7
Outdoor model
MUFZ-KW50VGHZ
MUFZ-KW60VGHZ
Power supply
Single phase, 230 V, 50 Hz
Capacity Rated (Min. - Max.)
Cooling
kW
5.0 (1.0 - 5.8)
6.1 (1.0 - 6.5)
Heating
6.0 (1.2 - 8.4)
6.5 (1.2 - 9.0)
Breaker Capacity
A
16
16
Electrical data
Power input *1 (Set)
Cooling
W
1,360
1,730
Heating
1,600
1,880
Running current *1 (Set)
Cooling
A
6.2
7.7
Heating
7.1
8.3
Power factor *1 (Set)
Cooling
%
95
97
Heating
97
98
Starting current *1 (Set)
A
7.1
8.3
Coefficient of performance
(COP) *1 (Set)
Cooling
3.67
3.52
Heating
3.75
3.45
Compressor
Model
SVB172FCKMT
Output
W
1,200
Current *1
Cooling
A
5.25
6.32
Heating
5.89
6.94
Refrigeration oil (Model)
L
0.40(FW68S)
Fan motor
Model
RC0J60-BC
Current *1
Cooling
A
0.68
0.83
Heating
0.74
0.84
Dimensions W × H × D
mm
840 × 880 × 330
Weight
kg
54
54
Special remarks
Dehumidification
Cooling
L/h
2.2
2.3
Airflow
Cooling
High
m
3
/h
2,628
2,928
Low
1,716
1,716
Heating
High
3,078
3,078
Medium
2,778
3,078
Low
2,280
2,280
Sound level *1
Cooling
dB(A)
50
52
Heating
54
56
Fan speed
Cooling
High
rpm
760
820
Low
450
450
Heating
High
860
860
Medium
800
860
Low
650
650
Fan speed regulator
3
Refrigerant filling capacity (R32)
kg
1.30
NOTE
: Test conditions are based on ISO 5151.
Cooling: Indoor
Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature 24°C
Heating: Indoor
Dry-bulb temperature 20°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
*1 Measured under rated operating frequency.
OBH895