Total operating current of the indoor unit
Minimum wire thickness (mm²)
Ground-fault interrupter *1
Local switch (A)
Breaker for wiring
(NFB)
Main cable
Branch
Ground
Capacity
Fuse
F0 = 16 A or less *2
1.5
1.5
1.5
20 A current sensitivity *3
16
16
20
F0 = 25 A or less *2
2.5
2.5
2.5
30 A current sensitivity *3
25
25
30
F0 = 32 A or less *2
4.0
4.0
4.0
40 A current sensitivity *3
32
32
40
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 =
^
V1 × (Quantity of Type1)
C
`
^
V1 × (Quantity of Type2)
C
`
^
V1 × (Quantity of Type3)
C
`
^
V1 × (Quantity of Others)
C
`
Indoor unit
V1
V2
Type 1
PLFY-VBM, PMFY-VBM, PEFY-VMS, PFFY-VKM,
PCFY-VKM, PKFY-VHM, PKFY-VKM, PLFY-VCM
18.6
2.4
Type 2
PEFY-VMA
38
1.6
Type 3
PEFY-VMHS
13.8
4.8
Others
Other indoor unit
0
0
C : Multiple of tripping current at tripping time 0.01 s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
*Condition PEFY-VMS × 4
PEFY-VMA × 1, C = 8 (refer to right sample chart)
F2 = 18.6 × 4
8
38 × 1
8
= 14.05
ĺ
16 A breaker (Tripping current = 8 × 16 A at 0.01 s)
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type1)
V2 × (Quantity of Type2)
V2 × (Quantity of Type3)
V2 × (Quantity of Others)
V3 × (Wire length
>
km
@
)
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Wire thickness
V3
1.5 mm
2
48
2.5 mm
2
56
4.0 mm
2
66
.
. Types of control cables
1. Wiring transmission cables
Types of transmission cable
Shielding wire CVVS or CPEVS
Cable diameter
More than 1.25 mm
2
Length
Less than 200 m
2. M-NET Remote control cables
Types of remote control cable
Shielding wire MVVS
Cable diameter
More than 0.5 to 1.25 mm
2
Length
Add any portion in excess of 10 m to within the
longest allowable transmission cable length
200 m.
. MA Remote control cables
Types of remote control cable
2-core cable (unshielded)
Cable diameter
0.3 to 1.25 mm
2
Length
Less than 200 m
. Electrical work
6000
600
60
10
1
0,1
0,01
1
2
3
4
6 8
C
10
20
SAMPLE
Sample chart
T
ripping T
ime
>
s
@
Rated Tripping current (x)
0.01
0.1