41
J Check of power supply
Is there voltage 230 V AC
between the indoor terminal
block S1 and S2?
No
Yes
Replace the indoor
electronic control P.C.
board.
Rectify indoor/outdoor
connecting wire.
Yes
If lights up, OK.
If blinks, refer to 12-3.
Does the upper OPERATION
INDICATOR lamp on the indoor unit
light up?
Does LED on the inverter P.C.
board light up or blink?
(Refer to 12-6.1.)
No
Replace the inverter
P.C. board.
Is there bus-bar voltage 260 - 370 V
DC between DB61 (+) and DB61 (–)
on the inverter P.C. board? (Refer
to 12-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between the
compressor and the power module
(IC700). Turn ON power supply and
press the emergency operation switch.
Inverter P.C. board
(Solder side)
DB61
260 - 370 V DC
OBH906A