En-2

Electrical specifications

MODEL

NTXFKS09A112A

NTXFKS12A112A

NTXFKS15A112A

NTXFKS18A112A

INDOOR UNIT
Power supply (V, PHASE, Hz)

208/230, 1, 60

Min. Circuit Ampacity 

(A)

1.0

Fan motor (F.L.A.) 

(A)

0.62

0.72

OUTDOOR UNIT
Power supply (V, PHASE, Hz)

208/230, 1, 60

Max. Fuse size (time delay) (A)

15

20

Min. Circuit Ampacity 

(A)

11

16

Fan motor (F.L.A.) 

(A)

0.50

0.93

Compressor

(R.L.A.) 

(A)

8.2

12.0

(L.R.A.) 

(A)

10.3

15.0

Control voltage

Indoor unit - Remote controller: (Wireless)

Indoor unit - Outdoor unit: DC12-24 V (Polar)

Pipe

Outside 

diameter

Minimum 

wall thick

-

ness

Insulation  

thickness

Insulation 

material

inch (mm)

For liquid

NTXFKS09/12/15/18A112A

1/4 (6.35)

0.0315 

(0.8)

5/16 (8)

Heat resistant 

foam plastic 

0.045 Specific 

gravity

For gas

NTXFKS09/12A112A

3/8 (9.52)

0.0315 

(0.8)

5/16 (8)

NTXFKS15/18A112A

1/2 (12.7)

0.0315 

(0.8)

5/16 (8)

Limits

Pipe length

NTXFKS09/12A112A

65 ft. (20 m) max.

NTXFKS15/18A112A

100 ft. (30 m) max.

Height difference

NTXFKS09/12A112A

40 ft. (12 m) max.

NTXFKS15/18A112A

50 ft. (15 m) max.

No. of bends

10 max.

Pipe length

Up to 25 ft. (7.5 m)

No additional charge is required.

Exceeding 25 ft. (7.5 m)

Additional charge is required.

(Refer to the table below.)

Refrigerant to be 

added

NTXFKS09/12A112A

1.08 oz each 5 ft. (20 g/m)

NTXFKS15/18A112A

1.62 oz each 5 ft. (30 g/m)

1-3. SPECIFICATIONS

1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR 

WIRE CONNECTION

•  Power should be taken from an exclusive branched circuit.

•  Wiring work should be based on applicable technical standards.

•  Wiring connections should be made following the diagram.

•  Securely tighten screws.

Connecting wires and the ground wire

•  Use  solid  conductor  Min. AWG14  or  stranded  conductor 

Min. AWG14.

•  Use double insulated copper wire with 600 V insulation.

•  Use copper conductors only.

  * Follow local electrical codes.

Power supply cable and ground wire

•  Use solid or stranded conductor.

  NTXFKS09/12A112A

   Min. AWG14

  NTXFKS15/18A112A

   Min. AWG12

•  Use copper conductors only.

  * Follow local electrical codes.

Note: 

When the indoor unit is powered from the outdoor unit, depend

-

ing on local code, a disconnect switch needs to be installed to a 

power supply circuit.

1-3-2. REFRIGERANT PIPES

•  To prevent condensation, insulate the two refrigerant pipes.

•  Refrigerant pipe bending radius must be 4 in. (100 mm) or more.

 CAUTION

Be sure to use the insulation of specified thickness (table on the 

right). Excessive insulation may cause incorrect installation of 

the indoor unit, and too little insulation may cause condensate 

to form.

•  The unit has flared connections on both indoor and outdoor 

sides.

•  Remove the valve cover from the outdoor unit, then connect 

the pipe.

•  Refrigerant pipes are used to connect the indoor and outdoor 

units.

•  Be careful not to crush or over bend the pipe in pipe bending.

•  Refrigerant adjustment... If pipe length exceeds 25 ft. (7.5 m), 

additional refrigerant (R410A) charge is required.

(The outdoor unit is charged with refrigerant for pipe length up 

to 25 ft. [7.5 m])

1-2. SELECTING THE INSTALLATION LOCATION

INDOOR UNIT

•  Where airflow is not blocked.

•  Where air spreads over the entire room.

•  Rigid wall and flat floor without vibration.

•  Where it is not exposed to direct sunlight. Do not 

expose to direct sunlight also during the period fol

-

lowing unpacking to before use.

