30
OPERATING PROCEDURE
PHOTOS
Photo 10
Photo 9
Screws of the
vane motor
Lead wires of the vane motor
Photo 11
Screw of
the motor band
Screw of the
ground wire
Screws of the vane
motor support
6. Removing the vane motor and the limit switch (vane
under)
(1) Remove the panel. (Refer to procedure 1)
(2) Remove the screws of the nozzle assembly (lower). (See
Photo 8)
(3) Remove the drain hose from the nozzle assembly (lower)
and pull out the nozzle assembly (lower) toward you.
(4) Remove the tape fixing the lead wires of the vane motor
from the nozzle assembly <lower>. (See Photo 9)
(5) Remove the screws of the vane motor support, and then
the vane motor support.
(6) Remove the screws of the vane motor, and then the vane
motor from the vane motor support.
(7) Disconnect the connector from the vane motor.
(8) Remove the limit switch (vane under) (LS).
7. Removing the indoor fan motor
(1) Remove the panel. (Refer to procedure 1)
(2) Remove the nozzle assembly (lower) and the drain hose.
(Refer to procedure 6)
(3) Remove the screw of the ground wire of the indoor fan
motor (lower), and then the ground wire. (See Photo 11)
(4) Remove the screw of the motor band, and then the motor
band. (See Photo 11)
(5) Remove the line flow fan and the indoor fan motor (lower)
from the box.
Photo 8
Screw of
the nozzle
Screw of
the nozzle
Drain
hose
OCH537