4-6. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units oper-

ate properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

Wiring/piping correction function

This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combi-
nation, and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.

Make sure that the following is done.
•  Power is supplied to the unit.
•  Stop valves are open.

Note:

During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not 
a malfunction.

Procedure
Press the piping/wiring correction switch (SW871) 1 minute or more after turning on the 
power supply.

•  Correction completes in 10 to 20 minutes. When the correction is completed, its result 

is shown by LED indication. Details are described in the following table.

•  To cancel this function during its operation, press the piping/wiring correction switch 

(SW871) again.

•  When the correction completed without error, do not press the piping/wiring correction 

switch (SW871) again.

When the result was “cannot be corrected”, press the piping/wiring correction switch 
(SW871) again to cancel this function. Then, confirm the wiring and piping combination 
in a conventional manner by operating the indoor units one by one.

•  The operation is done while the power is supplied. Make sure not to contact parts 

other than the switch, including the P.C. board. This may cause electric shock or burn 
by hot parts and live parts around the switch. Contacting the live parts may cause P.C. 
board damage.

•  To prevent electronic control P.C. board damage, make sure to perform static elimi-

nation before operating this function.

•  This function does not operate when the outside temperature is 0°C or below.

LED indication during detection:

LED

1 (Red)

2 (Yellow)

3 (Green)

Lighted

Lighted

Blinking

Result of piping/wiring correction function

LED

Result

1 (Red)

2 (Yellow)

3 (Green)

Lighted

Not lighted

Lighted

Completed
(Corrected successfully)

Blinking

Blinking

Blinking

Cannot be corrected

Other indications

Refer to “SAFETY PRE-
CAUTIONS WHEN LED 
FLASHES” located behind 
the service panel.

5. RELOCATION AND MAINTENANCE

5-1. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmos-
phere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 

MPa [Gauge] (0 kgf/cm

2

).

4) Start the emergency COOL operation on all the indoor units.
  To start the emergency operation in COOL mode, disconnect the power supply plug and/or turn off the breaker. After 15 seconds, connect the power 

supply plug and/or turn on the breaker, and then press the E.O. SW once. (The emergency COOL operation can be performed continuously for up to 30 
minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

6) Stop the emergency COOL operation.
 

Press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details .

When pumping down the refrigerant, stop the compressor before disconnecting 
the refrigerant pipes. The compressor may burst if air etc. get into it.

 

WARNING

4-7. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air fil-

ters, how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

Содержание MXZ-6C120VA

Страница 1: ...nuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidad...

Страница 2: ...ter space heater stove etc harmful substances will be generated N Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and incomplete installation could cause the pipes to burst or injury N When pumping down the refrigerant stop the compressor before disconnecting the refrigerant pipes If the refriger...

Страница 3: ...ear outdoor unit so as to reduce vibration transmitted from there 500 or more 200 or more 350 or more 100 or more 100 or more 500 or more 100 or more Service space 350 or more 350 or more When installing the unit in an area that is enclosed with walls such as a verandah be sure to have enough space as shown below In this case the air conditioning capacity and power consumption might deteriorate Wh...

Страница 4: ...t 1 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit More than 100 mm Open as a rule More than 500 mm if the front and both sides are open More than 100 mm More than 200 mm if there are obstacles to both sides Open as a rule More than 500 mm if the bac...

Страница 5: ...outdoor unit connecting wire B from the indoor unit correctly on the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confi...

Страница 6: ...s then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flar ing work again 1 Remove service port cap of sto...

Страница 7: ...o lock the operation mode in COOL DRY mode set the 2 of SW1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please n...

Страница 8: ...he live parts may cause P C board damage To prevent electronic control P C board damage make sure to perform static elimi nation before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED 1 Red 2 Yellow 3 Green Lighted Lighted Blinking Result of piping wiring correction function LED Result 1 Red 2 Yellow 3 Green Li...

Страница 9: ...осы описанные ниже и предназначенные для эксплуатации в жилых помещениях торговых залах и на предприятиях легкой промышленности erklærer et fullstendig ansvar for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrielle miljøer Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remar...

Отзывы: