14
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: m
Piping size O.D: mm
Max. Length A
Max. Height difference B
Gas
Liquid
MUFZ-KW25VGHZ
MUFZ-KW35VGHZ
20
12
9.52
6.35
MUFZ-KW50VGHZ
MUFZ-KW60VGHZ
30
15
12.7
6.35
ADDITIONAL REFRIGERANT CHARGE (R32: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
8 m
9 m 10 m 11 m 12 m 13 m 14 m 15 m 16 m 17 m 18 m 19 m 20 m
MUFZ-KW25VGHZ
MUFZ-KW35VGHZ
1,000
0
20
40
60
80
100
120
140
160
180
200
220
240
260
Calculation: X g = 20 g/m × (Refrigerant piping length(m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
8 m
9 m
10 m
15 m
20 m
25 m
30 m
MUFZ-KW50VGHZ
MUFZ-KW60VGHZ
1,300
0
20
40
60
160
260
360
460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
OBH895