34
Total
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Service Ref.
SHF
BF
W
kW
V
A
V
A
MPa
MPa
°
C
°
C
°
C
m
°
C
°
C
°
C
°
C
°
C
Mode
Capacity
Input
Indoor unit Service Ref.
Phase,Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
PEAD-P1.6EA
PEAD-P1.6EA
1 , 50
240
PU-P1.6VGA
1 , 50
240
PEAD-P2EA
PEAD-P2EA
1 , 50
240
PU-P2VGA
1 , 50
240
PEAD-P2.5EA
PEAD-P2.5EA
1 , 50
240
PU-P2.5VGA
1
1 , 50
240
Cooling
4,500
1.75
0.55
7.43
2.02
0.50
78.5
52.4
8.1
5
27
19
14.0
35
24
0.72
0.21
Cooling
5,550
2.44
0.63
10.39
2.35
0.51
85.3
55.2
7.0
5
27
19
13.6
35
24
0.74
0.19
Cooling
6,700
2.68
0.72
11.27
2.16
0.52
78.5
49.6
8.3
5
27
19
13.8
35
24
0.71
0.19
(22.0)
(5.3)
(24.0)
(5.2)
(20.6)
(5.1)
(kgf/
F
)
(kgf/
F
)
D.B.
W.B.
D.B.
D.B.
W.B.
Cooling only type Rating Conditions (ISO T1)
The unit of pressure has been changed to Mpa based on international SI system.
The conversion factor is : 1 (Mpa) = 10.2 (kgf/cm
2
)