•  Where easily drained.

•  At a distance 3 ft. (1 m) or more away from your 

TV and radio. Operation of the air conditioner may 

interfere with radio or TV reception. An amplifier may 

be required for the affected device.

•  In a place as far away as possible from fluorescent 

and incandescent lights. In order to make the infrared 

remote control operate the air conditioner normally. 

The heat from the lights may cause deformation or 

the ultraviolet may cause deterioration.

•  Where the air filter can be removed and replaced 

easily.

•  Where it is away from the other heat or steam source.

REMOTE CONTROLLER 

•  Where it is easy to operate and easily visible.

•  Where children cannot touch it.

•  Select the position where the indoor unit can receive 

the signal from the remote controller properly. Check 

that signals from the remote controller are surely re

-

ceived by the indoor unit from that position (‘beep’ or 

‘beep beep’ receiving tone sounds). After that, attach 

remote controller holder to a pillar or wall and install 

wireless remote controller.

Note: 

In  rooms  where  inverter  type  fluorescent  lamps  are 

used,  the  signal  from  the  wireless  remote  controller 

may not be received.

OUTDOOR UNIT

•  Where it is not exposed to strong wind.

•  Where airflow is good and dustless.

•  Where rain or direct sunlight can be avoided as much 

as possible.

•  Where  neighbours  are  not  annoyed  by  operation 

sound or hot air.

•  Where rigid wall or support is available to prevent 

the increase of operation sound or vibration.

•  Where there is no risk of combustible gas leakage.

•  When installing the unit at a high level, be sure to 

secure the unit legs.

•  Where it is at least 10 ft. (3 m)  away from the antenna 

of TV set or radio. Operation of the air conditioner may 

interfere with radio or TV reception in areas where 

reception is weak. An amplifier may be required for 

the affected device.

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall 

or blowing snow. In areas with heavy snow, please 

install  a  canopy,  a  pedestal  and/or  some  baffle 

boards.

Note:

It is advisable to make a piping loop near outdoor unit 

so as to reduce vibration transmitted from there.

Note: 

When operating the air conditioner in low outside 

temperature, be sure to follow the instructions 

described below.

•  Never install the outdoor unit in a place where its air 

inlet/outlet side may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor 

unit with its air inlet side facing the wall and a baffle 

board on the air outlet side.

Avoid the following places for installation where air 

conditioner trouble is liable to occur.

•  Where flammable gas could leak.

•  Where there is an excessive amount of machine 

oil in the air.

•  Where oil is splashed or where the area is filled 

with oily smoke (such as cooking areas and fac

-

tories, in which the properties of plastic could be 

changed and damaged).

•  Salty places such as the seaside.

•  Where sulfide gas is generated such as hot spring, 

sewage, waste water.

•  Where there is high-frequency or wireless equip

-

ment.

•  Where there is emission of high levels of VOCs, 

including  phthalate  compounds,  formaldehyde, 

etc., which may cause chemical cracking.

BH79A443H01_01En.indd   2

2018/07/25   10:02:09

Содержание NTXFKs09a112a Series

Страница 1: ...installation d unités multiples consultez la notice d installation des uni tés externes multiples Manual DE InstalaCIÓn PARA EL INSTALADOR Al instalar unidades múltiples consulte el manual de instalación de la unidad múltiple para obtener información sobre la instalación de la unidad exterior FLOOR TYPE AIR CONDITIONERS ntXFKs09a112a ntXFKs12a112a ntXFKs15a112a ntXFKs18a112a BH79A443H01_cover indd...

Страница 2: ...upply plug into the outlet make sure that there is no dust blockage or loose parts both in the outlet and on the plug Verify that the power supply plug is completely in the outlet If there is dust blockage or loose parts on the power supply plug or the outlet it could cause electric shock or fire If loose parts are found on the power supply plug replace it Securely attach the electrical cover to t...

Страница 3: ...ht Do not expose to direct sunlight also during the period fol lowing unpacking to before use Where easily drained At a distance 3 ft 1 m or more away from your TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be required for the affected device In a place as far away as possible from fluorescent and incandescent lights In order to make the in...

