1-2. List of Possible Combinations of Indoor and Outdoor Units
Units
✻
1: Refer to the following pages for detailed specifications of each unit.
✻
2: The values in the chart are as follows: Q, Total Capacity [kW]; W, Total Input [kW]; A, Total Electrical Current [A]; Power Factor [%].
They were measured at operation under the following conditions: Indoor Intake Temperature: 27˚CDB/19˚CWB,
Outdoor Intake Temperature 35˚CDB with 7.5m of refrigerant piping.
Outdoor Units
Indoor Units
Down-flow Type
380-415V(50Hz)
400,415V(60Hz)
20HP
380-415V(50Hz)
400,415V(60Hz)
10HP
Model Name
Power Source
380
/400
/415V
Q
W
A
PUD-
P250YMF-C
10HP
Unit Horse Power
Series Name
PFD-P250VM-A(-H)
PFD-P500VM-A(-H)
56.0
21.8
36.1/34.3/33.0
91
28.0
10.9
18.3/17.3/16.3
90
Power
factor
Air-cooling
1-3. Unit Specifications
28.0
3N ~ 380/400/415V 50/60Hz
Capacity
kW
Power source
✻
1
✻
2
kW
A
m
3
/min
kW
kW
A
kW
mm
dB(A)
kg
Power input
Current
Fan
Airflow rate
Type
✕
Quantity
Motor output
Type
Motor output
Crankcase heater
Compressor
Refrigerant / Lubricant
External finish
High pressure protection
Inverter
Compressor / Fan
External dimension
Protection
devices
Refrigerant piping diameter Liquid / Gas
Noise level
Note: Cooling capacity indicates the maximum value at operation under the following condition.
✻
1 Indoor 27˚CDB/19˚CWB, Outdoor 35˚CDB
Pipe length 7.5m, Height difference 0m
✻
2 It is measured in anechoic room.
Net weight
Operating temperature range
1715(H)
✕
990(W)
✕
840(L)
Propeller fan
185
0.38
Hermetic
7.5
0.045 (240V)
R407C/MEL32
Starting current
12
DC bus current protection, thermal switch
ø
12.7 flare /
ø
28.58 Flange
Steel plate painting with polyester powder <MUNSELL 5Y8/1 or similar>
2.94MPa
231
Indoor:12˚CWB ~ 24˚CWB
Outdoor:-15˚CDB ~ 43˚CDB
(0˚CDB ~ 43˚CDB with outdoorunit at lower position)
8.4
14.0/13.3/12.8
PUD-P250YMF-C
Over current protection / Thermal switch
56
(1) Outdoor Unit