26
a
b
c
d
Outdoor
unit
Indoor
units
49ft.
33ft.
49ft.
e
Max.
Height
difference
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables
below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Outdoor unit union diameter
For
Indoor unit A
Liquid
1/4
Gas
1/2
Indoor unit B
Liquid
1/4
Gas
3/8
Indoor unit C
Liquid
1/4
Gas
3/8
Indoor unit D
Liquid
1/4
Gas
3/8
Indoor unit E
Liquid
1/4
Gas
3/8
Operating Range
MXZ-5B42NA
Cooling
Heating
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
95°FDB, 71°FWB
67°FDB, 57°FWB
80°FDB, 67°FWB
70°FDB, 60°FWB
Outdoor intake air temperature
115°FDB
14°FDB
75°FDB, 65°FWB
6°FDB, 5°FWB
Piping length each indoor unit (a, b, c, d, e, f)
82 ft.
Total piping length (a+b+c+d+e+f)
262 ft.
Bending point for each unit
25
Total bending point
80
MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION
MXZ-5B42NA
Unit : inch
OBH560G