17
9. Special Functions
A
Distant control board
B
Relay circuit
C
External output adapter (PAC-SA88HA-E)
D
Outdoor unit control board
E
Lamp power supply
F
Procure locally
G
Max. 10 m (32 ft)
L1: Error display lamp
L2: Compressor operation lamp
X, Y: Relay (Coil standard of 0.9W or less for DC 12V)
X, Y: Relay (DC1mA)
A
Remote control panel
B
Relay circuit
C
External input adapter (PAC-SC36NA-E)
D
Outdoor unit control board
E
Relay power supply
F
Procure locally
G
Max. 10 m (32 ft)
ON
OFF
SW1
Heating
Cooling
SW2
Validity of SW1
Invalidity of SW1
The silent mode and the demand control are selected by switching the DIP switch 9-2 on outdoor controller board.
It is possible to set it to the following power consumption (compared with ratings) by setting SW1, 2.
Outdoor controller board DIP SW9-2
SW1
SW2
Function
Silent mode
OFF
ON
–
Silent mode operation
Demand control
ON
OFF
OFF
100 % (Normal)
ON
OFF
75 %
ON
ON
50 %
OFF
ON
0 % (Stop)
A
Remote control panel
B
Relay circuit
C
External input adapter (PAC-SC36NA-E)
D
Outdoor unit control board
E
Relay power supply
F
Procure locally
G
Max. 10 m (32 ft)
CN51
X
5
4
3
A
C
D
5
E
1
B
G
Y
F
~
Y
X
L
1
L
2
1
3
A
C
D
E
B
G
F
CN3N
X
Y
SW1
SW2
1
2
3
~
Y
X
1
3
A
C
D
E
B
G
F
CN3D
X
Y
SW1
SW2
1
2
3
~
Y
X
9.1. OUTDOOR UNIT INPUT/OUTPUT CONNECTOR
• State (CN51)
• Auto change over (CN3N)
• Silent Mode / Demand Control (CN3D)
RG79D595H07_EN.indd 17
9/7/2016 10:25:46 AM
Содержание MXZ-8C60NA
Страница 50: ...A4_white_tombo indd 1 2016 04 25 10 16 47 ...
Страница 51: ...A4_white_tombo indd 1 2016 04 25 10 16 47 ...