the cursor to the di...

Страница 16: ...ɬɜɟ ɩɨ ɭɫɬɚɧɨɜɤɟ ȼɫɟ ɷɥɟɤɬɪɨɪɚɛɨɬɵ ɞɨɥɠɧɵ ɜɵɩɨɥɧɹɬɶɫɹ ɤɜɚɥɢɮɢɰɢɪɨɜɚɧɧɵɦ ɷɥɟɤɬɪɢ ɤɨɦ ɢɦɟɸɳɢɦ ɫɨɨɬɜɟɬɫɬɜɭɸɳɭɸ ɥɢɰɟɧɡɢɸ ɜ ɫɨɨɬɜɟɬɫɬɜɢɢ ɫ ɦɟɫɬɧɵɦɢ ɧɨɪɦɚɬɢɜɚɦɢ ɍɫɬɚɧɨɜɤɭ ɧɟɨɛɯɨɞɢɦɨ ɜɵɩɨɥɧɹɬɶ ɜ ɫɨɨɬɜɟɬɫɬɜɢɢ ɫ ɞɟɣɫɬɜɭɸɳɢɦɢ ɩɪɚɜɢɥɚɦɢ ɷɥɟɤɬɪɨɛɟɡɨɩɚɫɧɨɫɬɢ ɉɨɜɪɟɠɞɟɧɧɵɣ ɤɚɛɟɥɶ ɢɡ ɤɨɦɩɥɟɤɬɚ ɩɨɫɬɚɜɤɢ ɞɨɥɠɟɧ ɛɵɬɶ ɡɚɦɟɧɟɧ ɜ ɰɟɥɹɯ ɛɟɡɨɩɚɫɧɨɫɬɢ ɩɪɨɢɡɜɨɞɢɬɟɥɟɦ ɫɟɪɜɢɫɧɵɦ ɚɝɟɧɬɨɦ ɢɥɢ ɥɢɰɚɦɢ ɨɛɥɚɞɚɸɳɢɦɢ ɧɟɨɛɯɨɞɢɦɨɣ ɤɜɚ...

Страница 17: ...ɜɶɬɟ 135 ɦɦ ɤ ɪɚɡɦɟɪɚɦ ɨɛɨɡɧɚɱɟɧɧɵɦ ɧɚ ɪɢɫɭɧɤɟ ɉɪɢɭɫɬɚɧɨɜɤɟɨɬɜɟɬɜɥɟɧɢɣɜɟɧɬɢɥɹɰɢɨɧɧɨɝɨɤɚɧɚɥɚɬɳɚɬɟɥɶɧɨɨɛɟɪɧɢɬɟɢɯɢɡɨɥɹɰɢɟɣ ȼ ɩɪɨɬɢɜɧɨɦ ɫɥɭɱɚɟ ɜɨɡɦɨɠɧɨ ɨɛɪɚɡɨɜɚɧɢɟ ɤɨɧɞɟɧɫɚɰɢɢ ɢ ɤɚɩɚɧɢɟ ɜɨɞɵ ȼɨ ɜɪɟɦɹ ɫɨɡɞɚɧɢɹ ɜɯɨɞɧɨɝɨ ɨɬɜɟɪɫɬɢɹ ɞɥɹ ɫɜɟɠɟɝɨ ɜɨɡɞɭɯɚ ɭɛɟɞɢɬɟɫɶ ɱɬɨ ɜɵ ɭɞɚɥɢɥɢ ɢɡɨɥɹɰɢɨɧɧɵɣ ɦɚɬɟɪɢɚɥ P ɤɨɬɨɪɵɣ ɧɚɥɨɠɟɧ ɧɚ ɜɧɭɬɪɟɧɧɢɣ ɩɪɢɛɨɪ A I ø175 B J C K 3 ø2 8 D L ø125 E M ø100 F G 14 ø2 8 N O P H ø150 2 4...

Страница 18: ... ɢɥɢ ɩɪɢ ɧɚɧɟɫɟɧɢɢ ɩɨɬɨɥɨɱɧɵɯ ɦɚɬɟɪɢɚɥɨɜ 2 6 ɉɪɨɜɟɪɤɚ ɪɚɫɩɨɥɨɠɟɧɢɹ ɝɥɚɜɧɨɝɨ ɩɪɢɛɨɪɚ ɢ ɡɚɬɹɝɢɜɚɧɢɟ ɧɚɜɟɫɧɵɯ ɛɨɥɬɨɜ Fig 2 7 3 ɉɨɞɫɨɟɞɢɧɟɧɢɟ ɞɪɟɧɚɠɧɨɣ ɬɪɭɛɵ 30 3 1 Ⱦɪɟɧɚɠɧɵɟ ɬɪɭɛɵ Fig 3 1 VP25 O D ø32 PVC TUBE 1 100 1 2 A 9 B 1 100 C K L M D O D ø32 PVC TUBE E F G H 1 100 I O D ø38 PVC TUBE 9 J 85 1 Fig 3 2 2 O D ø32 3 O D ø32 4 5 A B C D E F G O D ø32 H I J O D ø32 1 100 K L 11 25 25 25 Max 20m 1 5 ...

Страница 19: ...ɤɟ ɫɢɫɬɟɦɵ ɜɨ ɞɹɧɨɝɨ ɬɪɭɛɨɩɪɨɜɨɞɚ 1 0 145 HBC HBC HBC 5102 1 2 3 1 5 2 4 ɉɨɞɫɨɟɞɢɧɟɧɢɟ ɜɨɞɹɧɵɯ ɬɪɭɛ 40 40 4 2 Ɍɟɩɥɨɢɡɨɥɹɰɢɹ ɜɨɞɹɧɨɣ ɬɪɭɛɵ 1 HBC 2 HBC HBC 3 Fig 4 1 HBC 20 4 5 6 7 8 A B C D 40 E F F E D C B A B A Fig 4 1 Fig 4 2 A HBC B HBC ...

Страница 20: ...ɨɞɵ ɢ ɤɨɧɬɪɨɥɶ ɡɚ ɤɚɱɟɫɬɜɨɦ ɜɨɞɵ 1 1 mg 2 20 T 60 C pH 25 C 7 0 8 0 7 0 8 0 30 300 30 300 mS m 25 C s cm 25 C mg Cl 50 50 mg SO42 50 50 pH4 8 mg CaCO3 50 50 mg CaCO3 70 70 mg CaCO3 50 50 mg SiO2 30 30 mg Fe 1 0 0 3 mg Cu 1 0 0 1 mg S2 mg NH4 0 3 0 1 mg Cl 0 25 0 3 mg CO2 0 4 4 0 6 0 7 0 JRA GL02E 1994 3 4 C B E A D E ɉɪɢɦɟɱɚɧɢɟ 1 ɉɨɞɫɨɟɞɢɧɟɧɢɟ ɧɟɫɤɨɥɶɤɢɯ ɜɧɭɬɪɟɧɧɢɯ ɩɪɢɛɨɪɨɜ ɨɞɧɢɦ ɫɨɟɞɢɧɟɧɢɟɦ ɢɥɢ ɫ...

Страница 21: ... 5 2 ɗɥɟɤɬɪɨɩɪɨɜɨɞɤɚ ɞɥɹ ɩɨɞɜɨɞɚ ɩɢɬɚɧɢɹ 60245 IEC 53 60227 IEC 53 3 Fig 5 2 A B C D ɉɪɟɞɭɩɪɟɠɞɟɧɢɟ ɇɢɤɨɝɞɚ ɧɟ ɩɨɞɫɨɟɞɢɧɹɣɬɟ ɜɧɚɯɥɟɫɬ ɫɢɥɨɜɨɣ ɤɚɛɟɥɶ ɢɥɢ ɫɨɟɞɢɧɢɬɟɥɶɧɵɣ ɤɚɛɟɥɶ ɜɧɟɲɧɟɝɨ ɩɢɬɚɧɢɹ ɗɬɨ ɦɨɠɟɬ ɩɪɢɜɟɫɬɢ ɤ ɡɚɞɵɦɥɟɧɢɸ ɜɨɡɝɨɪɚɧɢɸ ɢɥɢ ɧɟɢɫɩɪɚɜɧɨɫɬɢ Fig 5 1 Fig 5 2 1 2 M1M2 S TB2 TB5 TB15 L N A B C D E F G K ...

Страница 22: ... 5 1 5 20A 3 16 16 20 F0 25 A 2 2 5 2 5 2 5 30A 3 25 25 30 F0 32 A 2 4 0 4 0 4 0 40A 3 32 32 40 IEC61000 3 3 1 2 F0 F1 F2 F1 1 2 F2 V1 1 C V1 2 C V1 3 C V1 C V1 V2 1 PLFY VBM PEFY VMS PFFY VLRMM 18 6 2 4 2 PEFY VMA 38 1 6 C 0 01 C F2 PEFY VMS 4 PEFY VMA 1 C 8 F2 18 6 4 8 38 1 8 14 05 16 A 8 16 A 0 01 3 G1 V2 1 V2 2 V2 3 V2 V3 G1 30 30 0 1 100 100 0 1 V3 1 5 2 48 2 5 2 56 4 0 2 66 1 2 3 4 6 8 10 20...

