5.7 Installation and wiring for products with MODBUS communication
Master Unit
MDU Unit
MDU Unit
Ter
Ter
(2) Grounding the shielded wire
Connect the shielded wire of the MODBUS communication cable to the “SLD” terminal of each unit at both ends.
Connect the shielded wire to “FG” at one point on the master unit side.
(1) Connection of termination resistor
A termination resistor must be connected to the unit at both
ends of the MODBUS communication line.
Since the MDU has built-in terminating resistors, it is possible
to connect a terminating resistor by short-circuiting 485- and
Ter terminal.