Страница 4: ...e fan stop The outdoor unit produces condensate during the heating operation Select the installation place to ensure to prevent the outdoor unit and or the grounds from being wet by drain water or damaged by frozen drain water 33 1 16 13 3 4 14 5 8 19 11 16 Air inlet Air inlet Air inlet Air inlet Air inlet 6 7 8 15 3 8 13 Air outlet 2 3 8 13 16 slot 1 9 16 40 840 175 500 Air inlet 390 330 349 371 ...

Страница 5: ...re is a view of the bottom of the indoor unit from above FOR REAR OR LEFT REAR PIPING The following figure is a front view of the indoor unit installation location FOR LEFT PIPING FOR RIGHT PIPING 2 3 8 60 1 3 16 30 2 3 8 60 1 3 16 30 2 3 8 60 2 3 8 60 29 17 32 750 8 37 64 218 6 3 16 157 12 21 64 313 2 7 16 62 8 15 32 215 5 45 64 145 2 61 64 75 5 7 8 150 2 3 8 60 HOLE POSITIONS ø3 in ø75 mm 6 32 9...

Страница 6: ...ted upward FOR LEFT OR LEFT REAR PIPING Bundle the connecting pipes and drain hose together and then wrap them in felt tape 11 Cut and use the lower side panels on the left and right sides of the indoor unit as shown below Smooth the cut edges of the side panels so that they will not damage the insula tion coating For left or right piping Installing flush against a wall with molding Molding Cut th...

Страница 7: ...After tightening verify that the wires are tightly fastened 7 Reinstall the conduit plate 8 Reinstall the electrical cover Fig 1 Lead wire 19 32 in 15 mm Fig 2 Terminal block Lock nut Electrical cover Electrical box Conduit pipe Grounding terminal Screw Less than 7 8 in 23 mm Conduit plate Conduit pipe Lock nut Conduit plate Do not make drain piping as shown below Accumulated drain water Air Wavin...

Страница 8: ...ace this part where customers cannot touch it Room air conditioner Main body of an interface Thick part of the connecting cable Indoor control P C board CN105 for interface CN24 for connector cable Connect an interface connector cable to the indoor control P C board of an air conditioner with a connecting cable Cutting or extending the connecting cable of the interface connector ca ble results in ...

Страница 9: ...ly cord L Indoor outdoor unit connecting wire A Make earth wire a little longer than others More than 4 in 100 mm For future servicing leave some slack in the connecting wires Be sure to attach each screw to its correspondent terminal when securing the cord and or the wire to the terminal block Service panel Lock nut Conduit cover Conduit plate Conduit pipe Grounding terminal Grounding terminal TB...

Страница 10: ...r Pipe cutter Fig 4 Smooth all around Even length all around Inside is shining without any scratches Fig 6 Clutch type Flaring tool Wing nut type Uneven Burred B Flare nut Die Copper pipe Fig 2 Fig 3 Fig 5 4 2 PIPE CONNECTION Fasten flare nut with a torque wrench as specified in the table refer to 3 2 When fastened too tight flare nut may eventually break and cause refrigerant leakage Be sure to w...

Страница 11: ...this procedure is not performed the unit will automatically begin operation when power supply is resumed To the user After installing the unit explain to the user about auto restart function If auto restart function is unnecessary it can be deactivated Consult the service representative to deactivate the function Refer to the service manual for details 5 2 TEST RUN 1 Insert power supply plug into ...

Страница 12: ...o una descarga eléctrica Al instalar reubicar o reparar la unidad asegúrese de que en el circuito de refrigeración no entra ninguna otra sustancia que no sea el refrigerante especificado R410A La presencia de cualquier otra sustancia extraña como aire por ejemplo puede provocar una elevación anómala de la presión una explosión o daños corporales El uso de un refrigerante distinto al especificado p...

Страница 13: ...odrían alterar y dañar En ambientes salobres como las zonas cos teras Donde haya gas sulfúrico como en zonas de baños termales alcantarillas o aguas residua les Donde haya algún equipo inalámbrico o de alta frecuencia Donde haya elevadas emisiones de COV incluidos compuestos de ftalato aldehído fórmico etc que puedan causar craqueos 1 3 ESPECIFICACIONES 1 3 1 CONEXIÓN DE CABLES DE ALIMENTACIÓN Y D...

