7

GB

Do not use a refrigerant other than R410A.

- If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may 

cause the refrigerator oil to deteriorate.

Use a vacuum pump with a reverse flow check valve.

- The vacuum pump oil may flow back into the refrigerant cycle and cause the 

refrigerator oil to deteriorate.

Do not use the following tools that are used with conventional refriger-

ants.
(Gauge manifold, charge hose, gas leak detector, reverse flow check 

valve, refrigerant charge base, vacuum gauge, refrigerant recovery 

equipment.)

- If the conventional refrigerant and refrigerator oil are mixed in the R410A, 

the refrigerant may deteriorated.

- If water is mixed in the R410A, the refrigerator oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conven-

tional refrigerants will not react to it.

Do not use a charging cylinder.

- Using a charging cylinder may cause the refrigerant to deteriorate.

Be especially careful when managing the tools.

- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteri-

orate.

1.3. Before getting installed

 Caution:

Do not install the unit where combustible gas may leak.

- If the gas leaks and accumulates around the unit, an explosion may result.

Do not use the air conditioner where food, pets, plants, precision instru-

ments, or artwork are kept.

- The quality of the food, etc. may deteriorate.

Do not use the air conditioner in special environments.

- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of 

the air conditioner or damage its parts.

When installing the unit in a hospital, communication station, or similar 

place, provide sufficient protection against noise.

- The inverter equipment, private power generator, high-frequency medical 

equipment, or radio communication equipment may cause the air condi-
tioner to operate erroneously, or fail to operate. On the other hand, the air 
conditioner may affect such equipment by creating noise that disturbs med-
ical treatment or image broadcasting.

Do not install the unit on a structure that may cause leakage.

- When the room humidity exceeds 80 % or when the drain pipe is clogged, 

condensation may drip from the indoor unit. Perform collective drainage 
work together with the outdoor unit, as required.

1.4. Before getting installed (moved) - elec-

trical work

 Caution:

Ground the unit.

- Do not connect the ground wire to gas or water pipes, lightning rods, or tele-

phone ground lines. Improper grounding may result in electric shock.

Install the power cable so that tension is not applied to the cable.

- Tension may cause the cable to break and generate heat and cause a fire.

Install an leak circuit breaker, as required.

- If an leak circuit breaker is not installed, electric shock may result.

Use power line cables of sufficient current carrying capacity and rating.

- Cables that are too small may leak, generate heat, and cause a fire.

Use only a circuit breaker and fuse of the specified capacity.

- A fuse or circuit breaker of a larger capacity or a steel or copper wire may 

result in a general unit failure or fire.

Do not wash the air conditioner units.

- Washing them may cause an electric shock.

Be careful that the installation base is not damaged by long use.

- If the damage is left uncorrected, the unit may fall and cause personal injury 

or property damage.

Be very careful about product transportation.

- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a 

means of transportation. It is dangerous.

- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on 

the unit base. Also support the outdoor unit at four points so that it cannot 
slip sideways. 

Safely dispose of the packing materials.

- Packing materials, such as nails and other metal or wooden parts, may 

cause stabs or other injuries.

- Tear apart and throw away plastic packaging bags so that children will not 

play with them. If children play with a plastic bag which was not torn apart, 
they face the risk of suffocation.

1.5. Before starting the test run

 Caution:

Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can 

result in severe damage to internal parts. Keep the power switch turned on 
during the operational season.

Do not touch the switches with wet fingers.

- Touching a switch with wet fingers can cause electric shock.

Do not touch the refrigerant pipes during and immediately after opera-

tion.

- During and immediately after operation, the refrigerant pipes are may be 

hot and may be cold, depending on the condition of the refrigerant flowing 
through the refrigerant piping, compressor, and other refrigerant cycle 
parts. Your hands may suffer burns or frostbite if you touch the refrigerant 
pipes.

Do not operate the air conditioner with the panels and guards removed.

- Rotating, hot, or high-voltage parts can cause injuries.

Do not turn off the power immediately after stopping operation.

- Always wait at least five minutes before turning off the power. Otherwise, 

water leakage and trouble may occur.

2. Accessories

The unit is provided with the following accessories:

[Fig. 2.0.1] (P.2)

No.

Accessories

Quantity

AH125

AH140

AH250

AH500

1

Controller

1

1

1

1

2

LEV-kit (EFM804)

1

0

2

4

LEV-kit (EFM1004)

0

1

0

0

3

Thermistor

4

4

4

4

4

Clip (1 spare)

3

3

3

3

5

Insulation (2 spares)

4

4

4

4

6

Tie band (2 spares)

6

6

6

6

7

Installation manual

1

1

1

1

8

Tube

5

5

5

5

Содержание PAC-AH125

Страница 1: ...GB Air Handling Unit Controller PAC AH125 140 250 500M J FOR INSTALLER INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the controller ...

Страница 2: ...1 A Air handling unit controller PAC AH M J B Air handling unit field supply C Controller field supply D Outdoor unit E Heat exchanger field supply F Gas pipe G Liquid pipe H LEV kit I Thermistor gas pipe J Thermistor liquid pipe K Thermistor suction air L Thermistor discharge air 1 2 3 4 5 6 7 8 B L H I J K G F A C D E ...

Страница 3: ...t C Brazing D Linear expansion valve E Outdoor unit F Refrigerant pipe size ø9 52 field supply G Distributor field supply H Refrigerant pipe size ø9 52 field supply I Refrigerant pipe size P400 ø12 7 field supply P500 ø15 88 field supply Fig 6 3 0 1 Fig 6 3 0 2 B A 400 274 A B A D C C E A Heat exchanger field supply B LEV kit C Brazing D Linear expansion valve E Outdoor unit Type 125 140 G G H H C...

Страница 4: ... signal K Error signal output L LEV kit M LEV kit N Distant signal ON OFF O Error signal input P Thermistor suction air Q Thermistor gas pipe R Thermistor liquid pipe S Thermistor discharge air T To outdoor unit U Contact signal V To remote controller W Analog signal X Distant signal Y Thermistor Z Transmission A B D E C F A B G D E C F A C C D B B A A F T U V W N O P Q R L M S E M Z B C D L Y X G...

Страница 5: ...smission cable B Terminal block for outdoor transmis sion cable C Remote controller Fig 7 2 3 Fig 7 2 4 A Non polarized B Remote Controller 8 9 Fig 8 1 1 A Address switch B SW2 Fig 9 0 1 A B D C TBY TBY TBY TBY S M1M2 S M1M2 TB3 M1M2 2 1 2 1 A A B C C TBY TBY S M1M2 S M1M2 TB3 M1M2 A A B C C DC10 13 V A B 1 2 A B 2 1 DC24 30 V A B 1 2 A B M2 M1 S A B ...

Страница 6: ...d Interior Wire Regulations and the instructions given in this manual and always use a special circuit If the power source capacity is inadequate or electric work is performed improperly electric shock and fire may result Keep the electric parts away from water washing water etc It might result in electric shock catching fire or smoke Securely install the outdoor unit terminal cover panel If the t...

Страница 7: ...quired If an leak circuit breaker is not installed electric shock may result Use power line cables of sufficient current carrying capacity and rating Cables that are too small may leak generate heat and cause a fire Use only a circuit breaker and fuse of the specified capacity A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire Do n...

Страница 8: ... 250 400 500 Reference air flow rate in case of connection without standard indoor units m3 h 2000 2500 3000 4000 5000 8000 10000 Max air flow rate in case of connection with standard indoor units except cooling only m3 h 800 1000 1120 1600 2000 3200 4000 Min volume inside heat exchanger tube cm3 1500 1900 2150 3000 3750 6000 7500 Max volume inside heat exchanger tube cm3 2850 3550 4050 5700 7100 ...

Страница 9: ... pro vided 50 cm away from the indoor unit s flare connection Warning When installing and moving the unit do not charge it with refrigerant other than the refrigerant specified on the unit Mixing of a different refrigerant air etc may cause the refrigerant cycle to malfunction and result in severe damage Caution Use refrigerant piping made of C1220 CU DHP phosphorus deoxidized copper as specified ...

Страница 10: ...s no slack on all wire connections 5 Some cables power remote controller transmission cables above the ceil ing may be bitten by mouses Use as many metal pipes as possible to insert the cables into them for protection 6 Never connect the power cable to leads for the transmission cables Other wise the cables would be broken 7 Be sure to connect control cables to the indoor unit remote controller an...

Страница 11: ...es 7 3 1 Connecting LEV kit cables Connect the lead wire of the linear expansion valve to the controller Pull the end of wire ring terminal through the bunch of wires LEV kit at the bot tom of the controller Connect the lead wire of the expansion valve to the same colored terminal When the lead wire is too long cut it to the appropriate length Do not bind it in the box This time connect the lead w...

Страница 12: ...remain SW12 for over 10 at 0 and match SW11 for 1 to 9 with 3 2 How to set branch numbers SW14 Series R2 only The branch number assigned to each indoor unit is the port number of the BC controller to which the indoor unit is connected Leave it to 0 on the non R2 series of units The rotary switches are all set to 0 when shipped from the factory These switches can be used to set unit addresses and b...

Страница 13: ... After 16 minute or more cooling operation and when 1 C or less of the thermistor detection temperature for liquid pipe is detected for 3 minutes in a row the linear expansion valve will be closed to prevent freezing The operation will be normal when either of the following conditions is met When 3 minutes have passed after 10 C or more of the thermistor detection temperature for liquid pipe is de...

Страница 14: ......

Страница 15: ......

Страница 16: ...anding it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K WT05932X01 Printed in Japan The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...

Отзывы: