22
Cooling capacity correction factors
Service Ref.
Refrigerant piping length (one way)
5m
10m
15m
20m
25m
30m
35m
40m
45m
50m
PEHD-P1.6EAH
PEAD-P1.6EA
1.00
0.993
0.984
0.978
0.969
0.961
0.956
0.948
–
–
PEHD-P2EAH
PEAD-P2EA
1.00
0.993
0.984
0.978
0.969
0.961
0.956
0.948
–
–
PEHD-P2.5EAH
PEAD-P2EA
1.00
0.989
0.980
0.970
0.960
0.950
0.940
0.930
0.920
0.910
PEHD-P3EAH
PEAD-P3EA
1.00
0.981
0.968
0.952
0.940
0.925
0.913
0.900
0.886
0.874
PEHD-P4EAH
PEAD-P4EA
1.00
0.989
0.980
0.970
0.960
0.950
0.940
0.930
0.920
0.910
PEHD-P5EAH
PEAD-P5EA
1.00
0.981
0.968
0.952
0.940
0.925
0.913
0.900
0.886
0.874
PEHD-P6EAH
PEAD-P6EA
1.00
0.975
0.955
0.935
0.918
0.900
0.884
0.869
0.855
0.840
OUTDOOR D.B.(
°
C)
TOTAL INPUT (RATIO)
CAPACITY (RATIO)
INDOOR W.B.(
°
C)
INDOOR W.B.(
°
C)
1.4
1.2
1.0
0.8
10
22
20
18
16
22
20
18
16
20
30
46
40
0
-5
1.2
1.0
0.8
0.6
0.4