Страница 14: ...rior y los terminales de tierra no se humedezcan con agua de drenaje ni se dañen debido a la congelación de este agua de drenaje 33 1 16 13 3 4 14 5 8 19 11 16 Entrada de aire Entrada de aire Entrada de aire 6 7 8 15 3 8 13 Salida de aire Ranura de 2 3 8 13 16 1 9 16 40 840 175 500 Entrada de aire 390 330 349 371 Salida de aire Ranura de 2 10 21 espacio sin obstáculos 3 3 4 pulg 100 mm o más cuand...

Страница 15: ... de la situación de instalación de la unidad interior TUBERÍA IZQUIERDA TUBERÍA DERECHA POSICIONES DE LOS ORIFICIOS ø3 pulg ø75 mm 6 32 9 32 pulg 5 7 mm 2 3 PREPARACIÓN DE LA UNIDAD INTERIOR Retire el panel frontal de la unidad interna 1 Presione las lengüetas en ambos lados de la unidad para abrir el panel frontal 2 Tire del panel frontal hacia usted para extraerlo 3 Retire los 2 tornillos 4 Abra...

Страница 16: ...se pueda mover ligeramente hacia delante atrás izquierda y derecha Cinta para tubería Manguera de drenaje Tubería de refrigerante Tubería doblada hacia fuera Empuje Asegúrese de aislar las tuberías de conexión de modo que no estén en contacto con el panel Tenga cuidado de no partir los tubos de conexión al doblarlos Utilice una dobladora de tubos para la tubería izquierda o derecha La cubierta de ...

Страница 17: ...n proveedor electricista autorizado Si así lo exigen las normativas nacionales estatales y locales aplicables deberá instalarse un interruptor de desconexión cuando la alimentación de la unidad interior provenga de la unidad exterior 1 Retire la cubierta eléctrica 2 Retire la placa de conducción 3 Una la tubería de conducción a la placa de conducción con la tuerca de fijación El cable de conexión ...

Страница 18: ...ón interior exterior y el cable de tierra Mantenga la distancia máxima posible entre el cable de conexión y esos cables La parte delgada del cable de conexión debe guardarse y situarse en un lugar donde los clientes no puedan tocarla Panel frontal Unidad interior Unidad interior Panel Panel Deflector hori zontal posterior 1 Retire el panel 2 Abra la cubierta del panel de control P C interior 3 Una...

Страница 19: ...A Tubería de conducción Terminal de tierra Fijación TB Terminal de tierra Placa de conducción Panel de servicio Tuerca de bloqueo Cubierta de conducción Placa de conduc ción Panel de servicio Tuerca de bloqueo Cubierta de con ducción Panel de terminales Panel de terminales a la cubierta de conducción a la cubierta de conducción Fijación TB Cable de alimentación L Cable de conexión de la unidad int...

Страница 20: ...bla véase 3 2 Si la aprieta demasiado la tuerca abocardada podría romperse y causar pérdidas de refrigerante Asegúrese de colocar el aislante alrededor de las tuberías El contacto directo con la tubería puede ocasionar quemaduras o congelación Conexión de la unidad interior Conecte las tuberías de líquido y de gas a la unidad interior Aplique una fina capa de aceite refrigerante K sobre los extrem...

Страница 21: ...Se debe utilizar siempre un medidor de micrones Rompa el vacío inyectando nitrógeno N2 en la válvula de servicio de descar ga a 0 PSIG 4 Realice el vaciado del sistema a 1500 micrones Rompa el vacío inyectando nitrógeno N2 en la válvula de servicio de descarga a 0 PSIG 5 Realice el vaciado del sistema a 500 micrones 6 Cierre las válvulas conectoras de manómetro detenga la bomba y realice una prueb...

Страница 22: ... du branchement de la fiche d alimentation dans la prise secteur vérifiez qu aucune poussière saleté ni d élément desserré n est présent sur la prise et la fiche Veillez à enfoncer à fond la fiche d alimentation dans la prise secteur La présence de poussière de saleté ou d éléments desserrés sur la fiche d ali mentation ou la prise secteur peut entraîner un choc électrique ou un incendie Remplacez...

Страница 23: ...ions d huile ou dont l atmosphère est chargée d huile tels que les centres de cuisson et les usines susceptibles de modifier et d altérer les caractéristiques du plastique Dans les régions où l air est très salin comme en bord de mer En présence de gaz sulfurés qui se dégagent par exemple des sources chaudes ou des eaux usées En présence d équipements haute fréquence ou sans fil En présence d émis...

