Outdoor model
MXZ-3F54VF
Outdoor unit power supply
Single phase
220 - 230 - 240 V, 50 Hz
System
Indoor units number
2 to 3
Piping total length
m
Max. 50
Connecting pipe length
m
Max. 25
Height difference (Indoor ~ Outdoor)
m
Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Height difference (Indoor ~ Indoor)
m
Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Function
Cooling
Heating
Capacity Rated frequency (Min.-Max.) 2
kW
5.4 (2.9 - 6.8)
7.0 (2.6 - 9.0)
Breaker capacity
A
25
Electrical
data
Power input (Total) 1, 2
W
1,320
1,400
Running current (Total) 1, 2
A
6.0 - 5.7 - 5.5
6.4 - 6.1 - 5.9
Power factor (Total) 1, 2
%
99
Starting current (Total) 1, 2
A
6.7
Coeffi cient of performance (C.O.P) (Total) 1, 2
4.09
5.00
Compressor
Model
SVB130FBBM1T
Output
W
1,400
Current 1, 2
A
5.06
Refrigeration oil (Model)
L
0.6 (FW68S)
Fan
motor
Model
SIC-82FX-F764-1
Current 1, 2
A
0.5
Dimensions W x H x D
mm
840 x 710 x 330
Weight
kg
57
Special
remarks
Air fl ow (Rated)
m
3
/h
1,860
1,632
Sound level (Rated)
dB(A)
46
50
Fan speed (Rated)
rpm
600
560
Pre-charged refrigerant quantity (R32)
kg
1.4
Max refrigerant quantity (R32)
kg
2.4
1 Measured under rated operating frequency.
2 When connected with indoor units below.
MSZ- MSZ- MSZ-LN18VG
NOTE:
Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m)
COOLING INDOOR
Dry-bulb temperature 27.0 °C Wet-bulb temperature 19.0 °C
OUTDOOR Dry-bulb temperature 35.0 °C Wet-bulb temperature 24.0 °C
HEATING INDOOR
Dry-bulb temperature 20.0 °C
OUTDOOR Dry-bulb temperature 7.0 °C Wet-bulb temperature 6.0 °C
OBH790
Содержание MXZ-2F33VF
Страница 22: ...22 OUTLINES AND DIMENSIONS 6 MXZ 2F33VF MXZ 2F42VF MXZ 2F53VF MXZ 2F53VFH Unit mm OBH790 ...
Страница 25: ...25 WIRING DIAGRAM 7 MXZ 2F33VF E1 ET1 MXZ 2F42VF E1 ET1 MXZ 2F53VF E1 ET1 OBH790 ...
Страница 26: ...26 MXZ 2F53VFH E1 OBH790 ...
Страница 27: ...27 MXZ 3F54VF E1 ET1 MXZ 3F68VF E1 ET1 OBH790 ...
Страница 28: ...28 MXZ 4F72VF E1 ET1 OBH790 ...
Страница 93: ...93 OBH790 ...