Outdoor unit does not operate at all, or stops immediately due to overcurrent.
Check of LEV (Expansion valve)
Check of current-limiting resistor
K
●
Check other electric parts in the main circuit together in the case of the defective current-limiting resistor.
Turn ON the power
supply and press
EMERGENCY
OPERATION switch of
the indoor unit.
Replace the power P.C.
board or the compressor.
Replace the power P.C.
board or the inverter P.C.
board.
Does the rush current
limiting relay(X64) work
properly? (Normally it
close 1 minutes after
outdoor unit power ON.)
Yes
No
No
No
Yes
Does the current-limiting resistor
(R64A or R64B) on the power P.C.
board short out? (Normal
resistance : 5
'
)
Replace the power P.C.board.
Replace the power P.C. board.
Does LED on the inverter
P.C. board light up?
L
Heating/Cooling does not work sufficiently.
Replace the LEV.
With remote controller set toward the indoor unit, press
OPERATE/ STOP(ON/ OFF) button and confirm one
beep tone.
LEV operates in full-opening
direction.
Is LEV properly fixed to the
expansion valve?
Ok
Do you hear the expansion
valve "click, click·······"?
Do you feel the expansion
valve vibrate on touching it ?
Does the resistance of LEV
have the characteristics?
Refer to 11-5.
Measure each voltage between connector pins
of CN724 on the inverter P.C. board.
1.Pin
3
(-) Pin
1
(+)
2.Pin
4
(-) Pin
1
(+)
3.Pin
5
(-) Pin
1
(+)
4.Pin
6
(-) Pin
1
(+)
Is there about 3~5V AC between each?
NOTE: Measure the voltage by an analog tester.
No
Yes
Yes
Yes
No
Replace the
expansion valve.
Yes
No
No
Properly fix the LEV to the
expansion valve.
Replace the
inverter P.C. board.
NOTE : After check of LEV, do the undermentioned
operations.
1. Turn OFF the power supply and
turn ON it again.
2. Press RESET button on the remote
controller.
Turn ON the power supply.
1
While pressing both OPERATION SELECT
button and TOO COOL button on the
remote controller at the same time,
press RESET button.
2
First, release RESET button.
And release the other two buttons since all LCD
in operation display section of the remote controller
is displayed after 3 seconds.
1
While pressing both OPERATION SELECT
button and TOO COOL button on the
remote controller at the same time,
press RESET button.
2
First, release RESET button.
And release the other two buttons since all LCD
in operation display section of the remote controller
is displayed after 3 seconds.
When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.