No.
Item
Details
1
LEV control
Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.
❈
For the differential start-up, the LEV is controlled at 52 pulse for the first 15 minutes after
compressor stop.
There are 10 levels specified for standard LEV opening depending on the compressor operational
frequency. Based on these standard valves, the LEV opening is modified according to the suction
superheat, discharge temperature, and gas pipe temperature.
<LEV opening>
<Standard LEV opening by capacity code>
Standard LEV opening
30
Level 10
Level 09
Level 08
Level 07
Level 06
Level 05
Level 04
Level 03
Level 02
Level 01
40
50
60
70
80
90
100
110
120
Hysteresis width
=5Hz
< COMP Hz >
Non-opening indoor unit
Outdoor unit ON (Indoor unit ON) : 5 pulse
Outdoor unit OFF (Indoor unit OFF or
Thermostat OFF) : Before shutdown
Refer to the standard LEV opening as shown below.
From the initial valve, the LEV opening is controlled according
to suction superheat and the discharge temperature.
Refer to the standard LEV opening as shown below.
From the initial valve, the LEV opening is controlled according
to the suction superheat and the discharge temperature.
Thermostat ON in HEAT mode
LEV opening
Thermostat ON in DRY mode
Thermostat OFF in
COOL or DRY mode
Thermostat OFF in HEAT mode
All indoor units OFF
❈
52
➝
500 pulse
Indoor unit status
COOL : 5 pulse
HEAT : 59 pulse
COOL : 5 pulse
HEAT : 49 pulse
Refer to the standard LEV opening as shown below.
Thermostat ON in COOL mode
Before shutdown
➝
350 pulse
Outdoor unit ON (Indoor unit ON) : 5 pulse
Outdoor unit OFF (Indoor unit OFF
or Thermostat OFF) :
❈
52
➝
500 pulse
Outdoor unit ON (Indoor unit ON) : 49 pulse
Outdoor unit OFF (Indoor unit OFF or
Thermostat OFF) : Before shutdown
Outdoor unit ON (Indoor unit ON) : 5 pulse
Outdoor unit OFF (Indoor unit OFF
or Thermostat OFF) :
❈
52
➝
500 pulse
MXZ-18NV
MXZ-32NV
Capacity class
Level 01
Level 02
Level 03
Level 04
Level 05
Level 06
Level 07
Level 08
Level 09
Level 10
07,09
100/70
100/70
100/90
100/110
100/130
110/150
120/170
130/190
140/210
150/230
MXZ-32NV-E1,E2
12,13
130/90
130/90
130/110
130/130
130/150
140/170
150/190
160/210
170/230
180/250
12
255/90
255/90
255/90
255/90
255/90
255/100
255/110
255/120
255/130
255/140
MXZ-18NV-E1
09
100/70
100/70
100/70
100/70
100/70
110/80
120/90
130/100
140/110
150/120
07,09
255/70
255/70
255/70
255/70
255/70
255/80
255/90
255/100
255/110
255/120
18
145/100
145/100
145/120
145/140
145/160
155/180
165/200
175/220
185/240
195/260
MXZ-18NV-E2