![Mitsubishi Electric MUZ-FA25VA-E1 Скачать руководство пользователя страница 44](http://html.mh-extra.com/html/mitsubishi-electric/muz-fa25va-e1/muz-fa25va-e1_service-manual_1810909044.webp)
27
ON
OFF
2.5-second OFF
2.5-second OFF
NOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.1.
2. LED lights up during normal operation.
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
Abnormal point/ Condition
When it consecutively occurs 3times that the compressor stops
for overcurrent protection or start-up failure protection within
1minute start-up.
When discharge temperature thermistor, fin temperature
thermistor, defrost thermistor, P.C. board temperature
thermistor or ambient temperature thermistor shorts or opens
during compressor running, compressor stops.
When nonvolatile memory data cannot be read properly,
compressor stops.
(When POWER lamp of the indoor unit lights up or flashes 7-time.)
When 14A(MUZ-FA25VA, MUZ-FA25VAH)/ 24A(MUZ-FA35VA,
MUZ-FA35VAH) current flows into intelligent power module,
compressor stops and restarts 3 minutes later.
When discharge temperature thermistor exceeds 116
:
,
compressor stops. Compressor can restart if discharge
temperature thermistor reads 100
:
or less 3 minutes later.
When temperature of fin temperature thermistor on the heat
sink exceeds 83
:
(MUZ-FA25VA, MUZ-FA25VAH)/ 82
:
(MUZ-
FA35VA, MUZ-FA35VAH) or temperature of P.C. board
temperature thermistor exceeds 85
:
(MUZ-FA25VA, MUZ-
FA25VAH)/ 81
:
(MUZ-FA35VA, MUZ-FA35VAH), compressor
stops and restarts 3 minutes later.
When indoor coil thermistor exceeds 70
:
in HEAT mode.
When the defrost thermistor exceeds 70
:
in COOL mode.
When current from power outlet exceeds 6.1A(MUZ-FA25VA,
MUZ-FA25VAH)/ 9.2A(MUZ-FA35VA, MUZ-FA35VAH),
compressor frequency lowers.
When indoor coil thermistor exceeds 55
:
in HEAT mode,
compressor frequency lowers.
When indoor coil thermistor reads 8
:
or less in COOL mode,
compressor frequency lowers.
When discharge temperature thermistor exceeds 111
:
,
compressor frequency lowers.
When discharge temperature has been 50
:
or less for 20
minutes.
No.
1
2
3
6
7
8
9
14
15
16
17
18
Symptom
LED indication
Detection method
Check point
Outdoor unit
does not
operate
'Outdoor unit
stops and
restarts 3
minutes later'
is repeated
Outdoor unit
operates
Outdoor unit
operates
1-time flash every
2.5 seconds
NOTE:
For abnormality
location, refer to
'Indoor
troubleshooting
check table'.
Refer to service
manual OB371.
2-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
1-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
Outdoor power
system
Outdoor
thermistors
Outdoor control
system
Overcurrent
protection
Discharge
temperature
overheat
protection
Fin temperature
/P.C. board
temperature
thermistor
overheat protection
High pressure
protection
Frequency drop by
current protection
Frequency drop by
high pressure
protection
Frequency drop by
defrosting in COOL
mode
Frequency drop by
discharge
temperature
protection
Low discharge
temperature
protection
· Check stop valve.
· Reconnect connector of compressor.
· Refer to 11-6.
A
"How to check
inverter/ compressor".
· Refer to 11-6.
C
"Check of intelligent
power module".
· Refer to 11-6.
G
"Check of outdoor
thermistors".
· Check stop valve.
· Reconnect connector of compressor.
· Refer to 11-6.
A
"How to check
inverter/compressor".
· Refer to 11-6.
C
"Check of
intelligent power module".
Replace inverter P.C. board.
· Check refrigerant circuit and
refrigerant amount.
· Refer to 11-6.
L
"Check of LEV".
· Check around outdoor unit.
· Check outdoor unit air passage.
· Refer to 11-6.
I
"Check of outdoor
fan motor".
· Check refrigerant circuit and
refrigerant amount.
· Check stop valve.
The unit is normal, but check the
following.
· Check if indoor filters are clogged.
· Check if refrigerant is short.
· Check if indoor/outdoor unit air
circulation is short cycled.
· Refer to 11-6.
L
"Check of LEV".
· Check refrigerant circuit and
refrigerant amount.
Inverter P.C. board (Parts side)
LED
Flashing
Refer to 11-6.
O
"How to check mis-
wiring and serial signal error.
When the communication failure between the indoor and
outdoor unit for 3 minutes.
serial signal
8-time flash
2.5 seconds OFF
Compressor
synchronous
abnormality
When the waveform of compressor current is distorted.
· Reconnect connector of compressor.
· Refer to 11-6.
A
"How to check
inverter/compressor".
· Refer to 11-6.
C
"Check of
intelligent power module".
8-time flash
2.5 seconds OFF
PAM protection
PAM:
Pulse
Amplitude
Modulation
When the overcurrent flows into IGBT(Insulated Gate Bipolar
transistor : TR821) or when the bus-bar voltage reaches 320V
or more, PAM stops and restarts.
This is not malfunction.
PAM protection will be activated in
the following cases;
1
Instantaneous power voltage drop
(Short time power failure)
2
When the power supply voltage is
high.
9-time flash
2.5 seconds OFF
Inverter check
mode
When the connector of compressor is disconnected, inverter
check mode starts.
Check if the connector of the
compressor is correctly connected.
Refer to 11-6.
A
"How to check
inverter/ compressor".
4
10
19
10-time flash
2.5 seconds OFF
Outdoor fan
6-time flash
2.5 seconds OFF
When outdoor fan has stopped within 30 seconds 3-times a
row after outdoor fan start-up, unit stops.
· Refer to 11-6.
I
"Check of outdoor
fan motor.
· Refer to 11-6.
N
"Check of inverter
P.C. board.
11
12
13
12-time flash
2.5 seconds OFF
Compressor each
phase current
When compressor each phase current cannot be detected
normally
· Refer to 11-6.
A
"How to check
inverter/compressor".
13-time flash
2.5 seconds OFF
DC voltage
When DC voltage of inverter cannot be detected normally.
· Check for short time power failure
by such as lightning strike.
· Refer to 11-6.
A
"How to check
inverter/compressor".
· Check refrigerant circuit and
refrigerant amount.
· Refer to 11-6.
L
"Check of
LEV".
· Refer to 11-6.
G
"Check of
outdoor thermistors".
Refer to 11-2.2. Flow chart of the
detailed outdoor unit failure mode
recall function.
When outdoor unit is failure.
Outdoor unit
(Other abnormality)
5
14-time flash
2.5 seconds OFF
0.5-second ON
0.5-second ON
11-4. Troubleshooting check table
OB372--1qxp 05.1.17 15:29 Page 27
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
www.ilmalämpöpumput.com