59
MXZ-5B
The left lamp of
OPERATION IN-
DICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C.
board)
Condition
Remedy
Indoor/out-
door unit
failure mode
recall function
LED 1
LED 2
OFF
None (Normal)
Lighted Lighted
2-time
fl
ash
Outdoor power system
Lighted Lighted Overcurrent protection cut-out operates 3
consecutive times, bus-bar voltage protec-
tion cut-out operates 3 consecutive times,
or primary current protection cut-out oper-
ates 3 consecutive times within 1minute
after the compressor gets started.
• Check the connection of the com-
pressor connecting wire.
• Refer to 11-6. How to check in-
verter/compressor.
• Check the stop valve.
○
3-time
fl
ash
Discharge temperature thermistor
Lighted
Once
Thermistor shorts or opens during com-
pressor running.
• Refer to 11-6. "Check of outdoor
thermistors".
○
Defrost thermistor
Lighted
Once
Ambient temperature thermistor
Lighted
Twice
Fin temperature thermistor
Lighted 3 times
• Replace the outdoor power P.C. board .
P.C. board temperature thermistor
Lighted 4 times
• Replace the outdoor power P.C. board .
Outdoor heat exchanger temperature
thermistor
Lighted 9 times
• Refer to 11-6. "Check of outdoor
thermistors".
4-time
fl
ash
Overcurrent
Once
Not
lighted
40 A current flows into intelligent power
module.
• Reconnect compressor connector.
• Refer to 11-6. "How to check in-
verter/compressor".
• Check the stop valve.
—
Out-of-step protection
9 times
Not
lighted
Waveform of compressor current is dis-
torted.
• Refer to 11-6. " How to check
inverter/compressor.
5-time
fl
ash
Discharge temperature
Lighted Lighted Discharge temperature exceeds 237.2°F
during operation.
Compressor can restart if discharge tem-
perature thermistor reads 212°F or less 3
minutes later.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6. "Check of LEV".
—
6-time
fl
ash
High pressure
Lighted Lighted High-pressure is detected with the high-
pressure switch (HPS) during operation.
• Check refrigerant circuit and refrig-
erant amount.
• Check the stop valve.
—
The outdoor heat exchanger temperature
exceeds 158°F during cooling or the
indoor gas pipe temperature exceeds
158°F during heating.
7-time
fl
ash
Fin temperature
3 times
Not
lighted
The fin temperature exceeds
:
230°F during
operation.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-6. "Check of outdoor
fan motor".
—
P.C. board temperature
4 times
Not
lighted
The P.C. board temperature exceeds
203°F during operation.
8-time
fl
ash
Outdoor fan motor
Lighted Lighted The fan motor speed is 50 rpm or less
or 1500 rpm or more for 1 minute, or the
fan motor speed is 100 rpm or less for 15
seconds when the outside temperature is
68°F or more.
• Refer to 11-6. "Check of outdoor
fan motor".
—
9-time
fl
ash
Nonvolatile memory data
Lighted 5 times Nonvolatile memory data cannot be read
properly.
• Replace the outdoor control P.C. board.
• Replace the outdoor power P.C. board.
○
10-time
fl
ash
Discharge temperature
Lighted Lighted The frequency of the compressor is kept
58Hz or more and the discharge tempera-
ture is kept under 122°F (cooling)/104°F
(heating) for more than 40 minutes.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6. "Check of LEV".
—
NOTE
: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4.).
OBH560G
Содержание MXZ-5B42NA
Страница 15: ...15 WIRING DIAGRAM 6 MXZ 2B20NA MXZ 2B20NA 1 OBH560G ...
Страница 16: ...16 MXZ 3B24NA MXZ 3B30NA MXZ 4B36NA OBH560G ...
Страница 17: ...17 MXZ 3B24NA 1 MXZ 3B30NA 1 MXZ 4B36NA 1 OBH560G ...
Страница 18: ...18 MXZ 5B42NA OBH560G ...