Страница 23: ...2 S M1M2 TB3 M1M2 2 1 2 1 5 6 ɍɫɬɚɧɨɜɤɚ ɩɟɪɟɤɥɸɱɚɬɟɥɟɣ ɩɪɢ ɜɵɫɨɤɨɦ ɩɨ ɬɨɥɤɟ ɢɥɢ ɩɪɢ ɢɦɟɧɟɧɢɢ ɱɢɫɥɚ ɜɵɯɨɞɨɜ ɜɨɡ ɞɭɯɚ Fig 5 4 SWA SWB SWA SWB PLFY WP32 WP40 WP50VBM SWA SWB 1 2 3 4 4 2 5 2 7 3 5 3 3 2 7 3 0 3 5 2 2 3 0 3 3 3 5 5 7 Ɉɩɪɟɞɟɥɟɧɢɟ ɬɟɦɩɟɪɚɬɭɪɵ ɜ ɩɨɦɟɳɟɧɢɢ ɜɫɬɪɨ ɟɧɧɵɦ ɞɚɬɱɢɤɨɦ ɩɭɥɶɬɚ ɞɢɫɬɚɧɰɢɨɧɧɨɝɨ ɭɩɪɚɜ ɥɟɧɢɹ Fig 5 4 SW1 1 SW1 7 SW1 8 5 5 ɍɫɬɚɧɨɜɤɚ ɚɞɪɟɫɨɜ Fig 5 4 1 9 10 1 3 SW12 10 0 SW1...

Страница 24: ...3 F4 Manual vane angle Input display Cur Address Check M NET address Identify unit Check button 1 Maintenance 2 F1 F2 Manual vane angle 3 M NET address M NET F2 F3 F4 Ŷ ɉɪɨɰɟɞɭɪɚ ɩɨɞɬɜɟɪɠɞɟɧɢɹ F1 F2 F3 F4 Manual vane angle Input display Cur Address Check M NET address Identify unit Check button F1 F2 F3 F4 Manual vane angle Input display M NET address The air conditioner with the vane pointing dow...

Страница 25: ...ɧɧɨɣ ɪɟɲɟɬ ɤɢ Fig 6 2 3 860 860 910 910 17 22 A B C 3 D 6 2 1 ɍɞɚɥɟɧɢɟ ɜɨɡɞɭɯɨɡɚɛɨɪɧɨɣ ɪɟɲɟɬɤɢ Fig 6 3 1 2 6 2 2 ɍɞɚɥɟɧɢɟ ɭɝɥɨɜɨɣ ɩɚɧɟɥɢ Fig 6 4 1 Fig 6 3 6 4 A B C D E F G H 6 3 ȼɵɛɨɪ ɜɵɬɹɠɧɵɯ ɨɬɜɟɪɫɬɢɣ 11 1 1 2 ɉɪɢɦɟɱɚɧɢɟ Ⱦɥɹ 3 ɧɚɩɪɚɜɥɟɧɧɨɝɨ ɢ 2 ɧɚɩɪɚɜɥɟɧɧɨɝɨ ɜɵɞɭɜɚ ɩɨɠɚɥɭɣɫɬɚ ɢɫɩɨɥɶɡɭɣɬɟ ɩɥɚɫɬɢɧɤɭ ɡɚɫɥɨɧɤɢ ɜɵɬɹɠɧɨɝɨ ɨɬɜɟɪɫɬɢɹ ɨɩɰɢɹ Fig 6 1 Fig 6 2 2 0 A 17 5 0 Fig 6 3 Fig 6 4 1 4 3 1 4 1 2 6 2 ...

Страница 26: ...ɨɧɧɨɣ ɪɟɲɟɬɤɨɣ ɢ ɩɨɬɨɥɤɨɦ Ɉɫɬɨɪɨɠɧɨ Ɂɚɬɹɝɢɜɚɹ ɜɢɧɬ ɫ ɩɪɭɠɢɧɧɨɣ ɡɭɛɱɚɬɨɣ ɲɚɣɛɨɣ 2 ɫɥɟɞɭɟɬ ɩɪɢɤɥɚɞɵɜɚɬɶ ɦɨɦɟɧɬ ɧɟ ɛɨɥɟɟ 4 8 ɇ ɦ ɇɢɤɨɝɞɚ ɧɟ ɢɫɩɨɥɶɡɭɣɬɟ ɭɞɚɪɧɵɣ ɝɚɣɤɨɜɺɪɬ ɗɬɨ ɦɨɠɟɬ ɩɪɢɜɟɫɬɢ ɤ ɩɨɜɪɟɠɞɟɧɢɸ ɞɟɬɚɥɟɣ 6 4 4 ɋɨɟɞɢɧɟɧɢɟ ɩɪɨɜɨɞɨɜ Fig 6 8 2 20 CNV 2 ɉɪɢɦɟɱɚɧɢɟ ɇɟ ɨɫɬɚɜɥɹɣɬɟ ɢɡɥɢɲɟɤ ɩɪɨɜɨɥɨɱɧɨɝɨ ɜɵɜɨɞɚ ɜ ɷɥɟɤɬɪɢɱɟɫɤɨɣ ɨɬ ɜɟɬɜɢɬɟɥɶɧɨɣ ɤɨɪɨɛɤɟ ɩɪɢɛɨɪɚ 6 ɍɫɬɚɧɨɜɤɚ ɜɟɧɬɢɥɹɰɢɨɧɧɨɣ ɪɟɲɟɬɤɢ Fig 6 5 Fig...

