8-5.External input/output specifications
32
(1) Input/output specifications
(2) Wiring
Function
Usage
Signals
Function
Usage
Signal
Input
Start/stop
Turning
ON/OFF
the indoor
unit
Pulse
(a-contact with voltage/without
voltage)
✻
1
<With voltage>
Power Source: DC12~24V
Electrical Current:
Approximately 10mA (DC12V)
<Standard Pulse>
Output
No.1
Operation
Status
Obtaining signals indicating
operation status of indoor units
in each refrigerant circuit.
Relay a-contact
output
DC 30V or
AC 100V/200V
Standard Current :
1A
Minimum Current :
1mA
No. 1
Error Status
Obtaining signals indicating
error status of indoor units in
each refrigerant circuit.
No. 2
Operation
Status
Obtaining signals indicating
operation status of indoor units
in each refrigerant circuit.
No. 2
Error Status
✻
✻
✻
20HP only
Obtaining signals indicating
error status of indoor units in
each refrigerant circuit.
over 200ms
✻
1 Use minute-current contact (DC12V 1mA)
External input/output board
Power Source for Display
No.1 Operation Status
No.1 Error Status
✻
No.2 Operation Status
✻
20HP only
✻
No.2 Error Status
Common
Stop/Start
Input with voltage (polarized)
Input without voltage
Relay Contact Point Output
Stop/Start
External power source
Connection to terminal board
Connection with connectors
L1
L2
L3
L4
SW12
Short Circuit
SW11
CN53
1
2
3
4
5
1
2
3
4
5
TB21
TB22
TB23
XA
XB
XC
XE
XD
XE
XD
XC
XB
XA
COM
1
2
BC
B1
B2
AC
A1
Short Circuit
A2
3
4
5
CN54
Maximum : 100 m
<Input with Applied Voltage (polarized)>
DC12~24V
Electrical current input (per contact)
Approximately 10mA (DC12V)
SW12
Remote start/stop switch
Each pressing of the SW (Pulse input) switches
between ON and OFF.
Remote start/stop
✻
Each pressing pf the SW (Pulse input) switches
between ON and OFF.
External powe
source
<Input without voltage applied>
Minute-current contact: DC12V 1mA
SW11
<Relay contact output>
DC30V 1A
AC220-240V 1A
No.1 Operation Status Indicator Lamp
L1
No.1 Error Status Indicator Lamp
L2
Power supply
for displays
No.2 Operation Status Indicator Lamp
L3
No.2 Error Status Indicator Lamp
L4
Relay
(Permissible Electrical Current: 10mA~1A)
XA~XE
●
Setting on the Indoor Unit
Confirm the following setting when using external input.
1
No.1, No.2 Controller board Dip SW 3-8: ON (Factory Setting: ON; External input will not be available when OFF.)
2
No.1, No.2 address board Dip SW 1-10: OFF (Factory Setting: OFF; External input will not be available when ON.)
3
Normal/Local switch inside the unit controller box is set to “Normal.” (Factory Setting: Normal; External input will not be
available when it is set to “Local.”)