84
No.
Symptom
Indication
Abnormal point / Con-
dition
Condition
Remedy
LED1(Red) LED2(Yellow)
21 'Outdoor unit
stops and
restarts
3 minutes
later' is
repeated.
11 times
Not lit
Low out side tempera-
ture protection(cooling)
The ambient became 10.4°F or less.
—
Low out side tempera-
ture protection(Heating)
The ambient became 1.4°F or less. (
0;=&&
&&1$0;=&&&&1$
)
The ambient became -18°F or less. (
0;=&
&&1$+=0;=&&&1$+=
)
22
13 times
Not lit
Outdoor fan motor
A failure occurs 3 consecutive times within 30
seconds after the fan gets started.
• Refer to 11-6. "Check of outdoor fan motor".
23
Lit
8 times
Current sensor protec-
tion
A short or open circuit is detected in the current
sensor during compressor operating.
• Replace the outdoor power P.C. board.
24
Lit
11 times
Communication
between P.C. boards
protection
Communication error occurs between the outdoor
control P.C. board and outdoor power P.C. board
for more than 10 seconds.
• Check the connecting wire between outdoor con-
trol P.C. board and outdoor power P.C. board.
25
Lit
12 times
Zero cross detecting
circuit protection (Out-
door power P.C. board)
Zero cross signal cannot be detected while the
compressor is operating.
• Replace the outdoor power P.C. board.
26 Outdoor unit
operates.
Once
Lit
Primary current protec-
tion
The input current exceeds 15.0 A (
MXZ-2C20NA2
)
18.4 A (
0;=&&&1$0;=&&
4C36NA2
)/26.8 A (
0;=&&&1$+=&1$
0;=&&&1$+=0;=&1$
).
These symptoms do not mean any abnormality of
the product, but check the following points.
&KHFNLILQGRRU¿OWHUVDUHFORJJHG
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short
cycled.
27
Twice
Lit
High pressure protec-
tion
The indoor gas pipe temperature exceeds 113°F
during heating.
Defrosting in cooling
The indoor gas pipe temperature falls 37.4°F or
below during cooling.
28
3 times
Lit
Discharge temperature
protection
The frequency of the compressor is kept 80 Hz or
more and the discharge temperature is kept under
122°F(COOL mode)/104°F(HEAT mode) for more
than 40 minutes.
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-6. "Check of LEV".
• Refer to 11-6. "Check of outdoor thermistors".
29
4 times
Lit
Low discharge
temperature protection
The frequency of the compressor is kept 80 Hz or
more and the discharge temperature is kept under
102.2°F for more than 20 minutes.
• Refer to 11-6. "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
30
5 times
Lit
Cooling high pressure
protection
The outdoor heat exchanger temperature exceeds
136.4°F during operation.
This symptom does not mean any abnormality of
the product, but check the following points.
&KHFNLILQGRRU¿OWHUVDUHFORJJHG
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
31
7 times
Lit
High
Low
Pressure bypass
valve
Cooling evaporating
temperature drop
prevention control
During cooling operation, the temperature of indoor
heat exchanger becomes 37.4°F or less within 1
hour after the compressor starts running, or it be-
comes less than 53.6°F - 60.8°F* later than that.
* It depends on the difference between the set
temperature and the room temperature.
(
0;=&&&1$+=0;=&1$
0;=&&&1$+=0;=&1$
)
This symptom does not mean any abnormality of
the product, but check the following points.
&KHFNWKHLQGRRU¿OWHUVDUHQRWFORJJHG
&KHFNWKHUHLVVXI¿FLHQWUHIULJHUDQW
• Check the indoor/outdoor unit air circulation is not
short cycled.
32
11 times
Lit
M-NET communication
error
M-NET adapter P.C. board detects an abnormality
in the communication error.
• Check the connecting wire between M-NET
adapter P.C. board and outdoor control P.C.
board, or terminal block.
33 Outdoor
unit
operates
normally.
7 times
Lit
High
Low
pressure bypass valve
High pressure protec-
tion control at startup of
heating operation
The room temperature is 75.2°F or more when 1 or
2 unit(s) start(s) the heating operation.
(
0;=&&&1$+=0;=&1$
0;=&&&1$+=0;=&1$
)
This symptom does not mean any abnormality of
the product.
High
Low
pressure bypass valve
Compressor oil temper-
ing control at startup of
heating operation
Both the following are true:
• The outside temperature is 28.4°F or less when
the heating operation is started.
• [(Discharge temperature) - (Indoor heat exchang-
er temperature)] < 9°F
(
0;=&&&1$+=0;=&1$
0;=&&&1$+=0;=&1$
)
34
8 times
Lit
Cooling evaporating
temperature
protection
During cooling operation, the temperature of
indoor heat exchanger becomes 44.6°F - 51.8°F*
or less within 1 hour after the compressor
starts running, or it becomes 48.2°F - 62.6°F* or
less later than that.
* It depends on the indoor unit type/model or the
difference between the set temperature and the
room temperature.
35
9 times
Lit
Inverter check mode
The unit is operated with emergency operation
switch.
—
36
Lit
Lit
Normal
—
—
NOTE
: 1. The location of LED is illustrated at the right figure. Refer to 11-7.1.
2. LED is lit during normal operation.
The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the blinking frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED1 LED2
Lit
Outdoor control P.C. board
(Parts side)
OBH702G
Содержание MXZ-2C20NA2-U1
Страница 19: ...19 MXZ 4C36NA MXZ 4C36NA2 Unit inch mm Lock nut Conduit plates Conduit connector OBH702G ...
Страница 21: ...21 MXZ 2C20NAHZ MXZ 2C20NAHZ2 Unit inch mm Lock nut Conduit connector Conduit plate OBH702G ...
Страница 24: ...24 MXZ 3C24NA MXZ 3C30NA OBH702G ...
Страница 25: ...25 MXZ 3C24NA2 MXZ 3C30NA2 OBH702G ...
Страница 26: ...26 MXZ 4C36NA OBH702G ...
Страница 27: ...27 MXZ 4C36NA2 OBH702G ...
Страница 29: ...29 MXZ 5C42NA2 OBH702G ...
Страница 30: ...30 MXZ 2C20NAHZ OBH702G ...
Страница 31: ...31 MXZ 2C20NAHZ2 OBH702G ...
Страница 32: ...32 MXZ 3C24NAHZ MXZ 3C30NAHZ OBH702G ...
Страница 33: ...33 MXZ 3C24NAHZ2 MXZ 3C30NAHZ2 OBH702G ...