Страница 27: ...ɤɟ ɫ ɩɨɦɨɳɶɸ ɜɢɧɬɚ 4 ɲɬ 4 8 ɤɚɤ ɩɨɤɚɡɚɧɨ ɧɚ ɢɥɥɸɫɬɪɚɰɢɢ 6 2 D E F G H i see sensor PLP 6BAE 6 6 ɍɫɬɚɧɨɜɤɚ ɭɝɥɨɜɨɣ ɩɚɧɟɥɢ i see sensor Fig 6 10 PLP 6BAE CN4Y CN6Y i see sensor 7 i see sensor 7 4 2 4 3 i see sensor 6 2 i see sensor 1 6 6 7 Ȼɥɨɤɢɪɨɜɤɚ ɧɚɩɪɚɜɥɟɧɢɹ ɜɨɡɞɭɲɧɨɝɨ ɩɨɬɨɤɚ ɜɜɟɪɯ ɜɧɢɡ Fig 6 11 1 2 5 7 6 8 ɉɪɨɜɟɪɤɚ PLP 6BAE i see sensor i see sensor 6 6 i see sensor Fig 6 9 Fig 6 11 Fig 6 10 A ...

Страница 28: ...ɪɨɠɧɨ ɉɨɞɤɥɸɱɢɬɟ ɷɥɟɤɬɪɨɩɢɬɚɧɢɟ ɩɪɢɛɨɪɚ ɧɟ ɦɟɧɟɟ ɱɟɦ ɡɚ 12 ɱɚɫɨɜ ɞɨ ɧɚɱɚɥɚ ɪɚɛɨɬɵ ɇɟ ɩɪɢɤɚɫɚɣɬɟɫɶ ɤ ɜɵɤɥɸɱɚɬɟɥɹɦ ɦɨɤɪɵɦɢ ɪɭɤɚɦɢ ɇɟ ɢɫɩɨɥɶɡɭɣɬɟ ɤɨɧɞɢɰɢɨɧɟɪ ɜɨɡɞɭɯɚ ɟɫɥɢ ɟɝɨ ɩɚɧɟɥɢ ɢ ɤɪɵɲɤɢ ɫɧɹɬɵ ɇɟ ɨɬɤɥɸɱɚɣɬɟ ɩɢɬɚɧɢɟ ɧɟɦɟɞɥɟɧɧɨ ɩɨɫɥɟ ɜɵɤɥɸɱɟɧɢɹ ɩɪɢɛɨɪɚ ɉɨɫɥɟ ɩɨɞɚɱɢ ɜɨɞɵ ɜ ɫɢɫɬɟɦɭ ɜɨɞɹɧɵɯ ɬɪɭɛɨɩɪɨɜɨɞɨɜ ɭɞɚɥɢɬɟ ɜɨɡɞɭɯ ɢɡ ɫɢɫɬɟɦɵ ɉɨɞɪɨɛɧɨɫɬɢ ɩɨ ɭɞɚɥɟɧɢɸ ɜɨɡɞɭɯɚ ɩɪɢɜɟɞɟɧɵ ɨɬɞɟɥɶɧɨ ɜ ɪɭɤɨɜɨɞɫɬɜɟ ɩɨ ɨɛɫɥ...

Страница 29: ...u Cursor Service menu Test run Drain pump test run Fig 7 5 F1 F2 F3 F4 Service menu Cursor Select Enter maintenance password Fig 7 3 7 4 ɉɪɨɜɟɪɤɚ ɞɪɟɧɚɠɚ Fig 7 8 ɉɨɫɥɟ ɡɚɜɟɪɲɟɧɢɹ ɷɥɟɤɬɪɢɱɟɫɤɢɯ ɪɚɛɨɬ Ⱦɨ ɡɚɜɟɪɲɟɧɢɹ ɷɥɟɤɬɪɢɱɟɫɤɢɯ ɪɚɛɨɬ 220 240 L N SWE Fig 7 8 A B 1000 C D F1 F2 F3 F4 Cool Pipe Auto Switch disp Mode Fan Remain Test run Fig 7 6 F1 F2 F3 F4 Remain Vane Fig 7 7 ɒɚɝ 2 ȼɵɩɨɥɧɢɬɟ ɩɪɨɛɧɵɣ ɩɭ...

Страница 30: ...is manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in UNITED KINGDOM BH79D500K02 ...

Отзывы: