background image

En-1

1-2. SPECIFICATIONS

1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY

‡

 

%

e sure to read 

³

T

+

E FOLLOWIN

*

 S

+

OULD ALWA

<

%

E O

%

SER

9

ED FOR SAFET

 before installing the air conditioner.

‡

 

%

e sure to obser

Y

e the warnings and cautions speci

¿

ed here as they include important items related to safety.

‡

  After reading this manual, be sure to 

N

eep it together with the OPERATIN

*

 INSTRUCTIONS for future reference.

Required Tools for Installation

Phillips screwdri

Y

er

Le

Y

el

Scale
Utility 

N

nife or scissors

Torque wrench
Wrench (or spanner)

5/32 in. (4 mm) hexagonal 
wrench
Flare tool for R410A

*

auge manifold for R410A

9

acuum pump for R410A

Charge hose for R410A
Pipe cutter with reamer

 ENGLISH

CONTENTS

1. 

%

EFORE INSTALLATION ............................................................ 1

2. OUTDOOR UNIT INSTALLATION ............................................... 3
3. FLARIN

*

 WOR

.

 AND PIPE CONNECTION ............................... 5

4. PUR

*

IN

*

 PROCEDURES, LEA

.

 TEST, AND TEST RUN ......... 5

5. PU

0

PIN

*

 DOWN ........................................................................ 7

Model

Power supply

Pipe length and height difference *1, *2, *3, *4, *5, *6, *8

Rated 

9

oltage

Frequency

Max. pipe length per indoor unit / 

for multi-system

Max. height 

difference

Max. no. of bends per indoor unit / 

for multi system

Refrigerant 

adjustment A *7

MXZ-2C20NA2

208 / 230 

9

60 

+

z

82 ft. (25 m) / 164 ft. (50 m)

49 ft. (15 m)

25 / 50

1.08 oz each 5 ft. 

(20 g/m)

*1 Ne

Y

er use pipes with thic

N

ness less than speci

¿

ed. The pressure resistance 

will be insuf

¿

cient.

*2 Use a copper pipe or a copper-alloy seamless pipe.
*3 

%

e careful not to crush or bend the pipe during pipe bending.

*4 Refrigerant pipe bending radius must be 4 in. (100 mm) or more.
*5 Insulation material 

 

+

eat resisting foam plastic 0.045 speci

¿

c gra

Y

ity

*6 

%

e sure to use the insulation of speci

¿

ed thic

N

ness. Excessi

Y

e thic

N

ness may 

cause incorrect installation of the indoor unit and insuf

¿

cient thic

N

ness may 

cause dew drippage.

  Do not install the unit by yourself (user).

  Incomplete installation could cause 

¿

re or electric shoc

N

, injury due to the unit 

falling, or lea

N

age of water. Consult the dealer from whom you purchased the 

unit or a quali

¿

ed installer.

  Follow the instructions detailed in the installation manual.

  Incomplete installation could cause 

¿

re or electric shoc

N

, injury due to the unit 

falling, or lea

N

age of water. 

  When installing the unit, use appropriate protective equipment and tools 

for safety.

  Failure to do so could cause injury.

  Install the unit securely in a place that can bear the weight of the unit.

  If the installation location cannot bear the weight of the unit, the unit could fall 

causing injury.

■ 

Perform electrical work according to the installation manual and be sure to use 
an exclusive circuit. Do not connect other electrical appliances to the circuit.

  If the capacity of the power circuit is insuf

¿

cient or there is incomplete electrical 

wor

N

, it could result in a 

¿

re or an electric shoc

N

.

  Ground the unit correctly.

  Do not connect the ground wire to a gas pipe, water pipe, lightning rod or 

telephone ground. Defecti

Y

e grounding could cause electric shoc

N

.

■ 

Do not damage the wires.

  Damaged wires could cause 

¿

re.

■ 

Be sure to shut off the main power when setting up the indoor P.C. board 
or wiring.

  Failure to do so could cause electric shoc

N

.

 Use the speci

¿

ed wires to securely connect the indoor and outdoor units. 

Attach the wires 

¿

rmly to avoid applying stress to the terminal block.

  Improper connection could cause 

¿

re.

■ 

Do not install the unit in a place where 

À

ammable gas may leak.

  If gas lea

N

s and accumulates around the unit, it could cause an explosion.

  Do not use intermediate connection of the power cord or the extension 

cord. Do not connect many devices to one AC outlet.

  It could cause a 

¿

re or an electric shoc

N

.

