9-6. HOW TO CHECK THE PARTS
PCA-A24KA4 PCA-A30KA4 PCA-A36KA4 PCA-A42KA4
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 50
"
F~86
"
F)
(Refer to the next page for a detail.)
Room temperature
thermistor (TH1)
Liquid pipe thermistor
(TH2)
Condenser/evaporator
temperature thermistor
(TH5)
Normal
4.3k
~9.6k
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(Winding temperature 68°F)
Measure the resistance between the terminals with a tester.
Drain pump (DP) (Option)
i-see sensor
(Option)
Drain float switch (FS)
(Option)
1
3
YLW
YLW
Normal
Abnormal
290
Open or short
State of moving part
Abnormal
DOWN
Other than open
UP
Normal
Open
Short
Other than short
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 68°F~86°F)
Vane motor (MV)
Vane motor for
i-see sensor (Option)
Abnormal
Open or short
Red - Yellow
Red - Blue
Red - Orange
Red - White
Connector
Normal
300
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 68°F~86°F)
Abnormal
Open or short
Red - Yellow
Red - Blue
Red - Orange
Red - White
Connector
Normal
250
Normal
Turn on the indoor unit with the black plastic tape on the outside of i-see sensor controller board.
i-see sensor rotates then pull out the connector of motor for i-see sensor.
With electricity being turned on, measure the power voltage between connectors with tester.
Abnormal
DC 1.857V~ 3.132V
Other than the normal
DC 0.939V~ 1.506V
(–)—
(+)
i-see sensor connector
i-see sensor (At the ambient temperature of 50°F~104°F)
NOTE
: Be careful not to discharge static electricity into electronic device.
(+)—
(–)
Other than the normal
4 3 2 1
4 3
1
Blue BlackPink Brown
2
Black plastic tape
2
1
Moving part
4
3
Switch
Magnet
Moving
Part
Yellow
Blue
Red
Orange
White
Yellow
Blue
Red
Orange
White