2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W
2.Blinking pattern when outdoor unit is abnormal:
Yes
(Blinks)
No
(OFF)
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
No beep
Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
Repeated cycle
W
1. Regardless of normal or abnormal, 2 short
beeps are emitted as the signal is received.
Does POWER lamp on the indoor
unit blink at the interval of 0.5 seconds?
W
2
Blinks: The outdoor unit is abnormal.
Beep sounds are emitted at the same
timing of the blinking of POWER lamp.
Deleting the abnormal condition
1
After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2
Press EMERGENCY OPERATION switch so that the memorized
abnormal condition is deleted.
3
Release the failure mode recall function according to "Releasing the
failure mode recall function" mentioned above.
Repair the defective parts.
Confirmation of abnormality presence
W
1
With the remote controller headed towards the indoor unit, press TOO COOL or TOO
WARM button to adjust the set temperature to 25
:
.
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
1
With the remote controller headed towards the indoor unit, press any button
that is not used in this failure mode recall function (e.g. TIMER button) .
OR
1
Turn OFF the power supply and turn ON it again.
2
Press RESET button of the remote controller.
The outdoor unit is abnormal.
Check the blinking pattern, and refer to confirm the
abnormal point(11-2.3.).
Make sure to check at least two consecutive blinking cycles.
W
2
Release the failure mode recall function according to the left
mentioned procedure.
Confirm that the remote controller is in the failure mode recall
function.
There is a possibility that the outdoor unit is abnormal.
Confirm the presence of abnormality according to the following procedures.
OB372--1qxp 05.1.17 15:29 Page 24