■ 

Use the parts provided or speci

¿

ed parts for the installation work.

  The use of defecti

Y

e parts could cause an injury or lea

N

age of water due to a 

¿

re, an electric shoc

N

, the unit falling, etc.

■ 

When plugging the power supply plug into the outlet, make sure that there 
is no dust, blockage, or loose parts both in the outlet and on the plug. 
Verify that the power supply plug is completely in the outlet. 

  If there is dust, bloc

N

age, or loose parts on the power supply plug or the outlet, 

it could cause electric shoc

N

 or 

¿

re. If loose parts are found on the power supply 

plug, replace it.

■ 

Securely attach the electrical cover to the indoor unit and the service 
panel to the outdoor unit.

  If the electrical co

Y

er of the indoor unit and/or the ser

Y

ice panel of the outdoor 

unit are not attached securely, dust, water, etc. could collect in the unit and 
could cause a 

¿

re or an electric shoc

N

.

■ 

When installing, relocating, or servicing the unit, make sure that no substance 
other than the speci

¿

ed refrigerant (R

10A) enters the refrigerant circuit.

  Any presence of foreign substance such as air can cause abnormal pressure 

rise and may result in explosion or injury. The use of any refrigerant other than 
that speci

¿

ed for the system will cause mechanical failure, system malfunction, 

or unit brea

N

down. In the worst case, this could lead to a serious impediment 

to securing product safety.

■ 

Do not discharge the refrigerant into the atmosphere. Check that the 
refrigerant gas does not leak after installation has been completed. If 
refrigerant leaks during installation, ventilate the room.

  If refrigerant comes in contact with a 

¿

re, harmful gas could be generated. 

  If refrigerant gas lea

N

s indoors, and comes into contact with the 

À

ame of a fan 

heater, space heater, sto

Y

e, etc., harmful gases will be generated.

■ 

Use appropriate tools and piping materials for installation. 

  The pressure of R410A is 1.6 times higher than R22. Not using the appropri-

ate tools and materials, or improper installation could cause the pipes to burst 
causing an injury. 

■ 

When pumping down the refrigerant, stop the compressor before discon-
necting the refrigerant pipes.

  If the refrigerant pipes are disconnected while the compressor is running and 

the stop 

Y

al

Y

e is open, air could be drawn in and the pressure in the refrigera-

tion cycle could become abnormally high, causing the pipes to burst. 

■ 

When installing the unit, securely connect the refrigerant pipes before 
starting the compressor.

  If the compressor is started before the refrigerant pipes are connected and the 

stop 

Y

al

Y

e is open, air could be drawn in and the pressure in the refrigeration 

cycle could become abnormally high, causing the pipes to burst.

■ 

Fasten a 

À

are nut with a torque wrench as speci

¿

ed in this manual.

  If fastened too tight, a 

À

are nut could brea

N

 and cause refrigerant lea

N

age.

■ 

Install the unit  according to national wiring regulations.

  Be sure to install a Ground Fault Interrupt (GFI) circuit breaker.

  Failure to install a 

*

round Fault Interrupt (

*

FI) circuit brea

N

er may result in 

electric shoc

N

 or 

¿

re.

  Perform the drainage/piping work securely according to the installation manual.

  If there is defect in the drainage/piping wor

N

, water could drip from the unit, 

and damage household items.

  Do not touch the air inlet or the aluminum 

¿

ns of the outdoor unit.

  This could cause injury. 

  Do not install the outdoor unit where small animals may live.

  If small animals enter the unit and damage its electrical parts, it could cause a 

malfunction, smo

N

e emission, or 

¿

re. 

.

eep the area around the unit clean. 

 CAUTION

(Could lead to serious injury when operated incorrectly.)

 WARNING

(Could lead to death or serious injury, etc.)

1. BEFORE INSTALLATION

*7 If pipe length exceeds 131.2 ft. (40 m), additional refrigerant (R410A) charge 

is required. (No additional charge is required for pipe length less than 131.2 ft. 
(40 m).)

 

Additional refrigerant (ft.) = A × 

(pipe length (ft.) - 131.2)

5

  Additional refrigerant (m) = A × (pipe length (m) - 40)
*8 The  piping  speci

¿

cation table does not pro

Y

ide a minimum line set length. 

+

owe

Y

er, indoor units with connected piping length less than 10 ft. (3m) could 

produce intermittent noise during normal system operation in 

Y

ery quiet en

Y

i-

ronments. Please be aware of this important information when installing and 
locating the indoor unit within the conditioned space.

Содержание MXZ-2C20NA2

Страница 1: ...e l appareil extérieur Lors de l installation de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local Manual de instalación Para el INSTALADOR En este manual sólo se describe la instalación de la unidad exterior Para instalar la unidad interior consulte el manual...

Страница 2: ...kage or loose parts both in the outlet and on the plug Verify that the power supply plug is completely in the outlet If there is dust blocNage or loose parts on the power supply plug or the outlet it could cause electric shocN or re If loose parts are found on the power supply plug replace it Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the e...

Страница 3: ...Yided it is allowed to install the unit where obstacles are behind and on the sides of the unit No obstacle aboYe the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT SerYice space When installing the unit in an area that is enclosed with walls such as a Yerandah be sure to haYe enough space as shown below In this case the air conditioning capacity and power consumption might deteriorate When installi...

Страница 4: ... P9C hose 15 mm inner diameter or hard P9C pipe 9P16 for drain socNet 1 1 Note Place indoor outdoor unit connecting wire and power supply cord A at least 3 ft 1 m away from the T9 antenna wire The 4 ty for to in the aboYe table is quantity to be used per indoor unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 500 mm if the front and both sides are open More than 3 15 16 in 100...

Страница 5: ...E Use solid conductor Min AW 14 or stranded conductor Min AW 14 Use double insulated copper wire with 600 9 insulation Use copper conductors only Follow local electrical code POWER SUPPLY CABLE Use solid or stranded conductor Min AW 8 Use copper conductors only Follow local electrical code GROUND WIRE Use solid or stranded conductor Min AW 8 Use copper conductors only Follow local electrical code ...

Страница 6: ...em on pipe haYing completed burr remoYal Not possible to put them on after Àaring worN 4 Flaring worN Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A inch mm from the table according to the tool selected 5 ChecN Compare the Àared worN with Fig 6 If Àare is noted to be defectiYe cut off the Àared section and do Àaring worN again 1 PURGING PROCEDURES AND LEAK TEST 1 Remo...

Страница 7: ...er warm the gas cylinder with warm water under 104 F 40 C during cold season But neYer use naNed re or steam Union Stop YalYe Liquid pipe Indoor unit Stop YalYe with serYice port as pipe Refrigerant gas cylinder operating YalYe for R410A auge manifold YalYe for R410A Charge hose for R410A Refrigerant gas cylinder for R410A with siphon Electronic scale for refrigerant charging Refrigerant liquid Ou...

Страница 8: ... and piping combination When there is possibility of incorrect wiring and piping combination and con rming the combination is dif cult use this function to detect and correct the combination by following the procedures below MaNe sure that the following is done Power is supplied to the unit Stop YalYes are open Note During detection the operation of the indoor unit is controlled by the outdoor uni...

Страница 9: ...e la chute de l unité etc Lors du branchement de la che d alimentation dans la prise secteur véri ez qu aucune poussiqre saleté ni d élément desserré n est présent sur la prise et la che Veillez à enfoncer à fond la che d alimentation dans la prise secteur La présence de poussière de saleté ou d éléments desserrés sur la che d alimentation ou la prise secteur peut entraîner un choc électrique ou u...

Страница 10: ...me si des obstacles se trouvent derrière lui et d un c té ou de l autre Absence d obstacle au dessus de l appareil 19 11 16 500 ou plus 7 7 8 200 ou plus 13 25 32 350 ou plus 3 15 16 100 ou plus 6 Espace d entretien Laissez un espace pour les travaux d entretien comme indiqué sur l illus tration 3 15 16 100 ou plus 19 11 16 500 ou plus 3 15 16 100 ou plus Espace d entretien 13 25 32 350 ou plus 13...

Страница 11: ...a quan tité à utiliser pour l appareil intérieur Après le test de contr le des fuites appliquer soigneusement du maté riau isolant pour obstruer les trous Si la tuyauterie doit être xée sur un mur contenant des métaux de l étain p ex ou un treillis métal lique utiliser un morceau de bois traité d une épaisseur de 25 32 po 20 mm minimum entre le mur et la tuyauterie ou isoler la tuyauterie en lui a...

Страница 12: ...sif ou toronné min AW 8 Utiliser des conducteurs en cuivre uniquement Respecter le code électrique local AVERTISSEMENT Utiliser le câble de connexion conforme aux normes techniques pour raccorder les unités interne et externe et xer le câble fer mement sur la bloc de sortie de façon que le côté raccordement de ce dernier ne soit soumis à aucune contrainte extérieure Un raccordement incomplet ou un...

