19
9
TROUBLE SHOOTING
9-1. HOW TO CHECK THE PARTS
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(Surrounding temperature 10
- 30
)
Disconnect the connector then measure the resistance valve with a tester.
(Surrounding temperature 20
)
Linear expansion
valve
(LEV)
(Refer to the next page for a detail.)
Room temperature
thermistor (TH21)
Liquid pipe temperature
thermistor (TH22)
Gas pipe temperature
thermistor (TH23)
Normal
4.3k
~9.6k
Abnormal
Open or short
Abnormal
Open or short
Normal
200
$
10%
(1)-(5)
White-Red
(2)-(6)
Yellow-Brown
(3)-(5)
Orange-Red
(4)-(6)
Blue-Brown
Orange
Red
White
Blue
Brown
Yellow
M
Refer to 9-2.
Fan motor
(MF1,2)
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20
- 30
)
Vane motor (MV2)
Normal
Connector
Abnormal
186~214
Open or short
Brown — Yellow
Brown — Blue
Red — Orange
Red — Pink
(Refer to the next
page for a detail.)
Blue
Yellow Brown
Orange
Red
Pink
M
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20
- 30
)
Vane motor (MV1)
Normal
Connector
Abnormal
282~306
Open or short
Yellow
Brown
Red
Brown — Red
Brown — Orange
Brown — Yellow
Brown — Blue
Orange Green
M
PFFY-P20VKM-E2
PFFY-P25VKM-E2
PFFY-P32VKM-E2
PFFY-P40VKM-E2
OCH537