- 5 -
[
III
SPECIFICATIONS ]
3-2. Electrical component specifications
Model
Component
Symbol
PEFY-P20VMR-E-L/R
PEFY-P25VMR-E-L/R
PEFY-P32VMR-E-L/R
Transformer
T
(Primary) 50/60Hz 220-240V (Secondry) (23.5V 0.9A)
Room temperature
thermistor
TH21
Resistance 0°C/15k
Ω
, 10°C/9.6k
Ω
, 20°C/6.3k
Ω
, 25°C/5.4k
Ω
, 30°C/4.3k
Ω
, 40°C/3.0k
Ω
Liquid pipe
thermistor
TH22
Resistance 0°C/15k
Ω
, 10°C/9.6k
Ω
, 20°C/6.3k
Ω
, 25°C/5.4k
Ω
, 30°C/4.3k
Ω
, 40°C/3.0k
Ω
Gas pipe thermistor
TH23
Resistance 0°C/15k
Ω
, 10°C/9.6k
Ω
, 20°C/6.3k
Ω
, 25°C/5.4k
Ω
, 30°C/4.3k
Ω
, 40°C/3.0k
Ω
Fuse
(Control board)
F1
250V 6.3A
Fan motor
(with Inner-
thermostat)
MF
4-pole, Output 18W
4-pole, Output 23W
Inner-thermostat
(Fan motor)
OFF 135°C±5°C ON 86°C±15°C
Fan motor capacitor
C1
1.5µF × 440V
Linear expansion
valve
LEV
12VDC Stepping motor drive port diameter ø3.2
(0~1800 pulses <on R410-compatible outdoor units>,
0~2000 pulses <on other types of outdoor units>)
Power supply
terminal block
TB2
(L, N,
) 330V 30A
Transmission
terminal block
TB5 TB15
(1, 2), (M1, M2, S) 300V 10A