GB
5HIULJHUDQWSLSHDQGGUDLQSLSH
'UDLQDJHSLSLQJZRUN)LJ
8VH932'¡´39&78%(IRUGUDLQSLSLQJDQGSURYLGHRU
more downward slope.
%HVXUHWRFRQQHFWWKHSLSLQJMRLQWVXVLQJDSRO\YLQ\OW\SHDGKHVLYH
2EVHUYHWKHILJXUHIRUSLSLQJZRUN
8VHWKHLQFOXGHGGUDLQKRVHWRFKDQJHWKHH[WUDFWLRQGLUHFWLRQ
1
Correct piping
2
Wrong piping
A
Insulation (9 mm or more)
B
'RZQZDUGVORSHRUPRUH
C
Support metal
K
Air bleeder
L
Raised
M
Odor trap
Grouped piping
D
O.D. ø32 PVC TUBE
E
Make it as large as possible
F
Indoor unit
G
Make the piping size large for grouped piping.
H
'RZQZDUGVORSHRUPRUH
I
2'¡39&78%(IRUJURXSHGSLSLQJ
(9 mm or more insulation)
J
8SWRPP
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 3-5)
(Affix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32).
(Affix the pipe using PVC adhesive then secure it with a band.)
3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a
band. (Both insulating material and band are supplied with the unit.)
A
Unit
B
Insulating material
C
Band (large)
D
Drain port (transparent)
E
Insertion margin
F
Matching
G
Drain pipe (O.D. ø32 PVC TUBE)
H
Insulating material (purchased locally)
I
Transparent PVC pipe
J
2'¡39&78%(6ORSHRUPRUH
K
Band (middle)
L
Drain socket
)LJ
)LJ
(mm)
Max. 15cm
0D[P
1.5~2m
1
2
(OHFWULFDOZRUN
(OHFWULFDOZRUN
,QGRRUXQLW)LJ)LJ)LJ
1. Remove 2 screws to detach the electric component cover.
2. Route each cable through the wiring intake into the electric component box. (Procure
power supply cable and control cable locally.)
3. Securely connect the power supply cable and control cable to the terminal
blocks.
4. Secure the cables with clamps outside the electric component box.
5. Attach the electric component cover as it was.
'RQRWDOORZVODFNHQLQJRIWKHWHUPLQDOVFUHZV
Always install earth.
(Earth cable dia: Thicker than 1.6 mm)
)L[SRZHUVXSSO\FDEOHDQGFRQWUROFDEOHWRHOHFWULFFRPSRQHQWER[E\XVLQJEXIIHU
bushing for tensile force. (PG connection or the like.)
A
Electric component cover
B
Electric component box
C
Entry for power supply cable
D
Entry for remote control cable and trans-
mission cable
E
Cable clamp
F
Power supply terminals (L, N)
G
Transmission terminals (M1, M2, S)
H
MA Remote controller terminal (1. 2)
I
Indoor controller
J
Remote control cable
K
Transmission cable
L
Power supply cable
M
Cable strap
N
L
F
L
)LJ
55 mm
12 mm
JKL
D
C
I
A
B
H
E
F
G
K
M
C
J
A
A
I
J
C
,
K
B
C
F
K
30 30
30
D E E
L
G
H
M
Secure with a band
4
(small) at the
location shown in the diagram