(3) List of switch settings
System remote controller (SF44SRA)
Name
Switch NO.
Setting method
Function
SW3-1
OFF
ON
Master SC setting
Slave SC setting
To set system controller as master
To set system controller as slave
External input function changeover
SW3-2, 3
Operation prohibit range setting changeover
SW3-5
Set the range to control the operation prohibit functions used with this system.
ON
OFF
Including system controller
Only local remote controller To prohibit operation of only the local remote controller
To prohibit operation of the local remote controller
and other system controllers
Not used
SW3-7
Not used
SW3-8
OFF
OFF
OFF
OFF
OFF
OFF
System controller master/slave
setting changeover
Default
setting
1
2
3
4
2
SW3
External input signal function
Do not use external inputs
Change between emergency stop/normal
Input state
Level input
Set ON/OFF
Level input
Set ON/OFF, prohibit/enable
Pulse input (0.5sec or more)
OFF
OFF
ON
ON
3
OFF
ON
OFF
ON
No.
Operation prohibit setting changeover
* Valid only when SW3-4 is ON
SW3-4
Set the local remote controller operation prohibit functions
ON
OFF
Operation prohibit enable
Operation prohibit use disable To not use this system's operation prohibit function
To use this system's operation prohibit function
Schedule timer (YT34STA)
Name
Switch NO.
Setting method
Function
SW3-1
OFF
ON
Master SC setting
Slave SC setting
To set system controller as master
To set system controller as slave
OFF
ON
Celsius display
Fahrenheit display
To display set temperature as Celsius (
;
)
To display set temperature as Fahrenheit (
,
)
External input function changeover
SW3-2, 3
Operation prohibit range setting changeover
SW3-5
Set the range to control the operation prohibit functions used with this system.
ON
OFF
Including system controller
Only local remote controller To prohibit operation of only the local remote controller
To prohibit operation of the local remote controller
and other system controllers
Set temperature display changeover
SW3-6
OFF
OFF
OFF
OFF
OFF
System controller master/slave
setting changeover
Default
setting
1
2
3
4
2
SW3
External input signal function
Do not use external inputs
Change between Emergency stop/Normal
Input state
Level input
Set ON/OFF
Level input
Set ON/OFF, prohibit/permit
Pulse input (0.5sec or more)
OFF
OFF
ON
ON
3
OFF
ON
OFF
ON
No.
Operation prohibit setting changeover
* Valid only when SW3-4 is ON
SW3-4
Set the local remote controller operation prohibit functions
ON
OFF
Operation prohibit enable
Operation prohibit use disable To not use this system's operation prohibit function
To use this system's operation prohibit function
OFF
Not used
SW3-7
OFF
Not used
SW3-8
ON/OFF remote controller (YT40ANRA)
Name
Switch NO.
Setting method
Function
SW4-1
OFF
ON
Master SC setting
Slave SC setting
To set system controller as master
To set system controller as slave
External input function changeover
SW4-2, 3
OFF
OFF
System controller master/slave
setting changeover
Default
setting
1
2
3
4
2
SW4
External input signal function
Do not use external inputs
Change between Emergency stop/Normal
Input state
Level input
Set ON/OFF
Level input
Set ON/OFF, prohibit/permit
Pulse input (0.5sec or more)
OFF
OFF
ON
ON
3
OFF
ON
OFF
ON
No.
$