Страница 24: ...ueur L J 4 in 100 mm minimum 14 in 350 mm minimum 8 in 200 mm 4 minimum 4 in 100 mm minimum Unité pouce Unité mm 31 1 2 19 11 16 13 9 16 11 1 4 12 12 3 4 1 9 16 800 500 344 5 285 150 40 304 325 5 15 16 09 12 15 18 J L Unité pouce Unité mm 4 in 100 mm minimum 4 in 100 mm minimum 14 in 350 mm minimum 20 in 500 mm 6 minimum Tuyau de vidange pour unité externe Installez l unité horizontalement N utili...

Страница 25: ...llez à installer les vis de fixation dans les trous indiqués sur l illustration Pour obtenir un support supplémentaire vous pouvez également poser des vis de fixation dans d autres trous 2 INSTALLATION DE L UNITE INTERNE 2 3 PREPARATION DE L APPAREIL INTERIEUR Déposez le panneau frontal de l unité intérieure 1 Poussez vers le bas l attache des deux côtés de l unité pour ouvrir le panneau avant 2 T...

Страница 26: ...575 29 9 64 740 2 3 4 70 4 Matériau de renfort Appareil Base Bande de feutre 11 Commencez par enrouler le ruban adhésif de tuyauterie G autour des tuyaux et du flexible à 25 64 in 10 mm à l intérieur de l appareil intérieur Fixez l extrémité de la bande de feutre 11 à l aide d une agrafe de bande Veillez à ce que le tuyau de vidange ne soit pas acheminé vers le haut Plinthe Coupez les panneaux lat...

Страница 27: ... fixation Après l opération de serrage vérifiez que les câbles sont bien fixés 7 Reposez la plaque de conduit 8 Reposez le couvercle du boîtier électrique Fig 1 19 32 in 15 mm Fig 2 Bloc de sortie Contre écrou Boîtier électrique Tuyau de conduit Borne de mise à la terre Vis Plaque de conduit Les exemples d installation de la tuyauterie de vidange illustrés ci dessous sont à éviter Ecoulement d eau...

Страница 28: ...nterne Panneau Panneau 2 9 RACCORDEMENT D UN CÂBLE D INTERFACE option CÂBLE DE CONNECTEUR option AU CLIMATI SEUR Partie fine du câble de connexion Placez cette section à un endroit où les clients ne peuvent pas la toucher Climatiseur de pièce Corps principal d une interface Section épaisse du câble de connexion Carte à circuits im primés du panneau de commande de l unité interne CN105 pour interfa...

Страница 29: ...retiens ulté rieurs Veiller à fixer chaque vis dans la borne correspondante lors de la fixation du cordon et ou du câble au bloc de raccordement Panneau de service Contre écrou 09 12 15 18 Cache de conduit Plaque de conduit Tuyau de conduit 3 2 CINTRAGE ET INSTALLATION DE LA TUYAU TERIE Remarque Voir point 4 RACCORDS A EVASEMENT RACCORDS DE TUYAUTERIE 3 3 ISOLATION THERMIQUE ET RUBANAGE 1 Recouvre...

Страница 30: ...rop serré il risque de se rompre et de provoquer une fuite de réfrigérant Assurez vous que la tuyauterie est enveloppée d isolant Un contact direct avec la tuyauterie nue peut entraîner des brûlures ou des engelures Raccordement de l unité interne Raccordez les deux tuyaux de liquide et de gaz à l unité interne Appliquez une fine couche d huile réfrigérante K sur les extrémités évasées des tuyaux ...

Страница 31: ... marche lorsque l alimentation est rétablie A l attention de l utilisateur Après l installation de l unité expliquez à l utilisateur la fonction de redé marrage automatique Si la fonction de redémarrage automatique n est pas nécessaire elle peut être désactivée Adressez vous au responsable de l entretien pour désacti ver cette fonction Consultez le manuel d entretien pour plus d informations 5 2 E...

Страница 32: ...USA MITSUBISHI ELECTRIC TRANE HVAC US LLC This product is designed and intended for use in the residential commercial and light industrial environment BH79A443H01_cover indd 2 2018 07 23 19 04 23 Publication No DL SVN001A XX Published Dec 2018 BH79A443H01 ...

Отзывы: