8.4 EVACUATION PROCEDURES
MXZ-18NV -
MXZ-18NV -
E2
E1
CAUTION :
If you run this unit with air in its refrigerant pipe before air purge, the compressor will decline in cooling
capacity, which may result in trouble.
❶
. Connect the refrigerant pipes (both the liquid and gas pipes) between the indoor and the uotdoor units.
❷
. Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe.[ The stop valve
will not work in its initial atate fresh out of the factory (totally closed with cap on).]
❸
. Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the side
of the outdoor unit gas pipe.
❹
. Run the vacuum pump.
❺
. Check the vacuum with the gauge manifold valve, then close the gauge manifold valve, and stop the
vacuum pump.
❻
. Leave it as is for one or two minutes.Make sure the pointer of the gauge manifold valve remains in the
same position.
❼
. Remove the cape from the stop valves of the outdoor unit, liquid pipe, and gas pipe. Pull the handle
towards you with a finger. Turn it one fourth turn counterclockwise, to obtain the full-open position.
❽
. Remove the cape manifold valve quickly from the service port of the stop valve.
❾
. Tishten the cap to the service port to obtain the initial status.
❿
. Thrust the handle of the stop valve into the unit, then retighten the cap.
Leak test
.......
With a gas detector or soap water, check the flared nut connections for any refrigerant leak.
●
Retighten the flared nut connections.
●
If the leak does not stop even after retightening, repair the leaking point, collect all from inside the unit
through the service port, apply a vacuum to it, then charge a specified amount of gas with a gas cylinder.
Gauge manifold valve
Connect pipes
Vacuum pump
Service port
In case of a refrigerant leak