34
Primary current protection
Secondary current protection
High-pressure protection
Defrosting in cooling
3 times
Lighting
Discharge temperature
protection
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-6.
D
"Check of LEV".
• Refer to 11-6.
F
"Check of outdoor thermistors".
4 times
Lighting
Low discharge temperature
protection
• Refer to 11-6.
D
"Check of LEV".
• Check refrigerant circuit and refrigerant amount.
5 times
Lighting
Cooling high-pressure protection
This symptom does not mean any abnormality of the product,
but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
-
-
These symptoms do not mean any abnormality of the product,
but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
Twice
Lighting
Once
Lighting
The discharge temperature exceeds 100
:
during operation.
The frequency of the compressor is kept 80Hz or more and the discharge
temperature is kept under 39
:
for more than 20 minutes.
The outdoor heat exchanger temperature exceeds 58
:
during operation.
9 times
Lighting
Inverter check mode
Lighting
Lighting
Normal
The unit is operated with emergency operation switch.
-
The input current exceeds 15A.
The current of the compressor exceeds 15A.
The indoor gas pipe temperature exceeds 45
:
during heating.
The indoor gas pipe temperature falls 3
:
or below during cooling.
LED1(Red) LED2(Yellow)
Abnormal point / Condition
Correspondence
Indication
Condition
Outdoor unit
operates.
Outdoor unit
operates
No. Symptom
20
21
22
23
24
25
26
OB389F--2qxp 07.9.3 5:08 PM Page 34
Содержание MUZ-GA50VA
Страница 10: ...10 MUZ GA60VA E3 ...
Страница 53: ...53 ...