background image

9

GB

4. Selecting an installation site and installing the controller

Avoid locations in direct sunlight.

Avoid locations exposed to outside air.

Avoid locations exposed to the elements or water splashes.

Avoid locations exposed to stream or oil vapour.

Avoid locations where combustible gas may leak, settle or be generated.

Avoid installation near machines emitting high-frequency waves.

Avoid places where acidic solutions are frequently handled.

Avoid places where sulphur-based or other sprays are frequently used.

4.1. Combining indoor units with outdoor 

units

For combining indoor units with outdoor units, refer to the outdoor unit installation 
manual.

4.2. Installing the controller

[Fig. 4.2.1] (P.3)

A

Controller

B

Screw (field supply)

When mounting the controller, use 4 supplied controller mounting screws, and 
mount it vertically.

 Warning:

Do not mount the horizontally laid controller.

5. Refrigerant pipe specifications

To avoid dew drops, provide sufficient antisweating and insulating work to the 
refrigerant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commer-
cially available insulating material (with a heat-resisting temperature of more than 
100

 

°C and thickness given below) onto both liquid and gas pipes.

Be also sure to wind commercially available insulating material (with a form poly-
ethylene’s specific gravity of 0.03 and thickness given below) onto all pipes which 
pass through rooms.

1

Select the thickness of insulating material by pipe size.

2

If the unit is used on the highest story of a building and under conditions of 
high temperature and humidity, it is necessary to use pipe size and insulating 
material’s thickness more than those given in the table above.

3

If there are customer’s specifications, simply follow them.

6. Connecting refrigerant pipes

6.1. Refrigerant piping work

This piping work must be done in accordance with the installation manuals for 
both outdoor unit and BC controller (simultaneous cooling and heating series 
R2).

Series R2 is designed to operate in a system that the refrigerant pipe from an 
outdoor unit is received by BC controller and branches at the BC controller to 
connect between indoor units.

For constraints on pipe length and allowable difference of elevation, refer to 
the outdoor unit manual.

Cautions On Refrigerant Piping

X

Be sure to use non-oxidative brazing for brazing to ensure that no for-
eign matter or moisture enter into the pipe.

X

Be sure to apply refrigerating machine oil over the flare connection 
seating surface and tighten the connection using a double spanner.

X

Provide a metal brace to support the refrigerant pipe so that no load is 
imparted to the indoor unit end pipe. This metal brace should be pro-
vided 50 cm away from the indoor unit’s flare connection.

 Warning:

When installing and moving the unit, do not charge it with refrigerant other 
than the refrigerant specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to 

malfunction and result in severe damage.

 Caution:

Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized 
copper as specified in the JIS H3300 “Copper and copper alloy seam-
less pipes and tubes”. In addition, be sure that the inner and outer sur-
faces of the pipes are clean and free of hazardous sulphur, oxides, dust/
dirt, shaving particles, oils, moisture, or any other contaminant.

Never use existing refrigerant piping.

- The large amount of chlorine in conventional refrigerant and refrigerator oil 

in the existing piping will cause the new refrigerant to deteriorate.

Store the piping to be used during installation indoors and keep both 
ends of the piping sealed until just before brazing.

- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate 

and the compressor may fail.

Use Suniso 4GS or 3GS (small amount) refrigerator oil to coat the flare 
and flange connection part. (For models using R22)

Use ester oil, ether oil or alkylbenzene (small amount) as the refrigera-
tor oil to coat flares and flange connections. (For models using R410A 
or R407C)

- The refrigerant used in the unit is highly hygroscopic and mixes with water 

and will degrade the refrigerator oil.

6.2. Liner expansion valve piping work

Attach the supplied LEV-kit to the liquid pipe of the heat exchanger (field supply).
For Type250, connect two LEV-kits. For Type500, connect four LEV-kits.

[Fig. 6.2.1] (P.3)

A

Remove the cap

[Fig. 6.2.2] (P.3)

A

Heat exchanger (field supply)

B

LEV-kit

C

Brazing

D

Linear expansion valve

E

Outdoor unit

[Fig. 6.2.3] (P.3)

A

Heat exchanger (field supply)

B

LEV-kit

C

Brazing

D

Linear expansion valve

E

Outdoor unit

F

Refrigerant pipe size ø9.52 (field supply)

G

Distributor (field supply)

H

Refrigerant pipe size ø9.52 (field supply)

[Fig. 6.2.4] (P.3)

A

Heat exchanger (field supply)

B

LEV-kit

C

Brazing

D

Linear expansion valve

E

Outdoor unit

F

Refrigerant pipe size ø9.52 (field supply)

G

Distributor (field supply)

H

Refrigerant pipe size ø9.52 (field supply)

I

Refrigerant pipe size
P400: ø12.7 (field supply)
P500: ø15.88 (field supply)

 Caution:

Install the LEV-kit inside the AHU, and keep it away from rain or direct sun-
light.

 Caution:

Install the LEV-kit with its motor upward.

6.3. Thermistor setting work

 Caution:

The evaporator and the thermistor must touch each other. The top of the 
most sensitive part of the thermistor must touch the evaporator.

[Fig. 6.3.0.1] (P.3)

A

Most sensitive point of the thermistor

B

Maximize the contact

 Caution:

Put the thermistor wire slightly down to avoid water accumulation on top of 
the thermistor.

