34
3 SPECIFICATIONS
3.3 Performance Specifications
NZ2GNCF1-32D DC input module
*1 The performance specifications vary depending on firmware versions of modules used. (
Page 256 Added and Changed Functions)
*2 If the input response time is set to "0ms", the actual input response time is 80
s at OFF
ON, and 160
s at ON
OFF.
*3 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*4 Use bar solderless terminals for wiring.
*5 Only one wire can be inserted into a wire insertion opening for the terminal block for module power supply and FG. Multiple wires cannot
be connected to a terminal. Connecting two or more wires may cause a poor contact.
*6 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. (
Page 225 Input module (32-point
*7 For the points for downward installation, horizontal installation (upside down), and upward installation, refer to the derating chart below.
Item
NZ2GNCF1-32D
Station type
Remote station
Authentication Class
Authentication Class B
Network topology
Line topology, star topology, mixture of star topology and line topology, ring topology
Number of input points
32 points
Rated input voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Rated input current
6.6mA TYP. (for 24VDC)
Maximum number of simultaneous input points
100%
ON voltage/ON current
11VDC or more/4mA or more
OFF voltage/OFF current
5VDC or less/1.5mA or less
Input resistance
3.3k
Input response time
OFF
ON
0ms
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Factory default: 1ms)
ON
OFF
Withstand voltage
510VAC for 1 minute between all DC external terminals and ground
Insulation resistance
10M
or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity
Noise voltage 500Vp-p, noise width 1
s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
Protection degree
IP2X
Wiring method for common
32 points/common (Common terminal: pin number B1, B2) (1-wire, 40-pin connector type)
Positive common/negative common shared type
External interface
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (2-piece spring clamp terminal block)
I/O part
40-pin connector
Applicable wire size
For power supply
Stranded wire: 0.3 to 1.5
(22 to 16 AWG), terminal slot size: 2.4mm
1.5mm
For I/O
40-pin connector
The size depends on the connector plug used (sold separately). (
Applicable solderless
terminal
Terminal block for module
power supply and FG
Page 127 Applicable solderless terminal
Multicast filter
Available
Cyclic transmission
RX/RY points
32 points
RWr/RWw points
4 points
Module power supply
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
110mA or less (24VDC, all points ON)
Weight
0.20kg
0
24
32
16
8
0
10
20
30
40
50 55
28.8VDC
26.4VDC
Maximum
number of
simultaneous
ON points
(points)
Ambient temperature (
)
28 points, 55
32 points, 55
32 points, 45
Input voltage
Input voltage