3. Installation location
3.5.2. When installing a single outdoor unit
Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.
Refer to the figures for each case.
Obstacles at rear only (Fig. 3-5)
Obstacles at rear and above only (Fig. 3-6)
Obstacles at rear and sides only (Fig. 3-7)
Obstacles at front only (Fig. 3-8)
* When using the optional air outlet guides, the clearance is 19-11/16” (500 mm) or more.
Obstacles at front and rear only (Fig. 3-9)
* When using the optional air outlet guides, the clearance is 19-11/16” (500 mm) or more.
Obstacles at rear, sides, and above only (Fig. 3-10)
• Do not install the optional air outlet guides for upward airflow.
1�
2�
3�
4�
5�
6�
5-29/32
11-13/16
39-3/8
7-7/8
11-13/16
7-7/8
39-3/8
5-29/32
39-3/8
9-27/32
9-27/32
59-1/16
19-11/16
11-13/16
59-1/16
19-11/16
59-1/16
59-1/16
59-1/16
19-11/16
39-3/8
23-5/8
78-24/32
5-29/32
59-1/16
23-5/8
118-4/32
19-11/16
59-1/16
31-1/2
5-29/32
Fig. 3-6
Fig. 3-10
Fig. 3-11
Fig. 3-12
4
1
-
3
.
g
i
F
3
1
-
3
.
g
i
F
7
1
-
3
.
g
i
F
6
1
-
3
.
g
i
F
5
1
-
3
.
g
i
F
Fig. 3-9
Fig. 3-8
Fig. 3-7
Fig. 3-5
(inch)
3.5.3. When installing multiple outdoor units
Leave 1” (5 mm) space or more between the units.
Obstacles at rear only (Fig. 3-11)
Obstacles at rear and above only (Fig. 3-1)
• No more than 3 units must be installed side by side. In addition, leave space as shown.
• Do not install the optional air outlet guides for upward airflow.
Obstacles at front only (Fig. 3-13)
*
When using the optional air outlet guides, the clearance is 39-3/8” (1000 mm) or more.
Obstacles at front and rear only (Fig. 3-14)
* When using the optional air outlet guides, the clearance is 39-3/8” (1000 mm) or more.
Single parallel unit arrangement (Fig. 3-15)
*
When using the optional air outlet guides installed for upward airflow, the clearance is
39-3/8” (1000 mm) or more
.
Multiple parallel unit arrangement (Fig. 3-16)
* When using the optional air outlet guides installed for upward airflow, the clearance is
59-1/16” (1500 mm) or more.
Stacked unit arrangement (Fig. 3-17)
• The units can be stacked up to units high.
• No more than stacked units must be installed side by side. In addition, leave space as
shown.
1�
2�
3�
4�
5�
6�
7�
Max. 19-1
1/16
Max. 1
1-13/16
Max. 19-1
1/16
01_RG79D595H04_EN.indd 5