13
0
10
20
30
40
50
-20
-10
0
10
20
30
40
50
< Thermistor for lower temperature >
Temperature (
:
)
Resistance (K
"
)
4
[
4
3
6
5
[
3
2
[
2
1
[
1
[
4
[
3
[
2
[
1
Controller board
Drive circuit
Connector(CN60)
DC12V
Brown
Red
Blue
Orange
Yellow
White
M
4
6
2
3
5
1
Blue
Brown
Yellow
Orange
Red
White
Linear expansion valve
<Thermistor Characteristic graph>
Room temperature thermistor(TH21)
Liquid pipe temperature thermistor(TH22)
Gas pipe temperature thermistor(TH23)
Thermistor R
0
=15k
'
± 3%
Fixed number of B=3480k
'
± 2%
Rt=15exp { 3480( ) }
0
:
15k
'
10
:
9.6k
'
20
:
6.3k
'
25
:
5.2k
'
30
:
4.3k
'
40
:
3.0k
'
Thermistor for
lower temperature
Linear expansion valve
①
Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
1
273+t
1
273
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color of
the lead wire.
OC254---1.qxp 2/19/01 11:15 AM Page 13