[Fig. 6.3.0.2] (P.3)

Pipe size

Insulating material’s thickness

6.4 mm to 25.4 mm

More than 10 mm

28.6 mm to 38.1 mm

More than 15 mm

Содержание PAC-AH125

Страница 1: ...GB Air Handling Unit Controller PAC AH125 140 250 500M J FOR INSTALLER INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the controller ...

Страница 2: ...1 A Air handling unit controller PAC AH M J B Air handling unit field supply C Controller field supply D Outdoor unit E Heat exchanger field supply F Gas pipe G Liquid pipe H LEV kit I Thermistor gas pipe J Thermistor liquid pipe K Thermistor suction air L Thermistor discharge air 1 2 3 4 5 6 7 8 B L H I J K G F A C D E ...

Страница 3: ...t C Brazing D Linear expansion valve E Outdoor unit F Refrigerant pipe size ø9 52 field supply G Distributor field supply H Refrigerant pipe size ø9 52 field supply I Refrigerant pipe size P400 ø12 7 field supply P500 ø15 88 field supply Fig 6 3 0 1 Fig 6 3 0 2 B A 400 274 A B A D C C E A Heat exchanger field supply B LEV kit C Brazing D Linear expansion valve E Outdoor unit Type 125 140 G G H H C...

Страница 4: ... signal K Error signal output L LEV kit M LEV kit N Distant signal ON OFF O Error signal input P Thermistor suction air Q Thermistor gas pipe R Thermistor liquid pipe S Thermistor discharge air T To outdoor unit U Contact signal V To remote controller W Analog signal X Distant signal Y Thermistor Z Transmission A B D E C F A B G D E C F A C C D B B A A F T U V W N O P Q R L M S E M Z B C D L Y X G...

Страница 5: ...smission cable B Terminal block for outdoor transmis sion cable C Remote controller Fig 7 2 3 Fig 7 2 4 A Non polarized B Remote Controller 8 9 Fig 8 1 1 A Address switch B SW2 Fig 9 0 1 A B D C TBY TBY TBY TBY S M1M2 S M1M2 TB3 M1M2 2 1 2 1 A A B C C TBY TBY S M1M2 S M1M2 TB3 M1M2 A A B C C DC10 13 V A B 1 2 A B 2 1 DC24 30 V A B 1 2 A B M2 M1 S A B ...

Страница 6: ...d Interior Wire Regulations and the instructions given in this manual and always use a special circuit If the power source capacity is inadequate or electric work is performed improperly electric shock and fire may result Keep the electric parts away from water washing water etc It might result in electric shock catching fire or smoke Securely install the outdoor unit terminal cover panel If the t...

Страница 7: ...quired If an leak circuit breaker is not installed electric shock may result Use power line cables of sufficient current carrying capacity and rating Cables that are too small may leak generate heat and cause a fire Use only a circuit breaker and fuse of the specified capacity A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire Do n...

Страница 8: ... 250 400 500 Reference air flow rate in case of connection without standard indoor units m3 h 2000 2500 3000 4000 5000 8000 10000 Max air flow rate in case of connection with standard indoor units except cooling only m3 h 800 1000 1120 1600 2000 3200 4000 Min volume inside heat exchanger tube cm3 1500 1900 2150 3000 3750 6000 7500 Max volume inside heat exchanger tube cm3 2850 3550 4050 5700 7100 ...

Страница 9: ... pro vided 50 cm away from the indoor unit s flare connection Warning When installing and moving the unit do not charge it with refrigerant other than the refrigerant specified on the unit Mixing of a different refrigerant air etc may cause the refrigerant cycle to malfunction and result in severe damage Caution Use refrigerant piping made of C1220 CU DHP phosphorus deoxidized copper as specified ...

Страница 10: ...s no slack on all wire connections 5 Some cables power remote controller transmission cables above the ceil ing may be bitten by mouses Use as many metal pipes as possible to insert the cables into them for protection 6 Never connect the power cable to leads for the transmission cables Other wise the cables would be broken 7 Be sure to connect control cables to the indoor unit remote controller an...

Страница 11: ...es 7 3 1 Connecting LEV kit cables Connect the lead wire of the linear expansion valve to the controller Pull the end of wire ring terminal through the bunch of wires LEV kit at the bot tom of the controller Connect the lead wire of the expansion valve to the same colored terminal When the lead wire is too long cut it to the appropriate length Do not bind it in the box This time connect the lead w...

Страница 12: ...remain SW12 for over 10 at 0 and match SW11 for 1 to 9 with 3 2 How to set branch numbers SW14 Series R2 only The branch number assigned to each indoor unit is the port number of the BC controller to which the indoor unit is connected Leave it to 0 on the non R2 series of units The rotary switches are all set to 0 when shipped from the factory These switches can be used to set unit addresses and b...

Страница 13: ... After 16 minute or more cooling operation and when 1 C or less of the thermistor detection temperature for liquid pipe is detected for 3 minutes in a row the linear expansion valve will be closed to prevent freezing The operation will be normal when either of the following conditions is met When 3 minutes have passed after 10 C or more of the thermistor detection temperature for liquid pipe is de...

Страница 14: ......

Страница 15: ......

Страница 16: ...anding it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K WT05932X01 Printed in Japan The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...

Отзывы: