Cable(100mm)

Cable(5300mm)

1

Part
name

Q'ty

Figure

External LEV Box

Joint pipe

Pipe cover

Band

Fastener

2

2

6

2

183

102

146

31

50

70

Cable (accessory) hole

40

122

82

200

70

Center line

Mounting plate

Remove the two screws (4  10)

Mounting plate

Install the two screws (4  10)

Center line

4-Oval hole

160

11

41

62

82

62

Center line

164

4-Oval hole

4-Oval hole

5

10

(R)

Oval hole dimension

164

Center line

w

Refer to this label when connecting the on-site refrigerant pipe. Make sure to keep

   the side with this label upward, and install the External LEV Box

1

 horizontally.

Washer (procure locally)

Washer (procure locally)

Nut (procure locally)

Nut (procure locally)

3. Set the External LEV Box

1

 to the

    suspension bolt and tighten each
    nuts and washers.

Two installation patterns are available by changing the position of the
mounting plate. Install the four screws (procure locally) in oval holes.

Install the four screws (procure locally) in oval holes.

443

295

(155)

(81)

(155)

133

(81)

External LEV Box

1

Joint pipe

2

Connection 

[

6.35

Connection 

[

9.52

To Outdoor Unit

To Indoor Unit

Please keep the right direction by following the 
arrows below when installing this unit.
This LEV Box must be installed horizontally, keeping
this side up.

BG79K515H02

2. Change the position of External LEV Box

1

 mounting plate as shown below.

    The mounting plate can also be fixed to suspension bolts before it is fixed to

the External LEV Box

1

.

Mounting plate

Remove the two screws (4  10)

Mounting plate

Install the two screws (4  10)

Safety precautions

Precautions that should be observed to prevent injury or damage to the premises and/or contents thereof.

Warning

Caution

Precautions that should be observed to prevent serious injury or death.

 

• Before installing the unit, make sure to read all the “Safety precautions”.
• These precautions provide very important points regarding safety. Make sure to follow them.
• Symbols used in this manual are categorized according to the degree of risk when used improperly as follows:

Warning

• If the unit is installed improperly, water leakage, electric shock or fire may be caused.

The unit must not be installed by the user. Ask the dealer or 
an authorized company to install the unit.

Installation must be properly done following this installation manual.

• If the unit is installed improperly, water leakage, electric shock or fire may be caused.

Caution

•  Children may put plastic bags over their head. And it may cause
   suffocation.

Keep plastic bags away from children.

• If piping is not properly installed, water leakage may result, which will 

make the ceilings, floors or other household items wet.

Perform drain piping according to the installation manual and
make sure water is drained properly and keep drain piping
warm to prevent bedewing.  

Before installation (relocation) and electrical work

• If proper electrical cables are not used, short circuit, electric shock or 

fire may be caused.

Use proper electrical cables to meet the standard for current 
capacity.

• Improper heat insulation may cause condensation on parts such as 
  pipings, and wet ceilings, floors or other valuable items.

Make sure heat insulation for refrigerant piping is properly 
installed to prevent bedewing.

Inserts rated at 100-150kg each
(procure locally)

Suspension bolts M10 (3/8")(procure locally)

Steel reinforcing rod

Install the suspension bolts as shown below or install it with angles or blocks.

1. Install the suspension bolts M10 (3/8")(procure locally). Decide the installation

location referring to the figure on the right. The unit must be suspended firmly.

Package air-conditioner Optional parts
Installation Manual of EXTERNAL LEV BOX
PAC-SG95LE-E
[For CITY MULTI INDOOR UNIT 20-63 MODELS]

Before installing the unit, make sure to read the installation manual of the indoor unit and this manual.

1

Parts check

This unit is provided with this manual and following parts in the box.

2

Installation procedure

Connect the External LEV Box to the liquid pipe and install it inside the ceiling (Do not install in an outdoor location. It may cause a
breakdown). Make sure to install the access door on the ceiling.  

The installation patterns below are available. Select the installation pattern according to the preferred installation method. The
distance between indoor unit and External LEV Box is within 5 m. (Pipe: 5m, Cable: 5.3m)

Outline of External LEV Box (Factory shipment)

(Unit: mm)

Installation pattern  A (Using Suspension bolts; recommended pattern)

(Unit: mm)

Installation pattern  B

(Unit: mm)

Installation pattern  C

(Unit: mm)

2-1  Installation  location

Note: Make sure to complete installation work of External LEV Box of optional parts before turning on the indoor unit. This unit may 

run improperly if the unit is not installed following this manual.

• After installation, perform the test run to ensure normal operation. Then explain the user the  "Safety Precautions", use and 

maintenance of the unit based on the information in the Operation Manual. Both the Installation Manual and the Operation 
Manual must be given to the user. These manuals must always be kept by the actual users.