M How to check miswiring and serial signal error
Turn OFF inverter-controlled lighting equipment.
Turn OFF the power supply and then turn ON again.
Press EMERGENCY OPERATION switch.
•
•
•
A
Is serial signal
error indicated 6
minutes later?
B
Yes
Reinstall either the unit or the light
away from each other.
Attach a
fi
lter on remote control
receiving section of the indoor unit.
•
•
No
Turn the power supply OFF.
Is there rated voltage in the power supply?
Yes
No
Check for incorrect indoor-outdoor connecting wiring.
Check the power supply.
A
Is there rated voltage between outdoor terminal block S1 and S2?
No
Yes
Check for miswiring, broken wires, and loose
wire connection between the power supply
and outdoor terminal block S1 and between
the power supply and outdoor terminal block
S2.
Wait for 2 or more minutes after the power supply is turned on.
Touch S2 and S3 with tester probes and start the emergency operation.
When the emergency operation starts, does the rated voltage occur for 2
seconds between indoor terminal block S2 and S3?
Yes
Turn the power supply OFF.
Turn the power supply ON.
Wait for 2 or more minutes after the power supply
is turned ON. Touch CN202 and JPG with tester
probes and start the emergency operation.
During the emergency operation,
does DC (2V or more) occur for 2
seconds between CN202 and
JPG on the indoor electronic control
P.C. board?
No
Does the indoor POWER lamp
blink continuously 6 minutes after
the emergency operation starts?
No
Does the outdoor LED light up?
Replace the
indoor electronic
control P.C. board.
Replace the
indoor power P.C.
board.
Yes
Yes
Does the outdoor LED blink 6
times?
Yes
Con
fi
rm that the thermostat is OFF
and wiring is not loose.
No
Does DC (6V or more) occur
between indoor terminal block S2
and S3?
Yes
Replace the outdoor inverter P.C. board. 1
No
Turn the power supply OFF.
Replace the indoor power P.C.
board.
Start the emergency operation.
No
Yes
Repair completed.
Does DC (20V or more) occur
between indoor terminal block S2
and S3 ?
No
Yes
Replace the outdoor
inverter P.C. board. 1
Replace the indoor electronic
control P.C. board.
1.
Electric charge may remain immediately
after the power supply is turned OFF.
Perform the procedure after 3 minutes.
Replace the outdoor inverter P.C. board. 1
Turn the power supply ON.
Does the indoor POWER lamp
blink continuously 6 minutes after
the emergency operation starts?
Yes
No
Turn the power supply ON.
B
No
No
Was the indoor unit ever connected to
the Multi (MXZ) series and operated
(turned on)?
The connection information to the Multi series is stored
in the indoor unit. Refer to “Deleting the memorized
abnormal condition” described in 11-2.1 to clear the error
history. When the error history is being cleared, the con-
nection information also will be initialized. The indoor unit
will be compatible with a low-standby-power model after
initialization.
OK
Yes
MUZ-FH25/35
OBH624A