75
Specifications
Controller specifications
Specifications
Power Source
17–32 VDC
*1
(for connection to M-NET only)
Receives power from outdoor units via
the M-NET transmission cable. The
power consumption coefficient
*2
of the
Smart ME Controller is “0.5”.
Operating
conditions
Temperature
Operating temperature range
0ºC – +40ºC (+32ºF – +104ºF)
Storage temperature range
-20ºC – +60ºC (-4ºF – +140ºF)
Humidity
20%–90% RH (Non-condensing)
Weight
0.3 kg (11/16 lbs)
External dimensions
(W x H x D)
140 x 120 (123) x 25 (28.8) mm
5-17/32 x 4-3/4 (4-27/32) x 1 (1-5/32) in
* The numbers in the parenthesis indicate the dimensions including the protruding
parts.
*1 Not for use with a generic DC power supply device.
*2 “Power consumption coefficient” is a coefficient to calculate the relative power consumption of the devices that receive
power through the M-NET transmission cable.
Refer to section 4 “System diagram” in Chapter 1 in the Installation Manual.