26
9-7. TEST POINT DIAGRAM
Indoor controller board
PCA-A24KA4 PCA-A30KA4 PCA-A36KA4 PCA-A42KA4
CN3C
Transmission (Indoor/outdoor)
(0~24V DC)
SW2
Capacity setting
SW1
Model selection
CN2L
Connector (LOSSNAY)
CN41
Connector (HA terminal-A)
CN90
Connect to the IR wireless
remote controller board (CNB)
CN20
Room temperature
thermistor (TH1)
CN22
Connect to the terminal block (TB5)
(Remote controller connecting wire)
(10.4~14.6V DC)
LED2
Power supply (R.B)
LED1
Power supply (I.B)
LED3
Transmission
(Indoor/outdoor)
CNP
Drain-pump output (DP)
(208/230V AC) (option)
CN01
Connect to the Terminal Block
(TB4)
(Indoor/outdoor connecting line)
Between
and
208/230V AC
CNV
Vane motor output (MV)
12V pulse output
SWE
Emergency operation
Jumper wire J41,J42
Pair No. setting for IR wireless
remote controller
FUSE
6.3A /250V
CNMF
Fan motor
-
: DC 294~325V
-
: DC15V
V
CC
: Voltage between pins of
C955 15VDC
(Same as
(+)–
(-) of CNMF)
CN44
Pipe temperature
thermistor
-
: Liquid (TH2)
-
: Cond./Eva. (TH5)
CN4F
Drain float switch (FS)
(option)
CN51
Centrally control
-
: Control signal
13VDC pulse input (
: +)
-
: Operation indicator
13VDC (
: +)
-
: Malfunction indicator
13VDC (
: +)
CN4Y
i-see sensor (option)
CN30
Connector (LLC)
CN24
Connector (Back-up heating)
CN6Y
sensor motor (option)
CN105
RFI
(Radio frequency interface)