Страница 13: ...du climatiseur 9 Serrez le bouchon de l ouverture de service pour recréer les conditions d origine 10 Test de contr le des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une ne couche d huile réfrigérante sur les embouts évasés des tuyaux ainsi que sur les raccords de tuyau de l appareil extérieur 2 Alignez la partie médiane du tuyau sur les raccords de tuyau de l appareil extérieur et serrez les ...

Страница 14: ...ature inférieure à 104 F 40 C pendant la saison froide Ne jamais utiliser une Àamme vive ou de la vapeur pour effectuer cette opération Raccord Robinet d arrêt Conduite de liquide Raccord Appareil intérieur Vanne d arrêt avec port d entretien Conduit de gaz réfrigérant Vanne de fonction nement du cylindre de réfrigérant pour le R410A Jauge collectrice pour le R410A Conduite Àexible de chargement p...

Страница 15: ... en marche trop rapide Lorsque le compresseur s arrête le dispositif de protection contre la remise en marche à trop brève échéance s enclenche Le compresseur restera arrêté trois minutes avant de se remettre en marche a n de protéger le climatiseur Fonction de correction de câblage tuyauterie L appareil est équipé d une fonction qui permet de corriger les branchements de câblage et de tuyauterie ...

Страница 16: ...a toma podrta provocar incendios o descargas eléctricas Si el enchufe de alimentación presenta piezas sueltas sustit yalo Fije rmemente la cubierta de la instalación eléctrica a la unidad interior y el panel de servicio a la unidad exterior Si no se jan con rmeza la cubierta de instalación eléctrica de la unidad interior y el panel de servicio de la unidad exterior podrta acumularse polvo agua etc...

Страница 17: ...ión al viento se recomienda instalar una placa de Àectora en el lado de salida de aire de la unidad exterior Para instalar el aparato de aire acondicionado evite los lugares siguientes donde es mis probable que ocurran problemas Donde pueda haber una fuga de gas inÀamable Donde haya demasiado aceite para maquinaria En ambientes salobres como las zonas costeras Donde haya gas sulf rico como en zona...

Страница 18: ... 32 pulg 350 mm Mis de 3 15 16 pulg 100 mm Mis de 7 7 8 pulg 200 mm si hay obsticulos a ambos lados Después de la prueba de fugas aplique material aislante de modo que no queden huecos Cuando los tubos deban instalarse en una pared con contenido metilico placas de latón o rejillas metilicas ponga un trozo de madera tratada qutmicamente de 25 32 pulg 20 mm o mis de grosor entre la pared y los tubos...

Страница 19: ...Use nicamente conductores de cobre Siga la normativa eléctrica local ATENCIÓN Conecte las unidades interior y exterior con el cable de conexión norma lizado destinado a este n y sujete bien el cable al panel de terminales de modo que no quede tenso en la zona de conexiones del panel Una conexión y jación defectuosas podrían provocar un incendio Conecte los cables al número correspondiente de termi...

Страница 20: ...rdado 1 Retire la tapa de la abertura de servicio de la vilvula de retención situada en el lado de la tuberta de gas de la unidad exterior Inicialmente las vilvulas de retención estin completamente cerradas y cubiertas con sus tapas 2 Conecte la vilvula colectora de manómetro y la bomba de vacto al puerto de servicio de la vilvula de retención en el lado de la tuberta del gas de la unidad exterior...

Страница 21: ... C en las estaciones frtas Nunca utilice fuego o vapor Unión Vilvula de retención Tuberta de ltquido Unión Unión Unión Unidad interior Vilvula de reten ción con abertura de servicio Tuberta de gas Vilvula de acciona miento del cilindro de gas refrigerante para R410A Vilvula m ltiple del manómetro para R410A Manguera de carga para R410A Cilindro de gas refrigerante del R410A con sifón Balanza elect...

Страница 22: ... elevada Si esto ocurre utilice el recogedor de refrigerante para recoger todo el refrigerante del sistema y a continuación una vez que las unidades interior y exterior se hayan reubicado vuelva a recargar el sistema con la cantidad adecuada de refrigerante 7 Desactive el disyuntor Retire el medidor de presión y las tubertas de refrigerante Al bombear el refrigerante detenga el compresor antes de ...

Страница 23: ......

Страница 24: ...BH79A325H03 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: